Activation of the cooling function via the
unmixed cycle
This is where you can select between the different
cooling cycle modes
. The choice is between con-
trol according to the set
"cooling curve"
and
"fixed value regulation"
.
Activation of the cooling function can take place in
every heating cycle via the operating mode.
Menu item
Parameter
Factory set-
ting
Cooling cycle
mode with
underfloor
system active
Cooling curve
According to
design
Fixed value
8 °C - 35 °C
Cooling curve cooling cycle mode
The cooling curve can be set at three points,
depending on the structural and location-related
conditions of the building:
Base point:
The base point corresponds to the minimum set
temperature of the cooling water at an outside tem-
perature of 20 °C. If the cooling is too cold at rela-
tively high outside temperatures (trans-seasonal
period), the base point should be set higher.
Standard inlet temperature:
The inlet temperature corresponds to the set tem-
perature of the cooling water at the standard out-
side temperature in the building location. If the
cooling is not warm enough at low outside temper-
atures, the inlet temperature should be increased.
Standard outside temperature:
The standard outside temperature is dependent on
the regional location of the building and must be
set according to the region.
2
1
4
3
Fig. 11: Cooling curve adjustment
1: Temperature of the cooling water in °C
2: Cooling curve, inlet temperature
3: Cooling curve, return flow
4: Outside temperature in °C
For optimal configuration of the cooling curve
parameters, the cooling load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.