After completion of the field conversion:
u
Clean out the interior of the unit to remove any debris.
u
Install energy exchanger cores, filters, and core strap.
www.renewaire.com (800) 627- 4499
5.7.2 To Field Convert the Outlet Opening
1. Remove the patch pan from the desired opening.
2. Using the exposed sheet metal cutout, cut the insulation from the desired opening.
3. Seal the edges of the cut insulation to prevent erosion of the insulation edges and having
debris in the airstream.
4. Install the patch pan over the undesired opening.
5. Install the insulation in the undesired opening. Seal the insulation.
6. If the RA Inlet Opening is being converted return to Step 10 in the “To Field Convert Return
Air (RA) Inlet Opening” instructions above.
NOTE: The FA
patch pan may be
on the underside
of the base pan. Safely
access the underside of
the unit to remove the
patch pan.
FIGURE 5.7.0 EXAMPLE OF CONVERTING VERTICAL OPENING TO HORIZONTAL OPENING