background image

System components 
required

Valve assembly for 2-conductor 
systems (accessory) 

In 2-conductor systems, cold or 
warm medium is fed through 
the heat exchanger into the unit 
and cold or warm air can be 
discharged. Control is provided 
by the 3-way valve assembly. 
It consists of the electrically 
actuated valve head and the valve 
body. If the head is electrically 
activated, it actuates the body, 
which routes the medium into 
the register. If the temperature is 
reached, the head is switched off 
and the medium is fed past the 
heat exchanger through the bypass 
. The bypass serves to ensure the 
minimum medium flow rate for the 
chiller or the heat pump.

Valves for hydronic balancing

The calculated individual pressure 
losses in the pipeline network 
layout for each individual unit are 
adjusted to the entire system with 
hydronic balancing valves to be 
provided by the customer. The 
nominal flow rates for the medium 
adjust to the values needed as a 
consequence of the pressure loss.

The time between being fully 
open and fully closed can be 
approx. three minutes.

      NOTE

Connection for 
medium piping

■ 

The connection of the piping 
by the customer is made on the 
rear side of the units.

■ 

For the purpose of servicing, 
connections must be equipped 
with shut-off valves and the 
medium flow rate adjusted 
using hydronic balancing 
valves.

■ 

Additional automatic bleed 
valves must be provided in the 
supply and return flows at the 
installation's highest point.

■ 

The medium piping must not 
exert any structural load on the 
unit.

■  

The pipe connections must 
not impose any thermal or 
mechanical stresses on the unit. 
If necessary cool the piping or 
support with the second tool.

Automatic bleed valves

The unit has one or two manual 
bleed valves on the collector pipe 
of the register.
The unit can be bled separately 
after the system has been filled. 
Automatic bleed valves must also 
be installed at the highest point in 
the collector line.

Glycol tolerant bleeding valves 
are necessary when using 
media which contain glycol.

      CAUTION

Anti-freeze protection 
(accessories)

A water glycol mix is generally 
used as the medium for a cold 
water system. Depending on the 
glycol type and quantity used, the 
viscosity changes, the pressure loss 
increases and the unit's cooling or 
heating capacity reduces.

All system components must be 
approved for use with glycol.

Diaphragm expansion vessel 
(MAG) 

To avoid pressure fluctuations 
because of temperature changes 
when not operating, diaphragm 
expansion vessels filled with 
nitrogen (moisture neutral) must 
be integrated in the system.

The product and safety data 
sheets of the glycol type which 
is used must be obeyed during 
use and disposal.

      NOTE

Bleeding valve

Outlet

Inlet

Manual bleeding 

valve

Outlet

Inlet

Manual bleeding 

valve

13

Summary of Contents for KWK 100-4R

Page 1: ...KWK 100 4R KWK 150 4R KWK 250 4R KWK 400 4R Wall and ceiling chilled hot water units for heat pump systems Operation Technology Spare parts Edition GB F01 REMKO KWK 4R...

Page 2: ......

Page 3: ...or misprints Safety notes 4 Environmental protection and recycling 4 Transportation and packaging 4 Guarantee 5 Unit description 5 System layout 6 Operation 6 7 Shutdown 7 Care and maintenance 7 8 Tro...

Page 4: ...it and its components must be set up connected and operated in accordance with the use and operating conditions stipulated in this manual and comply with all applicable local regulations Mobile units...

Page 5: ...is designed for use indoors in the lower wall area vertical installation and for ceiling installation horizontal installation Operation is either individually or in groups using a room temperature co...

Page 6: ...r warm water generator which extracts heat from the medium or heats the medium in a heat exchanger The cooled heated operating medium is then fed once again to the unit in the medium circuit Room temp...

Page 7: ...nance work may only be carried out if the unit is disconnected from electrical power CAUTION Care Ensure the unit is protected against dirt mould and other deposits Clean the unit using a damp cloth D...

Page 8: ...Switch the power supply and the unit back on Cleaning the condensate pump accessory The indoor unit may contain an integrated or separate condensate pump which pumps any accumulated condensate into ou...

Page 9: ...r wait for time period to pass Filter is dirty air inlet outlet opening is blocked by debris Have the filters been cleaned Clean filters Windows and doors open Heating cooling output has increased Hav...

Page 10: ...minimises the pressure loss in the lines Make all electrical connections in accordance with applicable DIN and VDE standards Always ensure the electrical cables are properly connected to the terminals...

Page 11: ...the heat exchanger slide into the retainer keep the same air duct and after installing the heat exchanger remove the film and screw the unit back together in reverse order 5 Removing the heat exchang...

Page 12: ...drainage line to the unit as described below Installation NOTE Installation should only be performed by authorised specialists Selecting the hydraulic connection 2 conductor cooling system Wall insta...

Page 13: ...ow rate adjusted using hydronic balancing valves Additional automatic bleed valves must be provided in the supply and return flows at the installation s highest point The medium piping must not exert...

Page 14: ...hich is not used must be permanently sealed a cap or similar CAUTION Condensate drainage connection Condensate drainage connection Condensate drainage connection Vertical mounting Horizontal mounting...

Page 15: ...ed KWK 100 4R to 400 4R Neutral conductor Phase conductor Earth conductor Power supply 230V 1 50Hz Level 2 Level 1 Level 3 Condensate pump If the condensate which forms is to be removed by a condensat...

Page 16: ...re and record all the required values in the commissioning report and check the safety functions 5 Check the unit control system using the functions described in the Chapter Operation Final tasks Reas...

Page 17: ...ned heat exchanger 4 rows of tubes 1111746 1111747 1111748 1111749 3 Outlet grill 1111764 1111764 1111764 1111764 4 Control panel right 1111765 1111765 1111765 1111765 5 Control panel left 1111766 111...

Page 18: ...6 5 26 5 27 5 36 5 25 5 26 5 34 5 Sound power level per stage dB A 34 37 43 34 41 45 35 36 45 34 35 43 Power supply V Hz 230 1 50 Enclosure class IP X0 Electr rated power consumption 1 kW 0 04 0 03 0...

Page 19: ...ssure power Level V l h dB A dB A QH kW LA C V l h QH kW LA C V l h QH kW LA C V l h QH kW LA C V l h KWK 100 4R min 128 25 5 34 0 48 31 83 0 69 35 9 119 9 0 91 41 1 159 3 1 13 46 196 8 5 147 28 5 37...

Page 20: ...in the field are more than just sales people above all they must be advisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably Howe...

Reviews: