resideo SV9540 Installation Instructions Manual Download Page 14

SMARTVALVE™ SYSTEM CONTROLS

69-1059—01

14

4.

After LED flash code analysis and appliance repair are complete, turn the thermostat below room temperature 

for 10 seconds; turn the thermostat above room temperature to initiate a new call for heat.

5.

Observe the ignition sequence, comparing it to the Sequence of Operation shown in Fig. 12. Allow the new igni-

tion sequence to proceed until appliance lights or an abnormal or unexpected event is observed. See next sec-

tion.

Troubleshooting Without LED Indicator Assistance

Appliance power or thermostat call for heat has cycled since appliance failure occurred.

WARNING

LINE VOLTAGE POWER CAN CAUSE PRODUCT DAMAGE, SEVERE INJURY OR DEATH

Only a trained, experienced service technician should perform this troubleshooting.

1.

Make sure the appliance power is on and any manually operated gas cock on the appliance is open.

2.

Remove appliance burner compartment door. Confirm that SV9540; SV9640 LED indicator is flashing in a 

“bright -dim” sequence.

3.

Make sure the ignition system control switch is in the ON position.

4.

Disconnect the system thermostat leadwires at the ST9160 EFT or the 208907 Terminal Board.

5.

Using alligator clips on a short jumper wire, jumper the R and W terminals on the EFT or Terminal Board.

6.

Observe the appliance operation, comparing it to the Sequence of Operation shown in Fig. 12 . Allow the ignition 

sequence to proceed until the appliance lights or an abnormal or unexpected event is observed.

7.

Check the appliance as shown in the following table:

If

And

Check/Repair

Combustion air blower 

does not energize.

2 Flash code does not come on 30 

seconds after call for heat starts.

1. Combustion air blower wiring

2. Combustion air blower

Combustion air blower 

does not energize.

2 Flash code does come on 30 

seconds after call for heat starts.

1. Airflow proving switch stuck closed.

2. Airflow proving switch miswired or jumpered.

Combustion air blower is 

energized.

3 Flash code does not come on 

after 30 seconds.

Wait for the prepurge time to expire

3 Flash code comes on 30 

seconds after combustion 

air blower is energized.

Combustion air blower turns off.

1. Ignition system control switch must be in the ON 

position.

2. Airflow proving switch stuck in open position.

3. Airflow proving switch tubing and wiring

4. Obstructions or restrictions in appliance air intake 

or exhaust flue system that prevent proper 

combustion air flow.

Prepurge time has expired. HSI element does not glow red 

within 5 seconds.

1. Broken or damaged HSI element

2. Broken or damaged HSI element leadwires

3. SV9540; SV9640 failure to power HSI element.

HSI element is glowing 

red.

Pilot does not light during the 90 

second trial for ignition.

NOTE: HSI element will turn off for 

approximately 25 seconds during 

the 90 second trial for ignition.

1. Pilot tubing not purged of air [Intiate another 

ignition sequence with the R-W jumper to clear pilot 

tubing more quickly]

2. Inlet gas pressure too low for proper appliance 

operation.

3. Pilot burner improperly positioned in airflow

4. Clogged or incorrect pilot orifice.

5. Combustion air blower moving pilot gas away 

from HSI element.

Pilot lights during trial for 

ignition.

Main gas does not flow.

If pilot flame is not sensed during 

trial for ignition, main valve will not 

open. System will shut off HSI 

element and pilot gas flow, go 

through a 5 minute delay period, 

then initiate another ignition trial.

1. Line voltage to L1 terminal of ST9160 or Terminal 

Board must be 120 volts with reference to appliance 

chassis.

2. Appliance must be reliably connected to earth 

ground.

3. Combustion air blower moving pilot flame away 

from pilot burner flame rod.

4. Inlet gas pressure too low for proper flame 

sensing.

5. Flame sense rod contaminated or in incorrect 

location.

6. Wiring between SV9540; SV9640 and  pilot burner 

must be in good condition and properly connected.

Main burner lights.

Circulating air fan is not turned on 

after appropriate delay time

(systems with ST9160 Electronic 

Fan Timer only).

1. Wiring between SV9540; SV9640 and ST9160 EFT.

2. Proper operation of ST9160 EFT.

Summary of Contents for SV9540

Page 1: ... SV9540 SV9640 system is suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appli ances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 1 for temperature ranges and regulator types SPECIFICATIONS CAUTIO...

Page 2: ... straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 5 Flange kits include one flange with attached O ring four mounting screws a 9 64 in hex wrench and instructions Approvals International Approval Services IAS Design Certified C2030025 a Capacity based on 1000 Btu feet3 0 64 specific gravity natural gas at 1 in wc pressure drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 ...

Page 3: ...ere water can drip on the control In addition high ambient humidity can cause the control to corrode and fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check out the system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing a failure If chemicals are used for routine clean...

Page 4: ...393691 to convert from natural manufactured to LP gas order part no 394588 to convert from LP to natural manufactured gas IMPORTANT Ignition system controls with step opening regulators SV9540P SV9640P CANNOT be field converted to LP or natural gas Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose the appropriate flange for your appli...

Page 5: ...ds bare On LP installations use a compound resistant to LP gas See Fig 3 Fig 3 Use moderate amount of pipe compound 5 Remove the seals over the ignition system control inlet and outlet if necessary 6 Connect the pipe to the ignition system control inlet and outlet Use a wrench on the square ends of the ignition system control If a flange is used place the wrench on the flange rather than on the ig...

Page 6: ... fitting Wiring Follow the wiring instructions furnished by the appliance manufacturer if available or use the general instructions provided below When these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances Disconnect power supply before making wiring connec tions to prevent ele...

Page 7: ...UT SWITCH LIMIT SWITCH COMBUSTION AIR BLOWER AIR DATA NEUTRAL 1 2 ELECTRONIC AIR CLEANER CIRCULATING FAN HUMIDIFIER L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY THERMOSTAT R 24 VAC R C W Y Y G G ST9160 ELECTRONIC FAN TIMER Q3450 IGNITER SENSOR L1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR 120 VAC INSTALLATIONS CONNECT THE 120V HOT LEAD TO L1 ON ST9160 FOR 240 VAC ...

Page 8: ...S MUST HAVE RELIABLE CONNECTION TO EARTH GROUND 1 2 3 3 C1 C2 C3 40 VA TRANSFORMER L1 L2 LOAD COMMON THERMOSTAT 4 5 1 2 M12172 PRESSURE SWITCH NEUTRAL HOT L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY ROLL OUT SWITCH LIMIT SWITCH INDUCER BLOWER MOTOR R R W 24 VAC Q3450 IGNITER SENSOR AIR DATA SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR 120 VAC INSTALLA...

Page 9: ...ain burner while lighting to prevent injury caused from hidden leaks that could cause flashback in the appliance vestibule Light the main burner 4 With the main burner in operation paint the pipe joints including adapters and the control inlet and outlet with rich soap and water solution 5 If another leak is detected tighten the adapter screws joints and pipe connections 6 Replace the part if a le...

Page 10: ...upply at the manual valve in the gas piping to the appliance or for LP at the tank Also shut off gas supply before disconnecting manometer and replacing plug Repeat Gas Leak Test at plug with main burner operating NOTE Check the inlet pressure before adjusting the pressure regulator 1 Carefully check the main burner lightoff Make sure that the main burner lights smoothly and that all ports remain ...

Page 11: ... be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environment Since these environments can cause the gas control to deteriorate more rapidly the system should b...

Page 12: ...TER POST PURGE PILOT AND MAIN VALVES CLOSE COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT THREE SECOND FLAME FAILURE RECYCLE DELAY NO YES YES YES NO NO PILOT AND MAIN VALVES CLOSE YES NO YES NO M12234 SV9540 SV9640 INTERMITTENT PILOT SmartValve SYSTEM CONTROL SEQUENCE OF OPERATION WITH ST9160 ELECTRONIC FAN TIMER OR 208907 TERMINAL BOARD ...

Page 13: ...or jumpered 3 Flashes Airflow proving switch remains open longer than 30 seconds after combustion air blower energized System goes into 5 minute delay period with combustion air blower off At the end of the 5 minute delay another ignition cycle will begin 1 Ignition system control switch must be in the ON position 2 Airflow proving switch operation tubing and wiring 3 Obstructions or restrictions ...

Page 14: ...rgized 3 Flash code does not come on after 30 seconds Wait for the prepurge time to expire 3 Flash code comes on 30 seconds after combustion air blower is energized Combustion air blower turns off 1 Ignition system control switch must be in the ON position 2 Airflow proving switch stuck in open position 3 Airflow proving switch tubing and wiring 4 Obstructions or restrictions in appliance air inta...

Page 15: ... not smell gas continue with the next step 6 Move the ignition system control switch to the ON position 7 Replace the ignition system control access panel 8 Reconnect all electric power to the appliance 9 Set the thermostat to the desired setting 10 If the appliance does not turn on move the ignition system control switch to the OFF position and con tact a qualified service technician for assistan...

Page 16: ...es Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 1059 01 M S 03 21 Printed in United States ...

Reviews: