"Automatic" mode
In "automatic mode", the controller autonomously
selects between heating, recirculation or cooling
mode based on the room temperature
Tr
and the
selected setpoint
Ts
.
The setpoint can be adjusted using the " " and
" " keys
between 17 °C and 30 °C. The fan speed is
selected automatically.
Fig. 12: "Automatic" mode
Function:
Tr<Ts=1 °C:
"Heating"
operating mode is
selected.
Tr>Ts=2 °C:
"Cooling"
operating mode is
selected.
Tr<-1 °C...Ts...+2 °C:
"Recirculation"
operating
mode is selected.
After the compressor is shut down and not
required for more than 15 minutes within an oper-
ating mode, if the room temperature deviates, the
appropriate mode (h
eating, cooling or recircula-
tion) is selected again.
The heating mode has priority!
Turns on the indoor unit to the heating mode,
switch off the other indoor units from which are
in cooling mode, the cooling. During heating
operation can not be cooled.
"Dehumidification" mode
We recommend setting the target temperature to
24 °C in dehumidification mode. The air is cooled
to below its dew point due to the refrigerant's low
temperature. The excess moisture in the air is con-
densed by the evaporator, the room is dehumidi-
fied.
Fig. 13: "Dehumidification" mode
"Cooling" mode
In "Cooling" mode, the air in the room is cooled to
the set target temperature. The desired room tem-
perature is set using the "Temp" keys in 1 °C incre-
ments. If the room temperature is 0.5 °C above the
selected target temperature, the indoor unit starts
to cool the air in the room. If the temperature falls
to approx. 1 °C below the set room temperature,
the controller will switch off cooling mode. To pro-
tect the compressor, the controller only turns
cooling on again after a wait time of 3 minutes.
Fig. 14: "Cooling" mode