resideo SV9540 Installation Instructions Manual Download Page 10

SMARTVALVE™ SYSTEM CONTROLS

69-1059—01

10

reduce the pilot flow if necessary. The pilot adjustment is 

shipped at the full pilot gas flow rate. If pilot adjustment 

is necessary, proceed as follows:

1.

Remove pilot adjustment cover screw. See Fig. 4.

2.

Pilot adjustment is shipped at full flow rate. Turn 

the inner adjustment screw clockwise if the inlet 

pressure is too high. Turn the inner adjustment 

screw clockwise to decrease or counterclockwise 

to increase pilot flame.

3.

Replace the cover screw after the adjustment to 

prevent gas leakage.

Fig. 11. Proper flame adjustment.

Check and Adjust Gas Input and 
Burner Ignition

CAUTION

1. Do not exceed input rating stamped on 

appliance nameplate, or manufacturer’s 

recommended burner orifice pressure for size 

orifice(s) used. Make certain primary air supply 

to main burner is properly adjusted for 

complete combustion. Follow instructions of 

appliance manufacturer.

2. IF CHECKING GAS INPUT BY CLOCKING GAS 

METER: Make certain there is no gas flow 

through the meter other than to the appliance 

being checked. Other appliances must remain 

off with the pilots extinguished (or that 

consumption must be deducted from the meter 

reading). Convert flow rate to Btuh as 

described in form 70-2602, Gas Controls 

Handbook, and compare to Btuh input rating 

on appliance nameplate.

3. IF CHECKING GAS INPUT WITH MANOM-ETER: 

Make sure the ignition system control is in the 

OFF position before removing outlet pressure 

tap plug to connect manometer (pressure 

gauge). Also move the ignition system control 

switch to the OFF position when removing the 

gauge and replacing the plug. Before removing 

inlet pressure tap plug, shut off gas supply at 

the manual valve in the gas piping to the 

appliance or, for LP, at the tank. Also shut off 

gas supply before disconnecting manometer 

and replacing plug. Repeat Gas Leak Test at 

plug with main burner operating.

NOTE:

Check the inlet pressure before adjusting the 

pressure regulator.

1.

Carefully check the main burner lightoff. Make sure 

that the main burner lights smoothly and that all 

ports remain lit.

2.

Check the full rate manifold pressure listed on the 

appliance nameplate. Ignition system control full 

rate outlet pressure should match this rating.

3.

With main burner operating, check the ignition sys-

tem control flow rate using the meter clocking 

method or check pressure using a manometer con-

nected to the outlet pressure tap on the ignition 

system control. See Fig. 4.

4.

If necessary, adjust the pressure regulator to 

match the appliance rating. See Tables 7 and 8 for 

factory-set nominal outlet pressure and adjust-

ment range.

a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise to increase or counterclock-

wise to decrease the gas pressure to the 

burner.

c. Always replace the cap screw and tighten 

firmly to prevent gas leakage.

5.

If the desired outlet pressure or flow rate cannot be 

achieved by adjusting the ignition system control, 

check the ignition system control inlet pressure 

using a manometer at the ignition system control 

inlet pressure tap. If the inlet pressure is in the 

nominal range (see Tables 7 and 8), replace the 

ignition system control. Otherwise, take the neces-

sary steps to provide proper gas pressure to the 

control.

PROPER FLAME 

ADJUSTMENT

HOT SURFACE

IGNITER

FLAME ROD

M3350A

GROUND

ELECTRODE

3/8 TO 1/2 IN.

(10 TO 13 MM)

NOTE: GROUND ELECTRODE MUST NOT TOUCH FLAME

ROD (.050 IN. MINIMUM CLEARANCE). BEND GROUND

ELECTRODE IF NECESSARY. DO NOT BEND FLAME ROD.

Summary of Contents for SV9540

Page 1: ... SV9540 SV9640 system is suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appli ances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 1 for temperature ranges and regulator types SPECIFICATIONS CAUTIO...

Page 2: ... straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 5 Flange kits include one flange with attached O ring four mounting screws a 9 64 in hex wrench and instructions Approvals International Approval Services IAS Design Certified C2030025 a Capacity based on 1000 Btu feet3 0 64 specific gravity natural gas at 1 in wc pressure drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 ...

Page 3: ...ere water can drip on the control In addition high ambient humidity can cause the control to corrode and fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check out the system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing a failure If chemicals are used for routine clean...

Page 4: ...393691 to convert from natural manufactured to LP gas order part no 394588 to convert from LP to natural manufactured gas IMPORTANT Ignition system controls with step opening regulators SV9540P SV9640P CANNOT be field converted to LP or natural gas Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose the appropriate flange for your appli...

Page 5: ...ds bare On LP installations use a compound resistant to LP gas See Fig 3 Fig 3 Use moderate amount of pipe compound 5 Remove the seals over the ignition system control inlet and outlet if necessary 6 Connect the pipe to the ignition system control inlet and outlet Use a wrench on the square ends of the ignition system control If a flange is used place the wrench on the flange rather than on the ig...

Page 6: ... fitting Wiring Follow the wiring instructions furnished by the appliance manufacturer if available or use the general instructions provided below When these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances Disconnect power supply before making wiring connec tions to prevent ele...

Page 7: ...UT SWITCH LIMIT SWITCH COMBUSTION AIR BLOWER AIR DATA NEUTRAL 1 2 ELECTRONIC AIR CLEANER CIRCULATING FAN HUMIDIFIER L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY THERMOSTAT R 24 VAC R C W Y Y G G ST9160 ELECTRONIC FAN TIMER Q3450 IGNITER SENSOR L1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR 120 VAC INSTALLATIONS CONNECT THE 120V HOT LEAD TO L1 ON ST9160 FOR 240 VAC ...

Page 8: ...S MUST HAVE RELIABLE CONNECTION TO EARTH GROUND 1 2 3 3 C1 C2 C3 40 VA TRANSFORMER L1 L2 LOAD COMMON THERMOSTAT 4 5 1 2 M12172 PRESSURE SWITCH NEUTRAL HOT L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY ROLL OUT SWITCH LIMIT SWITCH INDUCER BLOWER MOTOR R R W 24 VAC Q3450 IGNITER SENSOR AIR DATA SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR 120 VAC INSTALLA...

Page 9: ...ain burner while lighting to prevent injury caused from hidden leaks that could cause flashback in the appliance vestibule Light the main burner 4 With the main burner in operation paint the pipe joints including adapters and the control inlet and outlet with rich soap and water solution 5 If another leak is detected tighten the adapter screws joints and pipe connections 6 Replace the part if a le...

Page 10: ...upply at the manual valve in the gas piping to the appliance or for LP at the tank Also shut off gas supply before disconnecting manometer and replacing plug Repeat Gas Leak Test at plug with main burner operating NOTE Check the inlet pressure before adjusting the pressure regulator 1 Carefully check the main burner lightoff Make sure that the main burner lights smoothly and that all ports remain ...

Page 11: ... be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environment Since these environments can cause the gas control to deteriorate more rapidly the system should b...

Page 12: ...TER POST PURGE PILOT AND MAIN VALVES CLOSE COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT THREE SECOND FLAME FAILURE RECYCLE DELAY NO YES YES YES NO NO PILOT AND MAIN VALVES CLOSE YES NO YES NO M12234 SV9540 SV9640 INTERMITTENT PILOT SmartValve SYSTEM CONTROL SEQUENCE OF OPERATION WITH ST9160 ELECTRONIC FAN TIMER OR 208907 TERMINAL BOARD ...

Page 13: ...or jumpered 3 Flashes Airflow proving switch remains open longer than 30 seconds after combustion air blower energized System goes into 5 minute delay period with combustion air blower off At the end of the 5 minute delay another ignition cycle will begin 1 Ignition system control switch must be in the ON position 2 Airflow proving switch operation tubing and wiring 3 Obstructions or restrictions ...

Page 14: ...rgized 3 Flash code does not come on after 30 seconds Wait for the prepurge time to expire 3 Flash code comes on 30 seconds after combustion air blower is energized Combustion air blower turns off 1 Ignition system control switch must be in the ON position 2 Airflow proving switch stuck in open position 3 Airflow proving switch tubing and wiring 4 Obstructions or restrictions in appliance air inta...

Page 15: ... not smell gas continue with the next step 6 Move the ignition system control switch to the ON position 7 Replace the ignition system control access panel 8 Reconnect all electric power to the appliance 9 Set the thermostat to the desired setting 10 If the appliance does not turn on move the ignition system control switch to the OFF position and con tact a qualified service technician for assistan...

Page 16: ...es Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 1059 01 M S 03 21 Printed in United States ...

Reviews: