© RESOL 11089 deltasol_c2.monen.ind
d
5
|
D e lt a S o l
®
C2
1
2
S1
S2
S3
3
4
5
6
L
N
R1
N
20
19
18
17
16
15
S4
7
8
14
13
12
1 (1) A (100 ... 240) V~
VBus
9
10
T2A
100 ... 240 V~
50-60 Hz
IP 20
Temp. Sensor Pt1000
1.2 Electrical connection
mains terminals
fuse
load terminals
sensor terminals
ground terminals
The power supply to the controller must be carried out via
an external power switch (last step!) and the supply voltage
must be 100 ... 240 V~ (50 ... 60 Hz). Flexible cables must be
attached to the housing with the enclosed strain relief and
the corresponding screws.
The controller is equipped with 1 relay to which
loads
such
as pumps, valves etc. can be connected:
• Relay 1
18 = conductor R1
17 = neutral conductor N
13 = ground clamp
The
temperature sensors
(S1 to S4) have to be con-
nected to the following terminals (either polarity):
1 / 2 = sensor 1 (e. g. sensor collector 1)
3 / 4 = sensor 2 (e. g. sensor store 1)
5 / 6 = Sensor 3 (temperature sensor S3)
7 / 8 = sensor 4 (e. g. sensor store TRF)
The
mains connection
is at the terminals:
19 = neutral conductor N
20 = conductor L
12 = ground clamp
The controller is equipped with the
RESOL VBus
®
for
data transfer with and energy supply to external modules.
The connection is carried out at the two terminals 9 and
10 marked “VBus
®
“ (either polarity). One or more RESOL
VBus
®
modules can be connected via this data bus:
• RESOL calorimeter
• RESOL large display / Smart Display
• RESOL datalogger
Electrostatic discharge can cause damage of electronic
components!
High-voltage components!
S1
S2
S4 / TRF
1.2.1 Terminal allocation
Standard solar system
with 1 store, 1 pump and 3
sensors. Sensor S4 / TRF can optionnally be used for heat
quantity measurement.
R1
S3
Symbol
Description
S1
collector sensor
S2
store base sensor
S3
store top sensor
(optional)
S4 / TRF
Sensor for heat quantity
measurement (optional)
R1
solar pump
Note:
The relay is a semiconductor relay for pump speed control.
The minimum pump speed must be set to 100% when au-
xiliary relays or valves are connected.
VBus