Installation
Indications,
functions and options
Messages
Commissioning
Operation and function
System 22: Solar system with store loading in layers and east-/west collectors
The controller compares the temperatures at the collector sensors S1 and S5
to the store temperature at sensors S2 and S3. If one of the measured temper-
ature differences is higher than the adjusted switch-on temperature difference,
the corresponding pump (R1 and/or R2) will be activated and the corresponding
store zone will be loaded up to the adjusted store maximum or set temperature
respectively via the valve (R3). The priority logic effects prior loading of the upper
zone of the store.
Sensors
S1
Temperature collector 1
1 / GND
S2
Temperature store base
2 / GND
S3
Temperature store top
3 / GND
S4
Free
4 / GND
S5
Temperature collector 2 5 / GND
Relay
R1
Solar pump collector 1
R1 / N / PE
R2
Solar pump collector 2
R2 / N / PE
R3
Solar valve
R3 / N / PE
R4
Free
R4 / N / PE
R3
R2
R1
S5
S2
S1
S3
Durchflussrichtung
im stromlosen Zustand
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PW
M
2
N
R4
V40
VBus GN
D
L'
VFS
RPS
Flow direction when
normally open