6.2 For LED Model
The following guideline may be helpful for basic problem solving.
No.
UPS STATUS
ACTION
1
AC utility power is normal. UPS is
running normally, but battery capacity
is low. Buzzer beeps once every
second for battery low.
Charger may broke down.
Please replace charger
board.
2
AC utility power is normal. The output
load is supplied through bypass of AC
utility. Fault LED lits up and buzzer
beeps continuously.
Please contact your agent
for service.
3
AC utility power is normal but UPS is
overloaded. Warning LED lits up and
buzzer beeps per second.
Please reduce the critical
load to <100%.
4
AC utility power is normal but UPS is
overloaded up to 125%. Warning LED
does not fade out and buzzer beeps
per 0.5 second.
Please reduce the critical
load to <100%.
5
AC utility power is normal, but the load
is supplied by AC utility power via
bypass. Output power is more than
150%. Warning LED lits up and buzzer
beeps continuously.
Please reduce the critical
load to <100%.