REMKO HTL 150 FB Operation,Technology,Spare Parts Download Page 12

12 

Forced-Air Oil Burner

 

 
After loosening the 4 housing screws and the additional 
2 screws (pay attention to the arrow), the assembly 
base plate is removed from the housing and suspended 
to the side. 
The most important functional components for mainte-
nance are immediately accessible. 

The assembly base plate can also be suspended hori-
zontally for maintenance, installation and replacement 
of the nozzle. 

Proceed as follows: 

1.  Hold the assembly base plate horizontally. 

2.  Slide the right mount sideways into the suspension. 

3.  Suspend the left side up into the lug.. 

All dimensions are approximate values in mm. The opti-
mum setting must be adjusted to the local and struc-
tural conditions. 

Adjusting the ignition electrode and swivel disc 

7 – 8 

After the nozzle has been changed and the air intake 
nozzle adjusted, the assembly base plate is reinserted 
in the reverse order.

 

Adjusting the air intake nozzle

 

The necessary burner pressure can be adjusted with-
out changing the outlet diameter using the adjustable 
air intake nozzle depending on the combustion cham-
ber resistance and chimney draft. 

Loosen the Allen screw and ro-
tate the air intake nozzle to the 
desired position (pay attention to 
the arrow). 

“min”  =  lower burner    
  

pressure 

“max” =  higher burner   
  

pressure 

Adjusting the secondary air 

(nozzle connection rod setting) 

Left rotation (+) = higher scale value  

Ö

 lower pressure behind the swivel disc 

Ö

 higher performance range. 

Right rotation (-) = lower scale value  

Ö

 higher pressure behind the swivel disc 

Ö

 lower performance range. 

Adjusting the pump pressure

 

The oil pressure must be adjusted and/or checked prior 
to operation and maintenance.  

Do not run the pump without oil!

 

1.  Remove the plug on the “P” measuring connection. 

Pay attention to the seal. 

2. Open all oil shut-off mechanisms and switch the 

burner on with the unit operating switch. 

3.  Adjust the necessary oil pressure in accordance with 

the nozzle size and the unit capacity.  

4.  Remember that the required oil pressure first has to 

be set for the full capacity phase (DV2) and then the 
oil pressure for the start-up phase (DV1) because 
the pressure adjustment DV2 can also affect DV1.  

5.  Switch the burner off on the unit operating switch. 

6.  Disassemble the manometer and reinsert the plugs 

with seals.

 

*

 

The burner may only be operated at the second 
level. The first level may only be used as start-up 
relief! 

Summary of Contents for HTL 150 FB

Page 1: ...REMKO powerful like a bear REMKO HTL 150 FB HTL 250 FB Mobile oil fired heating centers Edition D R02 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...TL 150 FB 16 Wiring Diagram HTL 200 250 FB 17 Wiring Diagram HTL FB 18 Technical Data 18 Maintenance Log 19 Read these instructions carefully before setting up operating the unit Our guarantee becomes...

Page 4: ...r protected from weather conditions They are operated with a separate forced air oil burner and are suitable for outdoor operation The units are equipped both with a high performance axial fan that re...

Page 5: ...temperature 35 to 40 C automatically switches the air supply fan on beforehand The green fan operating light is illuminated on the control panel for monitoring purposes Warm air is blown out When the...

Page 6: ...for combustion exists when for example the room content in m is equivalent to at least 10 times the rated heat output in kW of all heating units in operation in the room and natural air venti lation i...

Page 7: ...eans of pipes or special hot air and plastic hoses The possible lengths of these lines depend on the air side resistance of the warm air ducting Make sure to observe the following when using warm air...

Page 8: ...t be exceeded Setting the thermal overcurrent relay 1 Measure each phase separately to eliminate meas urement errors 2 Set the thermal overcurrent relay according to the following calculation Multiply...

Page 9: ...cool the combus tion chamber and the heat exchanger and switches off at a later time The fan can be run several times until the unit is finally switched off Never interrupt the power supply except in...

Page 10: ...lters if necessary Check the unit for mechanical damage and replace defective parts if necessary Check the fan blades and combustion chamber with heat exchanger on a regular basis for dirt and clean t...

Page 11: ...on 3 Attach the exhaust connection properly Check the seal 7 and replace if necessary 4 Reattach all lines and connections and check them 5 Put the unit into operation and check that all operating mod...

Page 12: ...tance and chimney draft Loosen the Allen screw and ro tate the air intake nozzle to the desired position pay attention to the arrow min lower burner pressure max higher burner pressure Adjusting the s...

Page 13: ...opens and the burner would run with an insufficient quantity of air Setting Air quantity level 2 adjustment lever orange Turn back the adjustment lever for the Air quantity level 2 counter clockwise D...

Page 14: ...16 17 18 20 19 21 22 23 11 9 8 46 7 30 29 28 27 26 31 32 33 34 35 36 39 38 40 41 42 43 44 45 25 24 Unit housing Combustion chamber with heat exchanger 47 31 We reserve the right to make changes to dim...

Page 15: ...ottom rear 1105389 1105389 1105389 26 Fan console 1105390 1105391 1105391 27 Fan 1105375 1105377 1105380 28 Start up nozzle 1105376 1105378 1105378 29 Air intake plate 1105392 1105393 1105393 30 Linin...

Page 16: ...N X1 10 t 2 1 3 t t 1 0 2 K7 H4 H7 H3 H6 1 N L1 F4 RT STB A1 A2 1 5 4 X1 8 X1 12 X1 11 X1 7 X1 5 X1 4 X1 6 TW rot rot gr n rot St rlampe Brenner St rlampe Ventilator Betriebslampe Heizen Hilfsrelais F...

Page 17: ...3M K1M N L1 F4 K1T STB A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 X1 5 X1 4 X1 6 TR 2 rot gr n rot K5 K2M K3M D Sch tz Phasenfolge Relais Zeitrelais Ventilator Sch tz Betriebslampe Ventilator Betriebs stunde...

Page 18: ...6 8 7 1 Power consumption fuel pre heating W 300 300 300 Fuse protection customer installed A 3 x 16 3 x 16 3 x 16 Temperature increase t K 56 57 59 Sound pressure level LpA 1m 2 dB A 71 74 74 Air int...

Page 19: ...Date 9 Date 10 Date Signature Signature Signature Signature Signature 11 Date 12 Date 13 Date 14 Date 15 Date Signature Signature Signature Signature Signature 16 Date 17 Date 18 Date 19 Date 20 Date...

Page 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Reviews: