background image

- 3 -

www.rotork.com  www.remotecontrol.se

1. Fail Close

When there is no input signal, the actuator automatically turns to a full close position.

2. Fail Open

When there is no input signal, the actuator automatically turns to a full open position.

3. AF

If the input signal is at 3.8 ~ 4.3mA, the actuator turns to a full close position.

If the input signal is at 19.7 ~ 20.2mA, the actuator turns to a full open position.

4. CH1

Optional modulation

It is used when the user voluntarily changes the input signal.

ex) When setting to 6 ~ 18mA Input

CH1 ON 

 Input 6mA and press ZERO button 

 Input 18mA and press SPAN button. 

 CH1 OFF 

 Input and check if the device operates normally.

5. CH2

Optional modulation using manual handle. 

Ii is used when the user controls the actuator using the manual handle.

ex) When controlling using the manual handle.

CH2 ON 

 Put the actuator at Full Close. 

 Press the ZERO Button 

 Put the actuator at 

Full Open 

 Press the SPAN Button 

 CH2 OFF 

 Input and check if the device operates 

normally.

6. REV

It is used when the actuator operates in the inverse direction.

When REV is on and at 4mA, the actuator turns to a full open position, and to a full close position 

when at 20mA.

7. Full Close

    Output Control

If the output is 3.7mA (not 4mA), put no.7 switch up and put SPAN button.

Whenever the button is put, the output increase. When it reaches at 4mA, put ASCN button for a 

second to save it.

(If the output is higher than 4mA, (4.2mA), put ZERO button to decrease.)

8. Full Open

    Output Control

If the output is not 20mA, follow the same step as above (7. Full Close Output Control).

+

+

3

In / Output Connector

7

4

Name

Spec.

ZERO Close manual control button

/ Input module button

SPAN Open manual control button

/ Input module button

ASCN AUTO SCAN BUTTON

(Actuator automatic control button)

Delivered from the factory the resistance value 

of potentiometer may can be changed if the user 

modifies its limit setting. Please make sure to 

press the autoscan button for at least 2 seconds 

before operating proportional control.

Summary of Contents for RCEL

Page 1: ...of the 3 phase wires on the terminal block CAUTION Specifications Input Power 90 230V AC 10 50 60Hz DC 24V AC 24V 10 Input Power must match motor Ratings Command Signal 4 20mA DC Default 0 5VDC 0 10V...

Page 2: ...S Connector 7 Input Connector 8 OLS CLS Connector 9 Potentiometer Connector 10 DIP Switch for Input Setting 1 No 1 12 Connector 1 11 10 9 8 7 6 5 4 3 2 12 2 DIP SWITCH No 1 2 3 4 5 6 7 8 Name FC FO AF...

Page 3: ...tor at Full Open Press the SPAN Button CH2 OFF Input and check if the device operates normally 6 REV It is used when the actuator operates in the inverse direction When REV is on and at 4mA the actuat...

Page 4: ...ppening It s set to have 0 05mA per gradation If it is at 1PH when shipped from the factory it is set to have a 0 2mA dead band If it is at 3PH on the other hand it is set to have a 0 3mA dead band ex...

Page 5: ...an Button Actuator automatically setting button Delivered from the factory the resistance value of potentiometer may can be changed if the user modifies its limit setting Please make sure to press the...

Page 6: ...al Mode 1 When you pull the lever located on the side of actuator handle toward the handle the lever stands straight If you turn the handle in that condition the actuator moves 2 If the lever does not...

Page 7: ...completed replace the top cover and secure it using the six cover screws 9 Apply the power and do a final check to confirm proper operation Main Power must only be applied when the top cover is re ins...

Page 8: ...t the mechanical limit stop Actuator suddenly stops during operation The over torque switch has tripped Valves torque has increased Valve needs to be checked repaired or replaced or the over torque sw...

Reviews: