The suction pipeand / 
or liquid separator in the 
compressor have iced up

Heating output increases

Is the outdoor component 

running continuously?

Reduce the heating load. If 

necessary, install additional units / 

isolate the iced up components  

Troubleshooting and customer service

The equipment and components are manufactured using state-of-the-art production methods and tested several 
times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the 
list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have 
been performed!

Fault

possible cause

Checks

Remedial measures

The unit does not start or 
switches itself off

Power outage, undervoltage, defective 

mains fuse / main circuit breaker 

switched off

Are all electrical installations 

functioning correctly?

Check the voltage and if necessary 

wait for it to come back on

Damaged mains cable

Are all electrical installations 

functioning correctly?

Repair by specialist

Waiting time after switch-on too short Have approx. 5 minutes 

elapsed since the restart?

Schedule longer waiting times

Temperature outside operating 

temperature range

Are the fans in the indoor unit 

and outside component working 

correctly?

Take into account the temperature 

range for the indoor unit and 

outside component

Overvoltages caused by thunder 

storms

Has there recently been lightning?

Switch off the mains protection 

and switch it back on /have it 

checked by a specialist

Fault in external condensation pump

Did the pump shut down due to 

a fault?

Check and if necessary clean the 

pump

The unit does not respond 
to the remote control.

Transmission distance too far / receiver 

affected by interference

Does the indoor unit beep when 

pressing a button?

Reduce the distance to less than 6 

m or change position

Defective remote control

Is the unit running in manual mode?

Replace the remote control

Receiver&transmitter unit exposed to 

excessive solar radiation

Does it function correctly in the 

shade?

Place the receiver&transmitter unit 

in the shade

Electromagnetic fields are interfering 

with transmission

Does it function when switching off 

possible sources of interference?

Signal is not transmitted when 

interference sources are operational

Button in remote control jammed / 

two buttons pressed at same time

Does the “Send” symbol appear 

on the display?

Release the button / only press 

one button

Batteries in remote control are flat

Have new batteries been inserted? 

Is the display incomplete?

Insert new batteries

The unit is running but 
only provides reduced 
cooling or heating 
performance

Filter is unclean / air inlet / outlet 

blocked by foreign items

Have the filters been cleaned?

Clean the filters

Doors and windows open. Heating/ 

cooling output increases

Have modifications been made to 

the building?

Close windows and doors / install 

additional units

Neither cooling nor heating mode has 

been set

Is the cooling/heating symbol 

shown on the display?

Correct the settings for the unit

Fins on outdoor component blocked 

by foreign items

Is the fan on the outdoor 

component running ? Are the fins 

unobstructed?

Check the fan or winter controller, 

reduce the air resistance

Leaking refrigerant circuit

Are there signs of frost on the fins 

of the indoor unit?

Repair by specialist

Condensation is leaking 
out of the unit

Drainage pipe on collection container 

clogged / damaged

Can the condensation drain off 

without any obstruction?

Clean the drainage pipe and 

collection container

Faulty external condensation pump 

or float

Is the condensation tray full and 

the pump running?

Call out a specialist to replace the 

pump

Condensation has not drained away 

and has collected in the condensation 

pipe

Is there a steady fall on the 

condensation pipe? Check there is 

no blockage in the pipe.

The condensation pipe must have a  

 fall. If necessary, clean the pipe

Condensation does not drain off

Are the condensation pipes 

unblocked and is there a steady 

fall? Are the condensation pump 

and float switch functioning 

correctly?

The condensation pipe must have a  

 fall. If necessary, clean the pipe. 

A faulty condensation pump and 

float switch should be replaced.

Malfunction

15

Summary of Contents for RM 226

Page 1: ...Edition GB T05 REMKO RM RM 226 RM 235 RM 252 RM 268 RM 326 RM 335 RM 426 RM 435 Wall mounted split design air conditioning unit Operation Technology Spare parts...

Page 2: ......

Page 3: ...nty 4 Transportation and packaging 5 Description of the equipment 5 Operation 6 12 Shutdown 13 Care and maintenance 13 14 Troubleshooting and customer service 15 16 Installation instructions for quali...

Page 4: ...alified personnel The setup connection and operation of the unit and its components must be in accordance with the operating conditions stipulated in this manual and comply with all applicable local r...

Page 5: ...use and should be mounted high up on a wall It is operated by infrared remote control The outdoor component consists of two circuits A B three circuits A B C or four circuits A B C D refrigerant circ...

Page 6: ...Indoor unit B System layout Injection pipe Suction pipe Injection pipe Suction pipe Condensation pipe Condensation pipe Condensation pipe Condensation pipe Mains cable Control cable Control cable Ref...

Page 7: ...supplied with the remote control Remove the cover on the battery compartment and insert the batteries Take into account the correct polarity see markings The indoor unit is easy to operate using an in...

Page 8: ...ed 4 levels are available Automatic high medium and low fan speed FINS Button Press this button to adjust the position of the outlet fins 5 fixed positions and an oscillating function are available SL...

Page 9: ...y compartment to set the time CLOCK will flash on the display The HR and MIN buttons are used to set the current time Press the CLOCK button again to complete the programming procedure the display wil...

Page 10: ...idify Heating not supported In automatic mode the controller automatically selects heating or cooling mode after it is switched on The control range is 22 C to 26 C This can be raised or lowered using...

Page 11: ...the fan is intermittently switched on and off DEHUMIDIFY Mode DEHUMIDIFICATION MODE MODE Press this button to set the fan speed One can choose between low medium high and automatic fan speed FAN butt...

Page 12: ...tch on off time can be prematurely cancelled by pressing the appropriate Timer button or ON OFF button The timer symbol on the indoor unit extinguishes TIMER button ON Timer On HR MIN 30 sec TIMER but...

Page 13: ...r Care and maintenance Regular care and maintenance ensure trouble free operation and a long service life Care Ensure the indoor unit and outdoor component are protected against dirt mould and other d...

Page 14: ...uard using a soft damp cloth 4 Switch the supply voltage back on Air filter for indoor unit Clean the air filter at least every 2 weeks Reduce this interval if the air is especially dirty Cleaning the...

Page 15: ...es it function correctly in the shade Place the receiver transmitter unit in the shade Electromagnetic fields are interfering with transmission Does it function when switching off possible sources of...

Page 16: ...must be taken if the outdoor components is mounted above the indoor unit see section Oil return measures Add refrigerant if the basic length of the refrigerant pipe exceeds 5 metres The amount of addi...

Page 17: ...round using 4 screws and a wall or floor bracket Minimum clearance to snow 20 cm Snow Windbreak Wind Pipes and cables in wall breakthrough Control cable Condensation pipe Injection pipe Suction pipe P...

Page 18: ...Light well Outdoor unit Warm air Light well Additional fan 5 Installation inside buildings Air intake Air outlet All values in mm Minimum clearances The adjacent illustration specifies the minimum cl...

Page 19: ...ised specialists NOTE Oil return measures If the outdoor component is installed at a higher level than the indoor unit suitable oil return measures must be taken Usually an oil pump bend is installed...

Page 20: ...e fittings using 2 suitably sized open ended spanners Use one spanner to counter the force when tightening the fitting Fig 10 8 Use insulation hoses which are designed for this temperature range and d...

Page 21: ...during cooling The collection tray below the vaporiser should be connected to the drain The condensation pipe should have a fall of min 2 Fig 11 This is the responsibility of the customer If necessar...

Page 22: ...ain relief and re assemble the unit Fig 13 Check all plugged and clamped terminals to verify they are seated correctly and making a permanent contact Re tighten as required CAUTION Terminal block cont...

Page 23: ...onductor Outdoor component Circuit A Compressor Indoor unit Circuit B Outdoor component Circuit B PE PE N 1 N L L N L N L1 Neutral conductor Phase conductor Earth conductor Control conductor Compresso...

Page 24: ...r A Compressor B Compressor contactor A Compressor contactor B A A A A A A B B B B B B B B C C C C C O Gr Gr R R R W W W G Y G Y G Y G Y G Y G Y RM 252 AT Compressor A Compressor B Compressor contacto...

Page 25: ...sor contactor C Compressor contactor D A A A A A A A A A A A A B B B B B B B B B B B B B B B B C C C C C C C C C C O O Gr Gr Gr Gr R R R R R R W W W W W W G Y G Y G Y G Y G Y G Y G Y G Y G Y G Y G Y G...

Page 26: ...ompressor RM 326 AT RM 335 AT Mains cable To indoor unit A To indoor unit B To indoor unit C Compressor A Compressor B Compressor C Fan contactor Compressor contactor A Compressor contactor C A A A A...

Page 27: ...erant is always filled in liquid form CAUTION RM 226 RM 235 RM 252 RM 268 RM 326 RM 335 RM 426 RM 435 Basic pipe length Additional fill quantity Up to and including 5 m 0 g m 0 g m 0 g m 0 g m 0 g m 0...

Page 28: ...dure by briefly opening the stop valves on the outdoor component until the pressure gauge indicates a pressure of approx 2 bar 3 Use leak detection spray or suitable devices to check that all the conn...

Page 29: ...ded for pouring the water into the condensation tray 10 Switch the indoor unit to cooling mode 11 Check the correct function and settings of all regulation control and safety devices during the test r...

Page 30: ...t of the ongoing technical development process Unit dimensions All values in mm 500 315 RM 226 AT RM 235 AT 515 350 RM 252 RM 426 515 350 1240 310 830 RM 435 575 415 1240 390 930 1240 310 830 RM 268 5...

Page 31: ...filter set 1109401 1109427 1109440 1109414 3 Circuit board display 1109402 1109428 1109441 1109415 4 Swing motor 1109403 1109429 1109442 1109416 5 Outlet fins set 1109404 1109430 1109443 1109417 6 Con...

Page 32: ...ver panel 1109504 1109516 6 Side panel right 1109505 1109517 7 Compressor complete 1109602 1109605 8 Condenser compressor 1109507 1109519 9 Condenser liquefier fan 1109508 1109520 10 Stop valve suctio...

Page 33: ...9564 1109576 1109588 6 Side panel right 1109529 1109541 1109553 1109565 1109577 1109589 7 Compressor complete 1109608 1109611 1109614 1109617 1109620 1109623 8 Condenser compressor 1109531 1109543 110...

Page 34: ...31 Air flow rate per stage m h 320 370 420 380 450 520 600 700 800 800 900 1000 Noise output per stage 3 dB A 30 34 38 32 36 40 35 39 43 37 41 45 Protection degree IP X0 Condensation connection mm 17...

Page 35: ...to 31 Air flow rate per stage m h 320 370 420 380 450 520 380 450 520 320 370 420 380 450 520 Noise output per stage 3 dB A 30 34 38 32 36 40 32 36 40 30 34 38 32 36 40 Protection degree IP X0 Conden...

Page 36: ...ts in the areas of air conditioning and heating technology Customer service Our equipment is precise and reliable However should a fault should occur REMKO customer service is quickly at your side Our...

Reviews: