5. Output and bypass setting
Just connect the AC power (don't need to turn on the UPS) and the LCD
will light up with the welcome slogan (initial) screen. Then press the
Down-key to find the screen and then press Enter-key for setting. Once
finished, please disconnect the AC power and then reconnect power
again to refresh the setting.
Bypass Range Set
A. To protect the load, the function of
bypass auto-transfer is activated only
when the AC main voltage is within
the range of LO (low) and HI(high). In
this screen, press Enter-key to enter
the following steps for LO/HI voltage
setting.
B. The cursor (
→
) will pop up to
indicate the item newly selected.
Press Enter-key to get the item of
LO or HI range the user want to
adjust.
C. Use Up or Down-key to adjust the
voltage (changing 1V by every
press). LO (low rang):176V+/- 20V,
HI(high range):253V+/- 20V).
D. Once the value is confirmed, press
Enter-key again to save the data.