RenewAire LE-8X*INH Series Shipping, Rigging, Hoisting And Assembly Manual Download Page 2

SHIPPING, RIGGING, LIFTING AND ASSEMBLY: LE MODELS

RENEWAIRE.COM

  

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

1.800.627.4499

2

 

IMPORTANT SAFETY INFORMATION

 

           

WARNING

RISK OF DEATH 0R SERIOUS INJURY

Hoisting heavy equipment overhead is inherently dangerous. 

Failure to properly rig the ERV for hoisting or the use of incorrect 

rigging equipment may result in the ERV falling during hoisting.

Improper work procedures may result in death or serious injury 

to workers. Rigging, hoisting and assembly are to be performed 

by skilled and experienced personnel. OSHA-approved work 

guidelines are to be strictly followed. 

Before proceeding with installation, read all instructions, 

verifying that all the parts are included.

The information in this manual is provided as a guideline and 

does not neccessarily meet all local codes. It is the installer’s 

responsibility to comply with all local codes and OSHA-approved 

safety practices.

RISK OF DAMAGE TO ENTHALPIC CORES

Whenever working within the ERV cabinet, protect the enthalpic 

cores from accidental damage. The core media is subject to 

damage from dropped tools or other foreign objects. 

RISK OF DAMAGE TO ERV CABINET

Incorrect lifting can cause damage to the unit. 

Do not lift joined unit by the 4 corner lifting lugs only.  Secure 

lifting cables to the center lifting lugs also.

All lifting lugs provided must be used.  Never lift the unit or 

modules from the top of the unit.

This unit is intended for general ventilating only. Do not use to 

exhaust hazardous or explosive materials and vapors. Do not 

connect this equipment to range hoods, fume hoods or collection 

systems for toxics.

This unit is for ventilating finished structures only. It is not to 

be used until after all construction has been completed and 

construction debris and dust are cleaned from the Occupied 

Space. 

Do not lift joined unit by the 4 corner lifting lugs only.  Secure 

lifting cables to the center lifting lugs also.

All lifting lugs provided must be used.  Never lift the unit or 

modules from the top of the unit.

Incorrect lifting can cause damage to the unit.

This equipment is to be installed by following Industry Best 

Practices and all applicable codes. Any damage to components, 

assemblies, subassemblies or the cabinet which is caused by 

improper installation practices will void the warranty.

NOTICE

NOTICE

NOTICE

NOTICE

NOTICE

NOTICE

IMPORTANT

IMPORTANT

If this unit is installed in an area where it may draw air from 

a nearby fuel-burning device such as a gas furnace or water 

heater, verify that the air being extracted by the ERV does not 

conflict with proper operation of the fuel-burning device.

This unit can be delivered in two modules for on-site assembly 

or as a completely assembled unit (additional charges apply).

See separate unit-specific Installation, Operation and 

Maintenance manual for further information.

Summary of Contents for LE-8X*INH Series

Page 1: ...SHIPPING RIGGING HOISTING AND ASSEMBLY MANUAL ENERGY RECOVERY VENTILATORS RENEWAIRE COM LE6X LE8X LE10X...

Page 2: ...ll lifting lugs provided must be used Never lift the unit or modules from the top of the unit This unit is intended for general ventilating only Do not use to exhaust hazardous or explosive materials...

Page 3: ...ATION AND MAINTENANCE MANUAL RENEWAIRE COM OWNER INFORMATION IMPORTANT USER INFORMATION SAVE THIS MANUAL In the unlikely event that factory assistance is ever required information located on the unit...

Page 4: ...OODS 16 4 8 INSTALL MERV 8 FILTERS 17 5 0 ROOFTOP CURB DIMENSIONS 18 5 1 LE6XRT CURBS 18 5 2 LE8XRT CURBS 18 5 3 LE10XRT CURBS 19 6 0 ROOFTOP UNIT DIMENSIONS 20 6 1 LE6XRTH F DIMENSION DRAWING 20 6 2...

Page 5: ...ations 11 LE Rooftop Unit Base Bolt Locations 11 Alignment Spacer Bolt Location 11 Roof Beam Assembly Graphic 2 12 Roof Beam Assembly Graphic 1 12 Roof Beam Assembly Bolt Locations 12 Roof Cap Caulkin...

Page 6: ...Shipping Location typ Hoods are assembled at the factory and then secured for shipment inside the ERV LE models can be delivered in two modules for on site assembly or as a complete unit additional c...

Page 7: ...clearance between the cables and the cabinet or any of the equipment attached to the unit or modules Provide additional blocking or covering as required Secure hooks and cables at all lifting points...

Page 8: ...AND MAINTENANCE MANUAL 1 800 627 4499 8 RIGGING www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewa...

Page 9: ...ed unassembled for applications where modules must be manipulated separately If the unit was ordered unassembled then you will need to assemble the modules in the field Each module is labeled with a c...

Page 10: ...disposed of along with the screws that held them in place www renewaire com 800 627 4499 support renewaire com Apply 1 2 X 1 gasket tape provided as shown below Gasket tape creates an airtight seal be...

Page 11: ...N or base supports LE RT of the two adjacent modules Use 3 8 washers between the bolt head and the unit and between the nut and the unit Fasten the nuts to the bolts secure the bases of the two module...

Page 12: ...nsert 1 4 20 x 1 00 Grade 5 zinc plated hex head bolts through the holes in the roof beam Secure the nuts to secure the roof section www renewaire com 800 627 4499 support renewaire com AFTER THE LIFT...

Page 13: ...ewaire com A galvanized cap roof flange is provided to seal the roof seam and to maintain a water and airtight seal The cap roof flange is provided with pre drilled holes 12 X 75 hex head tek screw w...

Page 14: ...l not to over tighten the screw www renewaire com 800 627 4499 support renewaire com Two 2 galvanized roof cap ends are provided to seal the top end of each module and maintain a water and airtight se...

Page 15: ...n the electrical connection cover on the E Box side of the front module by removing screws in the access panel The access panel is located in the upper left corner of the front module to the left of t...

Page 16: ...4499 support renewaire com www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com Slide the top flange of the OA air hood beneath the roof panel over...

Page 17: ...that when filters are installed the filter spacers may tend to fall off the end of the filter receiving channels If this happens simply install the spacers between the first two filters in from the d...

Page 18: ...EA FA RTV 16 1 8 X 19 1 2 Opening 115 1 4 O D 64 1 4 O D 3 60 1 2 I D 17 1 4 33 20 25 9 1 2 A A TOP VIEW CURB LE6X FA RA LEFT VIEW Model LE6X RTV RTR Drawing Type Unit Dimension Version MAY18 LE6XRT...

Page 19: ...Lugs 4 111 1 4 Overall 69 1 8 Case 2 Typ 2 Duct Flange Typ C L 2 1 4 Wiring Pressure Ports 4 Typ 4 1 2 37 7 8 44 5 8 69 5 8 Case 71 1 8 Overall 29 5 8 53 1 2 47 1 4 84 5 8 9 C L 5 1 4 2 7 8 Knockouts...

Page 20: ...ard AIRFLOW CONFIGURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x L...

Page 21: ...CONFIGURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x LERT RTR RENE...

Page 22: ...GURATION Available as shown UNIT MOUNTING APPLICATION Must be mounted as shown Airstreams can not be switched EA A R A F OA HERT except 6x 8x LERT RTV OA A R EA FA HERT except 6x 8x LERT RTR RENEWAIRE...

Page 23: ...ator Standard AIRFLOW CONFIGURATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain optio...

Page 24: ...GURATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain options are selected FOR THE MOS...

Page 25: ...ATION Available as shown in dimension drawing UNIT MOUNTING APPLICATION Must be mounted as shown RA EA airstream can be switched with OA FA airstream unless certain options are selected FOR THE MOST C...

Page 26: ...CORNER WEIGHTS AT LIFTING LUGS BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2086 579 580 464 463 2100 583 585 466 465 2218 625 630 483 480 5 HP 7 5 HP Options UNIT LF LR RR RF ADDITIONAL WEIGHT...

Page 27: ...X INH Front Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 119 5 Lifting Lug CORNER WEIGHTS AT LIFTING LUGS BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 1984 569 433 424 558 19...

Page 28: ...ng LE 8XRT_CORNER LE 8X RT Fron Corner Weigh 73 5 Lifting Lug LR RR LF RF 159 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2625 753 680 568 624 2645 745 737 578 585 2763 790 780 5...

Page 29: ...ing LE 8X INH Front Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 159 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2495 727 524 521 723 2509 733 524 522 730 2627...

Page 30: ...ro Corner Weigh LE10X RT_CORNE 73 5 Lifting Lug LR RR LF RF 194 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 3031 842 841 674 674 3045 847 846 676 676 3163 892 890 690 691 5 HP 7...

Page 31: ...nt Module Corner Weights Sheet 3 of 4 73 5 Lifting Lug LR RR LF RF 194 5 Lifting Lug BASIC UNIT WEIGHTS lbs Motors UNIT LF LR RR RF 3 HP 2859 819 665 616 759 2873 825 666 617 765 2990 874 676 628 812...

Page 32: ...ulting in significant energy savings Our ERVs are competitively priced simple to install easy to use and maintain and have a quick payback They also enjoy the industry s best warranty with the lowest...