background image

11 

G

 

Prior to performing any work on the unit, it must be 
unplugged from the power supply and secured 
against being inadvertently switched on!

 

Connecting the outdoor part 

Before proceeding with the connections, please read the 
following instructions: 

Electrical Connection 

 

A power supply to the outdoor part must be installed as 
well as a 4-wire control line for pure cooling operation 
from the outdoor part to the indoor unit. 

A 7-wire and a 2-wire control line is required between 
the outdoor part and the indoor unit for cooling / heating 
operation. 

These electrical installations may only be performed by 
authorised service personnel in accordance with the 
relevant regulations. 

Local guidelines for operation as well as the require-
ments established by local energy supply companies 
must be observed for install and initial operation. 

The connections of the outside part are located inside 
the unit above the connection valves. 

The power supply’s wire cross section is based on the 
design specifications and the connection capacity of the 
unit. 

For the control circuit, we recommend using shielded 
lines with a wire cross section of at least 1.5 mm². 

The connection box must be 
installed close to the outdoor 
part.          

We recommend using a main 
switch or a repair switch.

 

Power for  the indoor unit is 
supplied via the connection line 
from the outdoor part. 

Fuse protection for the system 
occurs in accordance with the 
technical data. 

Proceed as follows to connect the line 

1. Disassemble the unit cover by removing the fixing 

screws. 

2. Remove the side panel where the connection is lo-

cated. 

3. Select the wire cross section of the connection line 

based on the respective requirements. 

4. Guide both lines through the rubber protective rings 

of the fixed connection plate. 

5. Clamp the lines as shown in the wiring diagram on 

page 13. 

6. Place the line securely in the strain relief and reas-

semble the unit. 

Winter Regulation

 

 

To ensure that the system functions properly, the pres-
sure and temperature of the refrigerant must be kept 
within the operating ranges in the indoor unit and out-
door part. The integrated winter regulation mechanism 
makes it possible to keep operating ranges constant 
even when outside temperatures go as low as –15 °C. 

The winter regulation mechanism gradually adjusts the 
condenser ventilator’s motor speed depending on the 
operating pressure of the system and outside tempera-
ture. For this reason, the rotating motion of the ventilator 
can be completely discontinued in winter. 

The regulating mechanism consists of a regulating board 
in a housing and a temperature sensor. The sensor rec-
ords the temperature of the air entering the condenser. 

The regulating board regulates the starting voltage for 
the ventilator depending on the regulating hysteresis set 
by the two jumpers (JP). 

LVS 

JP 1 

10 

JP 5 

20 

JP 2 

15 

JP 6 

30 

JP 3 

20 

JP 7 

40 

JP 4 

25 

JP 8 

50 

HVS 

Adjusting the regulating hysteresis with the jumpers 

HVS = Highest Ventilator Speed 

HVS

 is the maximum ventilator speed for ventilation. It 

is also called 

E

ffective 

P

roportional 

B

and (EPB). 

LVS = Lowest Ventilator Speed 

LVS

 is the design-specific, minimum  ventilator speed 

when the regulating board has a starting voltage of 
35%. It is also called the 

F

ixed 

V

entilator 

V

oltage (FVV). 

Starting voltage 

35 % 
(approx.80 V) 

100 % (230 V) 

5  10  15  20  25  30  35  40  45  50 

-5 

Temperature (°C) 

HVS 

20 

HVS 

30 

HVS 

40 

HVS 

50 

LVS 

10 

LVS 

15 

LVS 

25 

LVS 

25 

Example: 

Jumper JP 4 (

LVS) 

and JP 7 (

HVS)

 are plugged in. 

The maximum ventilator speed is reached at a tem-
perature of 40 °C. 

The minimum ventilator speed is set at a tempera-
ture of 15 °C. 

Summary of Contents for RKS 510

Page 1: ...REMKO powerful like a bear REMKO RKS 510 513 524 REMKO RKS 513 H 524 H Combi Air Conditioning Units Edition GB M08 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...ration 12 Adding Refrigerant 12 Initial Operation 12 Customer Service and Guarantee 13 Environment and Recycling 13 Wiring Diagram 13 Initial Operation Certification 15 Combi Air Conditioning Units RE...

Page 4: ...eratures between 15 and 46 C Never open the units housing There may cause an electric shock Protect the connection lines from being damaged for example by animals All REMKO air conditioners are suppli...

Page 5: ...in your area Troubleshooting This unit has been designed based on state of the art manufacturing methods and it has been tested repeatedly to ensure that it is working properly However should problems...

Page 6: ...rting current LRA A 23 31 77 31 77 Supplied fuse protection recommended A 16 16 25 16 25 Sound pressure level max dB A 49 49 59 49 59 Width mm 850 850 950 850 950 Depth mm 322 322 417 322 417 Weight k...

Page 7: ...ng air conditioners high pressure and electrical current can pose hazards Be especially careful when covers are removed The components in the cold cycle can reach tem peratures of more than 70 C Selec...

Page 8: ...s containing cement or lime Location of installation for the outdoor part The outdoor part must be set up on a surface that is level smooth and solid The outdoor part can either be set up outside or i...

Page 9: ...escribe installation of the cold cycle and the assembly of the indoor unit and out door part 1 The required cross sections are provided in the Technical Data table 2 Install the indoor unit and connec...

Page 10: ...ly removed from the system the manometer station valves are closed and the valves of the outdoor part are opened as described in the section Initial Operation Impermeability Test Once all connections...

Page 11: ...both lines through the rubber protective rings of the fixed connection plate 5 Clamp the lines as shown in the wiring diagram on page 13 6 Place the line securely in the strain relief and reas semble...

Page 12: ...documented Prior to handover After all components have been connected and checked the system can be put into operation To ensure that the unit is functioning properly a func tional check must be perfo...

Page 13: ...liability for damage re sulting from non compliance with manufacturer specifi cations and legal requirements or if modifications are made to the units Only authorised personnel may come into contact w...

Page 14: ...P 1 JP 2 JP 3 JP 4 JP 5 JP 6 JP 7 JP 8 Fuse 3 A 250 V TS 3 Winterregulation P1 Sensor VM C3 brn blu Ventilator blk brn wht blk or wht Legende TS1 terminal strip power supply TS2 terminal strip to indo...

Page 15: ...ional quantities g Condensation pump Operator Assembly location Name Street Postal code city Telephone Fax Test of cold cycle Result Visual check Assembly of outdoor part and indoor unit R good Q poor...

Page 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: