background image

12 

Attaching the wall mount

 

The unit wall mounts are attached with screws and dow-
els suitable for attachment.

 

Installation

 

 

Make absolutely sure to follow the instructions below 
prior to assembling the indoor unit: 

à

When assembling the indoor unit, make sure that the 
required minimum distances are observed. 

à

Assemble the indoor unit in such a way that conden-
sation drainage is not blocked and air can always 
flow freely in and out of the unit. 

à

The indoor unit is attached by means of a wall 
mount. 

120 

120 

120 

120 

1500 

Dimensions in mm 

These safety zones ensure that air can flow freely in 
and out of the unit, that maintenance and repair work 
can be performed and to protect the unit from damage. 

Minimum distances for the indoor units 

The figure below shows the required distances to ensure 
that the indoor units function properly. 

RKV 24 W 

Front view, all specifications in mm 

240 

107 

36 

Lead-through options 

Prior to installation, take a look at the various options for 
lead-throughs of the refrigerant, condensation and con-
trol lines (see figure below). 

Units RKV 10 W, RKV 13 W and RKV 18 W can be 
connected using all five options while the RKV 24 W 
units can only be connected using options 1 to 3. 

1    Outflow on the wall right             2   Outflow through the wall right 
3    Outflow on the wall bottom         4   Outflow through the wall middle 
5    Outflow on the wall left 

Assembling the indoor unit

 

Installation is performed as follows: 

1. The required line cross-sections are provided in the 

"Technical Data” table. 

Only use refrigerant lines with refrigerator quality. 

2. Decide on a drainage option for the indoor unit and 

cut the refrigerant connection line hose accordingly. 

3. When assembling the unit, observe the bending radii 

of the refrigerant lines and never bend the hose in 
the same place twice.  

This may cause the line to become brittle or crack

 

4. Remove the preinstalled swivel nuts of the units. 
5. Keep in mind that the indoor units have been filled 

with dry nitrogen as a sealant at the factory.          

The pressurised nitrogen is released when the 
swivel nuts are loosened.

 

 

Only use the swivel nuts supplied for further as-
sembly.

 

RKV 10 W / 13 W / 18 W 

320 

1000 

midddle of the unit 

160 

240 

200 

200 

35 

500 

Front view, all specifications in mm 

Summary of Contents for RKW 10 W

Page 1: ...REMKO powerful like a bear REMKO RKV 10 W 13 W 18 W 24 W Multi purpose room air conditioners Edition GB P05 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...n 14 Condensation Connection 15 External Condensation Pump 15 Prior to Initial Operation 17 Initial Operation 17 Environment and Recycling 18 Customer Service and Guarantee 18 Internal Wiring Diagram...

Page 4: ...the units exclusively within the permissible operating ranges Pay attention to surrounding temperatures Make sure that the unit is kept at a safe distance from flammable materials Do not install the i...

Page 5: ...e The difference between the point at which it switches on and off hysterisis is higher than in cooling mode 7 Temp button The temperature button can be used to set the de sired temperature in 0 5 C i...

Page 6: ...unit to switch on or off at a later time If the room air conditioner is to be switched on at a later time press the or button for approximately 2 seconds when the unit is off In both operating modes...

Page 7: ...ou hear a beep the COMP display begins to blink for approximately 3 minutes This waiting period is a forced pause to increase the service life of the compressor and the outdoor part Once the display s...

Page 8: ...the filters and close the grille Maintenance and Service Shutting Down the Unit Temporary shutdown 1 Switch the indoor unit off using the remote control 2 Disconnect the system with the main switch o...

Page 9: ...nsmission signal at a dis tance of approx 3 m when the but ton is pressed Reduce distance to under 6 m and change location Remote control defective Does the unit work in manual mode Replace remote con...

Page 10: ...40 65 Power consumption cooling A 0 2 0 2 0 2 0 4 Current consumption max A 0 2 0 2 0 2 0 4 Supply diffuse protection recommended A See corresponding outdoor part Operating range cooling C 15 C bis 30...

Page 11: ...oid if third party components are used Remember that when installing and maintaining air conditioners high pressure refrigerant lines and electrical current can pose hazards During unit operation some...

Page 12: ...n and con trol lines see figure below 4 3 2 1 5 Units RKV 10 W RKV 13 W and RKV 18 W can be connected using all five options while the RKV 24 W units can only be connected using options 1 to 3 1 Outfl...

Page 13: ...5 If you have selected Option 2 or 4 drainage through the wall guide the condensation water and control line through the wall lead through to the indoor unit If you also need a condensation pump it mu...

Page 14: ...terminal strip of the connection towards you out of the unit Please observe the following We recommend that the customer install a main or repair switch close to the outdoor part Power is supplied to...

Page 15: ...n If the unit is being operated at outside temperatures below 0 C the lines must be placed in such a way that they are protected from frost External Condensation Pump The condensation pump which can b...

Page 16: ...ly The end of the ventilation hose must at least be at the same height as the con densation tray to prevent water from overflowing The supplied metal wire clips are used to secure the hose in a vertic...

Page 17: ...values in the initial operation log Cooling operation test run Perform a test run for cooling operation as follows 1 Switch the customer installed main switch or fuse on 2 Adjust the target temperatur...

Page 18: ...horised personnel may come into contact with the cold cycle This ensures that refrigerant does not es cape into the environment when the unit is being re paired Both the refrigerant and the system par...

Page 19: ...tup location Name Street Postal code city Telephone Fax Testing of cycles A B C D Result Visible check Setup of outdoor part and indoor unit R good Q poor Heat exchanger insulation lines R good Q poor...

Page 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Reviews: