background image

TIP

5

 “Dehumidify“ mode 

1. 

Attach the air outlet hose to the wall 
bushing or the window.

2. 

Activate the device using the “Power“ 
button (1).

3.

  Press the “Mode“ button (2) until the 

“Dehumidify“ LED (9) lights up; the fan 
is automatically switched to the “Med“ 
or medium fan speed stage.

“Fan“mode 

1. 

Activate the device using the “Power“ 
button (1).

2. 

Press the “Mode“ button (2) until the 
“Fan“ LED (9) lights up.

3. 

Select the fan setting using the “Fan 
Speed“ button (3):

  “High“ highest speed
  “Med“ medium speed
  “Low“ lowest speed
4. 

The room temperature is not infl uenced 
and remains constant. For this reason, 
the  temperature and time setting 
“Timer/Temp. Adjust“ buttons (5/6) 
cannot be used.

 “Cool“ mode 

1. 

Attach the air outlet hose to the wall 
bushing or the window.

2. 

Activate the device using the “Power“ 
button (1) .

3. 

Press the “Mode“ button (2) until the 
“Cool“ LED (9) lights up.

4. 

Select the fan setting using the “Fan 
Speed“ button (3):
“High“ highest speed

  “Med“ medium speed
  “Low“ lowest speed
5.  I

f the “Room Temp.“ LED (12) lights up, 

the current room temperature is shown 
in the display (7).

6. 

As soon as the (4/5/6) button is 
pressed, the display switches from the 
room temperature to the set tempera-
ture (LED 13 lights up) and shows the 
desired temperature for 15 seconds.

7.

Set the desired room temperature using 
the “Timer/Temp. Adjust“ button (5/6). 
The up arrow (5) increases the set value 
shown in the display (7), while the 
down arrow (6) decreases it.

“Timer“ time delay (4)

You can turn the device on and off    
automatically using the timer. To do so, 
an activation/deactivation delay is pro-
grammed.

■ 

Automatic activation
1.

Activate the device using the 
“Power“ button (1).

2.

  Select the mode and make all set-

tings for the desired mode.

3.

Deactivate the device using the 
“Power“ button (1) .

4.

Press the “Timer“ button (4). 

5.

Set the time using the “Timer/
Temp. Adjust“ button (5/6). 
Only whole hours can be entered.

6.

The LED (11) fl ashes.

7.

The device activates automatically 
at the set time.

■ 

Automatic deactivation
1.

The device is running in the previ-
ously set mode.

2.

Press the “Timer“ button (4).

3.

Set the remaining run time using 
the “Timer/Temp. Adjust“ button 
(5/6). 
Only whole hours can be entered.

4.

The LED (11) fl ashes.

5.

The device deactivates automati-
cally at the set time.

   

“Cool“ mode

You can achieve a pleasant 
room climate by selecting 
a set temperature that is a 
maximum of 4 to 7°C below 
the outdoor temperature.

Summary of Contents for MKT 240

Page 1: ...Timer Functional Principle of the Cooling Process Maintenance and Care Cleaning the Filter Draining the Condensate Trouble Shooting Taking the Device Out of Service Warranty Environment and Recycling...

Page 2: ...lines under carpeting Do not lay lines under carpeting Never operate the device with Never operate the device with out an air lter Never direct the air ow at Never direct the air ow at people Never op...

Page 3: ...ed Observe the following notices Plug the air outlet hose in cluded in delivery onto the air outlet on the rear panel of the device Lock both catches on the air outlet into both openings of the air ou...

Page 4: ...D 14 C F toggle button only on the remote control Operation The device is operated comfortably using the control panel on the device or the in frared remote control Keys with the same symbols have the...

Page 5: ...ed the display switches from the room temperature to the set tempera ture LED 13 lights up and shows the desired temperature for 15 seconds 7 Set the desired room temperature using the Timer Temp Adju...

Page 6: ...porates during operation and is then conducted outside with the exhaust air via the air outlet hose In case of extreme humidity the device collects conden sate in a reservoir If the permissible level...

Page 7: ...and pull the mains plug 2 Place a at tray under the condensate drain spout and remove the plug Fig 17 3 After the condensate has drained reinsert the plug rmly The device is not cooling properly Chec...

Page 8: ...design sub ject to alteration Control panel Evaporator fan Condenser Red Orange Yellow White White W Red Red Red Blue Blue Blue Blue Condenser Condenser Compressor Evaporator fan Reservoir motor Mains...

Page 9: ...480 mm with a diameter of at least 135 mm Take the minimum distance of 430 mm between the oor mounting surface of the device and the centre of the wall bushing into consideration Insert the telescopi...

Page 10: ...of the MKT 240 Technical dimensions and design subject to alteration Device Diagram 28 28 35 35 33 33 34 34 18 18 29 29 19 19 21 31 31 18 18 18 18 20 30 27 25 25 8 1 2 3 10 7 7 6 6 11 5 9 4 23 23 13...

Page 11: ...n wheel right circulation air 1106870 21 Fan motor circulation air 1106871 22 Side wall right 1106872 23 Circuit board 1106873 24 Mains supply line with plug 1106874 25 Front wall 1106875 26 Back wall...

Page 12: ...setting range C 16 bis 32 Temperature operating limits C 16 bis 35 Refrigerant R 407 C Refrigerant quantity kg 0 770 Circulation air volume ow rate m3 h 230 260 300 Exhaust air volume ow rate Max m3...

Reviews: