background image

 

RKS 510 

RKS 513 

RKS 524 

200 mm 

200 mm 

300 mm 

700 mm 

700 mm 

900 mm 

400 mm 

400 mm 

400 mm 

100 mm 

100 mm 

200 mm 

Wind 

These safety zones ensure that air can flow freely in and 
out of the unit, that maintenance and repair work can be 
performed and to protect the unit from damage. 

Minimum distances 

The figure below indicate the minimum distances that 
must be maintained to ensure that the units operate 
properly. 

Wall lead-throughs 

Wall lead-throughs are necessary to establish the con-
nection between the indoor unit and the outdoor part. 
Please observe the following: 

For the connection line to the outdoor part, a lead-
through of at least 70 mm in diameter per cold cycle 
must be created. 

The lead-through must be placed at an incline of at 
least 10 mm between the inside and outside. 

Before beginning work, make sure that there are no 
supply lines (water, etc.) located in the vicinity of the 
wall lead-through. 

We recommend cushioning the inside of the hole or 
lining it with a PVC pipe to prevent damage to the 
lines. 

Control lines 

Refrigerant 
return line 

Condensation tube 

Refrigerant 
supply line 

After assembly is complete, the wall lead-through 
must be sealed with a suitable sealing compound. 

Do not use any materials containing cement or lime! 

Location of installation for the outdoor part

 

The outdoor part must be set up on a surface that is 
level, smooth and solid. 

The outdoor part can either be set up outside or inside a 
building. If it is set up outside, follow these instructions 
to protect the unit from weather conditions. 

This prevents dirt and rust caused by splashing rain. 

Rain: 

If the  outdoor part  is set up on the ground or a roof, 
there must be at least 10 cm ( measurement X in the 
illustration below) between it and the surface. 

A base console can be purchased as an accessory. 

Sun: 

The plate fin exchanger (condenser) on the outdoor part 
is a heat-emitting component. 

Direct sunlight also increases the temperature of the 
plate fins and reduces the amount of heat expelled by 
the plate fins exchanger. 

If possible, the outdoor part should be installed on the 
north side of the respective building. 

A small structure should be set up to provide shade for 
the unit and protect it from the sun if necessary. How-
ever, it must not be allowed to interfere with the flow of 
hot air being released from the unit. 

Wind: 

If the outdoor part is operated primarily in windy areas, 
make sure that the hot air current being released from 
the outdoor part is flowing in the primary wind direction. 

If this is not possible, you should provide protection from 
the wind. Make sure that the wind protection does not ad-
versely affect the flow of the air to the unit. 

Summary of Contents for RKS 510

Page 1: ...REMKO powerful like a bear REMKO RKS 510 513 524 REMKO RKS 513 H 524 H Combi Air Conditioning Units Edition GB M08 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...ration 12 Adding Refrigerant 12 Initial Operation 12 Customer Service and Guarantee 13 Environment and Recycling 13 Wiring Diagram 13 Initial Operation Certification 15 Combi Air Conditioning Units RE...

Page 4: ...eratures between 15 and 46 C Never open the units housing There may cause an electric shock Protect the connection lines from being damaged for example by animals All REMKO air conditioners are suppli...

Page 5: ...in your area Troubleshooting This unit has been designed based on state of the art manufacturing methods and it has been tested repeatedly to ensure that it is working properly However should problems...

Page 6: ...rting current LRA A 23 31 77 31 77 Supplied fuse protection recommended A 16 16 25 16 25 Sound pressure level max dB A 49 49 59 49 59 Width mm 850 850 950 850 950 Depth mm 322 322 417 322 417 Weight k...

Page 7: ...ng air conditioners high pressure and electrical current can pose hazards Be especially careful when covers are removed The components in the cold cycle can reach tem peratures of more than 70 C Selec...

Page 8: ...s containing cement or lime Location of installation for the outdoor part The outdoor part must be set up on a surface that is level smooth and solid The outdoor part can either be set up outside or i...

Page 9: ...escribe installation of the cold cycle and the assembly of the indoor unit and out door part 1 The required cross sections are provided in the Technical Data table 2 Install the indoor unit and connec...

Page 10: ...ly removed from the system the manometer station valves are closed and the valves of the outdoor part are opened as described in the section Initial Operation Impermeability Test Once all connections...

Page 11: ...both lines through the rubber protective rings of the fixed connection plate 5 Clamp the lines as shown in the wiring diagram on page 13 6 Place the line securely in the strain relief and reas semble...

Page 12: ...documented Prior to handover After all components have been connected and checked the system can be put into operation To ensure that the unit is functioning properly a func tional check must be perfo...

Page 13: ...liability for damage re sulting from non compliance with manufacturer specifi cations and legal requirements or if modifications are made to the units Only authorised personnel may come into contact w...

Page 14: ...P 1 JP 2 JP 3 JP 4 JP 5 JP 6 JP 7 JP 8 Fuse 3 A 250 V TS 3 Winterregulation P1 Sensor VM C3 brn blu Ventilator blk brn wht blk or wht Legende TS1 terminal strip power supply TS2 terminal strip to indo...

Page 15: ...ional quantities g Condensation pump Operator Assembly location Name Street Postal code city Telephone Fax Test of cold cycle Result Visual check Assembly of outdoor part and indoor unit R good Q poor...

Page 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: