background image

Assembly Instructions for 

Service Personnel 

 

Prior to installation 

To avoid having an adverse effect on the performance 
of the air conditioner, several basic rules must be ob-
served when setting up the outdoor part and installing 
the refrigerant lines:

 

Make sure that the refrigerant line is no longer than 
15 m with a maximum height difference of 10 meters. 

Add more refrigerant to the system when the basic 
length of the refrigerant line exceeds 5 m.  

The required amounts of additional refrigerant are in-
dicated in the section "Adding Refrigerant".

 

Make sure that the indoor unit and the outdoor part of 
the system have been adjusted to one another from 
a technical standpoint.

  

The guarantee becomes null and void if third-party 
components are used.

 

Ensure that the contents of the package are com-
plete and that the unit has no visible damage results 
in from transport. 

Any problems must be communicated immediately to 
your contract partner and the shipping company. 
Subsequent complaints will not be acknowledged.

 

Dimensions

 

615 

290 

322 

850 

500 

320 

RKS 510, RKS 513, RKS 513 H 

645 

390 

417 

950 

590 

330 

RKS 524, RKS 524 H 

Place the unit in its original packaging as close as 
possible to the location where it will be assembled. 

This will prevent damage resulting from transport.

 

Prior to installation, the electrical connection values 
must be checked for consistency with the data on 
the type plate. 

Remove the protective caps of the unit connections 
just before connecting the refrigerant lines. 

Do not bend or press on the refrigerant lines. 

Remember that when installing and  maintaining air 
conditioners, high pressure and electrical current can 
pose hazards. 

Be especially careful when covers are removed.  

The components in the cold cycle can reach tem-
peratures of more than 70 °C.

 

Select a location to set up the unit where air can flow 
freely in and out of the device.

          

Minimum distances that must be maintained for 
safety purposes are provided in the section 
“Minimum Distances”. 

The power supply may only be connected to the out-
door part. The control lines to the indoor units should 
be laid at the same time as the refrigerant lines. 

The electrical connections must meet the relevant 
DIN and VDE standards. 

Make sure that all refrigerant lines including all con-
nectors and valves are insulated against heat and 
sealed against diffusion.

 

Preventable installation mistakes 

When performing the installation, make sure to observe 
the following:

 

Place the lines between the indoor unit and the out-
door part, keeping the length of the refrigerant lines 
as short as possible. 

The cooling connection valve may only be opened 
once installation is complete. 

Always secure electrical lines properly in the electri-
cal clamps.

         

Not doing so could cause a fire. 

Seal open refrigerant lines with suitable caps and/or 
adhesives to prevent moisture penetration. 

Avoid bending the lines unnecessarily.

       

This minimises pressure loss in the refrigerant lines 
and guarantees that the compressor oil can flow 
freely.

 

If the outdoor part is mounted above the indoor unit, 
you must take steps to recirculate the oil.   

See section on oil recirculation. 

Do not set up the unit in the direct proximity of de-
vices that emit intense heat, such as glass reflection 
surfaces.

  

If the unit is assembled close to heat emissions, the 
amount of warm air expelled by the plate fins of the 
outdoor part is reduced.

 

Summary of Contents for RKS 510

Page 1: ...REMKO powerful like a bear REMKO RKS 510 513 524 REMKO RKS 513 H 524 H Combi Air Conditioning Units Edition GB M08 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...ration 12 Adding Refrigerant 12 Initial Operation 12 Customer Service and Guarantee 13 Environment and Recycling 13 Wiring Diagram 13 Initial Operation Certification 15 Combi Air Conditioning Units RE...

Page 4: ...eratures between 15 and 46 C Never open the units housing There may cause an electric shock Protect the connection lines from being damaged for example by animals All REMKO air conditioners are suppli...

Page 5: ...in your area Troubleshooting This unit has been designed based on state of the art manufacturing methods and it has been tested repeatedly to ensure that it is working properly However should problems...

Page 6: ...rting current LRA A 23 31 77 31 77 Supplied fuse protection recommended A 16 16 25 16 25 Sound pressure level max dB A 49 49 59 49 59 Width mm 850 850 950 850 950 Depth mm 322 322 417 322 417 Weight k...

Page 7: ...ng air conditioners high pressure and electrical current can pose hazards Be especially careful when covers are removed The components in the cold cycle can reach tem peratures of more than 70 C Selec...

Page 8: ...s containing cement or lime Location of installation for the outdoor part The outdoor part must be set up on a surface that is level smooth and solid The outdoor part can either be set up outside or i...

Page 9: ...escribe installation of the cold cycle and the assembly of the indoor unit and out door part 1 The required cross sections are provided in the Technical Data table 2 Install the indoor unit and connec...

Page 10: ...ly removed from the system the manometer station valves are closed and the valves of the outdoor part are opened as described in the section Initial Operation Impermeability Test Once all connections...

Page 11: ...both lines through the rubber protective rings of the fixed connection plate 5 Clamp the lines as shown in the wiring diagram on page 13 6 Place the line securely in the strain relief and reas semble...

Page 12: ...documented Prior to handover After all components have been connected and checked the system can be put into operation To ensure that the unit is functioning properly a func tional check must be perfo...

Page 13: ...liability for damage re sulting from non compliance with manufacturer specifi cations and legal requirements or if modifications are made to the units Only authorised personnel may come into contact w...

Page 14: ...P 1 JP 2 JP 3 JP 4 JP 5 JP 6 JP 7 JP 8 Fuse 3 A 250 V TS 3 Winterregulation P1 Sensor VM C3 brn blu Ventilator blk brn wht blk or wht Legende TS1 terminal strip power supply TS2 terminal strip to indo...

Page 15: ...ional quantities g Condensation pump Operator Assembly location Name Street Postal code city Telephone Fax Test of cold cycle Result Visual check Assembly of outdoor part and indoor unit R good Q poor...

Page 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: