en
68
Installation
Indications,
functions and options
Messages
Commissioning
Operation and function
Code
The access to some adjustment values can be restricted via a user code (custom-
er).
1. Installer 0262 (Factory setting)
All menus and adjustment values are shown and all values can be altered.
2. Customer 0000
The installer level is not shown, adjustment values can be changed partly.
For safety reasons, the user code should generally be set to the customer code
before the controller is handed to the customer!
Î
In order to restrict the access, enter 0000 in the menu item CODE.
The display changes to the status level. The short menu shown will then be available
in the adjustment level. The short menu suits the selected system.
Î
In order to authorise access to the installer level, enter 0262 in the menu
item CODE.
Short menu
Channel
Factory
setting
Adjustment range
Designation
TIME
12:00
00:00 … 23:59
Time
DT O
6
1.0 … 50.0
Switch-on temperature difference store
DT F
4
0.5 … 49.5
Switch-off temperature difference store
DT S
10
1.0 … 50.0
Set temperature difference store
S MAX
60
4 … 95
Store maximum limitation
DT1O
6
1.0 … 50.0
Switch-on temperature difference store 1
DT1F
4
0.5 … 49.5
Switch-off temperature difference store 1
DT1S
10
1.0 … 50.0
Set temperature difference store 1
S1MAX
60
4 … 95
Store maximum limitation store 1
DT2O
6
1.0 … 50
Switch-on temperature difference store 2
DT2F
4
0.5 … 49.5
Switch-off temperature difference store 2
DT2S
10
1.5 … 50.0
Set temperature difference store 2
S2MAX
60
4 … 95
Store maximum limitation store 2
LST2
On
On / OFF
Loading store 2 on
MAN1
Auto
Auto / On / OFF / n LO / n HI Manual mode pump 1
MAN2
Auto
Auto / On / OFF / n LO / n HI Manual mode pump 2
MAN3
Auto
Auto / On / OFF / n LO / n HI Manual mode pump 3
MAN4
Auto
Auto / On / OFF
Manual mode pump 4
CODE
0000
0000 / 0262
User code
8 User code and short menu – Adjustment values
In the case of an error, the directional pad starts flashing red and a message is indi-
cated in the status display. A warning triangle is additionally indicated. If more than
one error or fault condition has occurred, only the one with the highest priority will
be displayed as a message in the status display.
Error message Value
Cause
Solution
FS1 … 7; FS6, 8
-88.8
Short circuit at sensor 1 … 7
Check the cable.
888.8
Broken cable at sensor 1 … 7
EVFS
9999
Error at Grundfos Direct Sensor
TM
VFS
Sensor fault. Check and, if necessary, correct the connection of the sensor plugs. If a sensor
signal does not appear, the sensor has to be replaced.
ERPS
9999
Error at Grundfos Direct Sensor
TM
RPS
ELEAK
Measured minimum pressure
Leakage error
Check the system for a leakage.
EPRES
Measured maximum pressure Pressure error
Check the functioning of the valves and pumps.
EFLOW
Flow rate error
Threshold values for VFS 1 - 10: 1.0 - 1.1 l/min
Threshold values for VFS 2 - 40: 2.0 - 2.1 l/min
Check the pump.
Check whether a flow rate exists.
PARAM
Remote parameterisation
Do not parameterise the controller via the push buttons during remote parameterisation.
After the error has been removed, the error message disappears.
In the case of a sensor error, the system is switched off, and a message appears on
the display marked by an “E”. Additionally, a corresponding value for the error type
assumed is indicated.
9 Messages