SHIPPING, RIGGING, LIFTING AND ASSEMBLY: LE MODELS

RENEWAIRE.COM

  

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

1.800.627.4499

24

UNIT DIMENSIONS

7.3 LE8XINH DIMENSION DRAWING

7.4 LE8XINV DIMENSION DRAWING

FOR 

THE MOST COMPLETE 

AND CURRENT INFORMA

TION 

VISIT  

RENEW

AIRE.COM 

LE-SERIES

109

5" Damper

Frames Typ.

  80 3/8" Overall  

  4"  

  2"  

   2" Typ.  

  69 1/4" Case  

CL 73 3/8"

Lift Lugs

CL 2 1/4"

Wiring

Pressure 

Ports (4) Typ.

  41 5/8"  

  27 3/8"  

  27 3/8"  

8 7/8"  Typ.

  161 3/8" Case  

  164 7/8" Overall  

OA Inlet

48" X 24" 

Duct Receiving

Flange 

RA Inlet

48" X 24" 

Duct Receiving

Flange 

OA Damper

Location

(Optional)

RA Damper

Location

(Optional)

  29 5/8"  

  53 1/2"  

  27 3/4"  

  64 5/8"  

  41 1/8"  

  27 3/4"  

  69 5/8" Case  

  71 1/8" Overall  

78 1/2" Minimum Blower Service Area Typ.

111" Minimum

Service Area

69 3/4"

Minimum

Service Area

36" E-Box

Minimum

Service Area

CL 5 1/4"

(2)  7/8"

Knockouts

CL 11 3/8"

(5)   1 1/8

Knockouts

48" X 24"

Duct Receiving

Flange Typ.

13 3/8" X 15 1/2"

Electrical 

Connection

Cover

E-Box

Disconnect 

Switch

Door

Swing

Door

Swing

Door

Swing

Door

Swing

RA

EA

FA

OA

FRONT VIEW

RIGHT VIEW

LEFT VIEW

TOP VIEW

FA

OA

RA

EA

Model: LE8XINH

Drawing Type: Unit Dimension

Version: MAY18

ABBREVIATIONS

EA: Exhaust Air to outside

OA: Outside Air intake

RA: Room Air to be exhausted

FA: Fresh Air to inside

INSTALLATION ORIENTATION

Unit must be installed in orientation

shown.

NOTE

1.UNLESS OTHERWISE SPECIFIED, 

DIMENSIONS ARE ROUNDED TO THE

NEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECT

TO CHANGE WITHOUT NOTICE.
3.MIN. DUCT CLEARANCE FROM 

DAMPER BLADES WHEN FULLY

OPENED TO BE 2". SMACNA RULES 

APPLY.

LE8X

INH

   Energy Recovery Ventilator  

Standard

AIRFLOW CONFIGURATION

Available as shown in dimension drawing.

UNIT MOUNTING & APPLICATION

Must be mounted as shown. RA/EA airstream can 

be switched with OA/FA airstream unless certain 

options are selected.

FOR 

THE MOST COMPLETE 

AND CURRENT INFORMA

TION 

VISIT  

RENEW

AIRE.COM 

LE-SERIES

111

  4"  

   2" Typ.  

2" Duct 

Flange Typ.

5" Damper

Frames Typ.

  69 1/4" Case  

CL 73 3/8"

Lift Lugs

  81 1/2" Overall  

CL 2 1/4"

Wiring

Pressure 

Ports (4) Typ.

41 3/4" Typ.

  26 1/4"  

  27 5/8"  

9" Typ.

  161 3/8" Case  

  164 7/8" Overall  

OA Inlet

48" X 24" 

Duct Receiving

Flange

 

48" X 24"

Duct Receiving

Flange Typ.

OA Damper

Location

(Optional)

  29 5/8"  

  53 1/2"  

  69 5/8" Case  

  71 1/8" Overall  

  26 1/4"  

  27 3/4"  

  64 5/8"  

78 1/2"

Minimum Blower

Service Area 

111" Minimum

Service Area

69 3/4" Minimum

Service Area

36" E-Box

Minimum

Service Area

CL 5 1/4"

(2)  7/8"

Knockouts

CL 11 3/8"

(5)   1 1/8

Knockouts

34"

Minimum

Service Area

13 3/8" X 15 1/2"

Electrical 

Connection

Cover

E-Box

Disconnect 

Switch

RA Inlet

48" X 24" 

Duct Receiving 

Flange

RA Damper

Location

(Optional)

Door

Swing

Door

Swing

Door

Swing

Door

Swing

RA

EA

FA

OA

FRONT VIEW

RIGHT VIEW

LEFT VIEW

TOP VIEW

FA

OA

RA

EA

Model: LE8XINV

Drawing Type: Unit Dimension

Version: MAY18

ABBREVIATIONS

EA: Exhaust Air to outside

OA: Outside Air intake

RA: Room Air to be exhausted

FA: Fresh Air to inside

INSTALLATION ORIENTATION

Unit must be installed in orientation

shown.

NOTE

1.UNLESS OTHERWISE SPECIFIED, 

DIMENSIONS ARE ROUNDED TO THE

NEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECT

TO CHANGE WITHOUT NOTICE.
3.DUCT CLEARANCE FROM DAMPER 

BLADES WHEN FULLY OPENED TO BE 

2". SMACNA RULES 

APPLY.

LE8X

INV 

  Energy Recovery Ventilator  

Standard

AIRFLOW CONFIGURATION

Available as shown in dimension drawing.

UNIT MOUNTING & APPLICATION

Must be mounted as shown. RA/EA airstream can 

be switched with OA/FA airstream unless certain 

options are selected.

Summary of Contents for LE-8X*INH Series

Page 1: ...SHIPPING RIGGING HOISTING AND ASSEMBLY MANUAL ENERGY RECOVERY VENTILATORS RENEWAIRE COM LE6X LE8X LE10X...

Page 2: ...ll lifting lugs provided must be used Never lift the unit or modules from the top of the unit This unit is intended for general ventilating only Do not use to exhaust hazardous or explosive materials...

Page 3: ...ATION AND MAINTENANCE MANUAL RENEWAIRE COM OWNER INFORMATION IMPORTANT USER INFORMATION SAVE THIS MANUAL In the unlikely event that factory assistance is ever required information located on the unit...

Page 4: ...OODS 16 4 8 INSTALL MERV 8 FILTERS 17 5 0 ROOFTOP CURB DIMENSIONS 18 5 1 LE6XRT CURBS 18 5 2 LE8XRT CURBS 18 5 3 LE10XRT CURBS 19 6 0 ROOFTOP UNIT DIMENSIONS 20 6 1 LE6XRTH F DIMENSION DRAWING 20 6 2...

Page 5: ...ations 11 LE Rooftop Unit Base Bolt Locations 11 Alignment Spacer Bolt Location 11 Roof Beam Assembly Graphic 2 12 Roof Beam Assembly Graphic 1 12 Roof Beam Assembly Bolt Locations 12 Roof Cap Caulkin...

Page 6: ...Shipping Location typ Hoods are assembled at the factory and then secured for shipment inside the ERV LE models can be delivered in two modules for on site assembly or as a complete unit additional c...

Page 7: ...clearance between the cables and the cabinet or any of the equipment attached to the unit or modules Provide additional blocking or covering as required Secure hooks and cables at all lifting points...

Page 8: ...AND MAINTENANCE MANUAL 1 800 627 4499 8 RIGGING www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewa...

Page 9: ...ed unassembled for applications where modules must be manipulated separately If the unit was ordered unassembled then you will need to assemble the modules in the field Each module is labeled with a c...

Page 10: ...disposed of along with the screws that held them in place www renewaire com 800 627 4499 support renewaire com Apply 1 2 X 1 gasket tape provided as shown below Gasket tape creates an airtight seal be...

Page 11: ...N or base supports LE RT of the two adjacent modules Use 3 8 washers between the bolt head and the unit and between the nut and the unit Fasten the nuts to the bolts secure the bases of the two module...

Page 12: ...nsert 1 4 20 x 1 00 Grade 5 zinc plated hex head bolts through the holes in the roof beam Secure the nuts to secure the roof section www renewaire com 800 627 4499 support renewaire com AFTER THE LIFT...

Page 13: ...ewaire com A galvanized cap roof flange is provided to seal the roof seam and to maintain a water and airtight seal The cap roof flange is provided with pre drilled holes 12 X 75 hex head tek screw w...

Page 14: ...l not to over tighten the screw www renewaire com 800 627 4499 support renewaire com Two 2 galvanized roof cap ends are provided to seal the top end of each module and maintain a water and airtight se...

Page 15: ...n the electrical connection cover on the E Box side of the front module by removing screws in the access panel The access panel is located in the upper left corner of the front module to the left of t...

Page 16: ...4499 support renewaire com www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com Slide the top flange of the OA air hood beneath the roof panel over...

Page 17: ...that when filters are installed the filter spacers may tend to fall off the end of the filter receiving channels If this happens simply install the spacers between the first two filters in from the d...

Page 18: ...EA FA RTV 16 1 8 X 19 1 2 Opening 115 1 4 O D 64 1 4 O D 3 60 1 2 I D 17 1 4 33 20 25 9 1 2 A A TOP VIEW CURB LE6X FA RA LEFT VIEW Model LE6X RTV RTR Drawing Type Unit Dimension Version MAY18 LE6XRT...

Page 19: ...Lugs 4 111 1 4 Overall 69 1 8 Case 2 Typ 2 Duct Flange Typ C L 2 1 4 Wiring Pressure Ports 4 Typ 4 1 2 37 7 8 44 5 8 69 5 8 Case 71 1 8 Overall 29 5 8 53 1 2 47 1 4 84 5 8 9 C L 5 1 4 2 7 8 Knockouts...

Page 20: ...ard AIRFLOW CONFIGURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x L...

Page 21: ...CONFIGURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x LERT RTR RENE...

Page 22: ...GURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x LERT RTR RENEWAIRE...

Page 23: ...ator Standard AIRFLOW CONFIGURATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain optio...

Page 24: ...GURATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain options are selected FOR THE MOS...

Page 25: ...ATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain options are selected FOR THE MOST C...

Page 26: ...CORNER WEIGHTS AT LIFTING LUGS BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2086 579 580 464 463 2100 583 585 466 465 2218 625 630 483 480 5 HP 7 5 HP Options UNIT LF LR RR RF ADDITIONAL WEIGHT...

Page 27: ...X INH Front Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 119 5 Lifting Lug CORNER WEIGHTS AT LIFTING LUGS BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 1984 569 433 424 558 19...

Page 28: ...ng LE 8XRT_CORNER LE 8X RT Fron Corner Weigh 73 5 Lifting Lug LR RR LF RF 159 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2625 753 680 568 624 2645 745 737 578 585 2763 790 780 5...

Page 29: ...ing LE 8X INH Front Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 159 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2495 727 524 521 723 2509 733 524 522 730 2627...

Page 30: ...ro Corner Weigh LE10X RT_CORNE 73 5 Lifting Lug LR RR LF RF 194 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 3031 842 841 674 674 3045 847 846 676 676 3163 892 890 690 691 5 HP 7...

Page 31: ...nt Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 194 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2859 819 665 616 759 2873 825 666 617 765 2990 874 676 628 812...

Page 32: ...ulting in significant energy savings Our ERVs are competitively priced simple to install easy to use and maintain and have a quick payback They also enjoy the industry s best warranty with the lowest...

Reviews: