Instruction

Digital Controller PCU Solid State

RCEL

- 1 -

www.rotork.com  www.remotecontrol.se

ELECTRICAL SHOCK HAZARD.To avoid serious personal injury, 

property damage, turn off ALL power to the actuator before remov-

ing the cover.

Before installation or use, verify the nameplate information infor-

mation to insure the correct model number, torque, voltage and 

enclosure type.

Be sure to completly review the actuator manual prior to operation.

Final limit switch adjustment MUST be done after mounting the ac-

tuator to the valve. Incorrect adjustment may cause actuator failure.

Over torque switches are factory set, tampering with the over 

torque switch settings may damage the actuator and void the war-

ranty.

The actuator must be properly grounded. Use the grounding lugs 

provided on the inside and outside of the actuator body.

To minimize the possible damage caused by condensation, be sure 

to energize the heater.

Care should be taken when wiring 3 phase actuators.

Confirm proper rotation and limit switch shutoff function during the 

initial operation. If the actuator rotates in the reverse direction, then 

the phasing needs to be corrected by switching two of the 3 phase 

wires on the terminal block.

CAUTION

Specifications

Input Power

90~230V AC ±10%, 50/60Hz

DC 24V / AC 24V ±10%

Input Power must match motor Ratings

Command Signal

4~20mA DC (Default), 0~5VDC,

0~10VDC, 1~5VDC, 2~10VDC

Dead Band

1 ~ 7,5% (1 scale 0,5%)

Output Signal

4~20mA DC

Load Resistance

750

Ω

Terminals

1~12 Connector, +, - 2EA (In/Output)

Visual Indicators

 4 LEDS,

Power (Blue), Fault (Yellow),

Open (Red), Close (Green)

Calibration Method

ASCN (Autoscan) Button

Output Contact

Relay Contact 250V AC 16A MAX.

(Inductive Load)

Delay Time

1 Sec 

Parameters

Dead Band: 0.2mA(Step)

Fail operation (during loss of command 

signal) Select input signal. A FULL Set 

or Clear

Resolution

Min 1/1,000

Ambient Temperatur -10 

º

C ~ +60 

º

C

Ambient Humidity

90% RH MAX. (Non-Condensing)

Dielectric Strenght

1,500V AC 1 MIN. 

(Input to Output to Power to Ground)

Insulation Resistance

500V DC 30MΩ MIN.

Warranty Information

The warranty will be void under the following conditions:

1. Failure or damage caused by misuse or abuse.

2. Failure or damage caused by unauthorized modifications or repairs done to the actuator.

3. Failure caused by the unauthorized modification / change or the wiring.

4. Failure caused by water entering the actuator due to improper sealing of the conduit entries.

5. Failure caused by improperly set limit switches.

6. Failure caused by fire, flood damage or other natural disasters.

7. Failure occuring more than one year after shipment date.

Summary of Contents for RCEL

Page 1: ...of the 3 phase wires on the terminal block CAUTION Specifications Input Power 90 230V AC 10 50 60Hz DC 24V AC 24V 10 Input Power must match motor Ratings Command Signal 4 20mA DC Default 0 5VDC 0 10V...

Page 2: ...S Connector 7 Input Connector 8 OLS CLS Connector 9 Potentiometer Connector 10 DIP Switch for Input Setting 1 No 1 12 Connector 1 11 10 9 8 7 6 5 4 3 2 12 2 DIP SWITCH No 1 2 3 4 5 6 7 8 Name FC FO AF...

Page 3: ...tor at Full Open Press the SPAN Button CH2 OFF Input and check if the device operates normally 6 REV It is used when the actuator operates in the inverse direction When REV is on and at 4mA the actuat...

Page 4: ...ppening It s set to have 0 05mA per gradation If it is at 1PH when shipped from the factory it is set to have a 0 2mA dead band If it is at 3PH on the other hand it is set to have a 0 3mA dead band ex...

Page 5: ...an Button Actuator automatically setting button Delivered from the factory the resistance value of potentiometer may can be changed if the user modifies its limit setting Please make sure to press the...

Page 6: ...al Mode 1 When you pull the lever located on the side of actuator handle toward the handle the lever stands straight If you turn the handle in that condition the actuator moves 2 If the lever does not...

Page 7: ...completed replace the top cover and secure it using the six cover screws 9 Apply the power and do a final check to confirm proper operation Main Power must only be applied when the top cover is re ins...

Page 8: ...t the mechanical limit stop Actuator suddenly stops during operation The over torque switch has tripped Valves torque has increased Valve needs to be checked repaired or replaced or the over torque sw...

Reviews: