Point of emissions
Assessment level in accordance
with TA noise
days in dB(A)
nights in dB(A)
Industrial areas
70
70
Commercial areas
65
50
Core areas, village areas and mixed zones
60
45
General residential areas and small housing estates
55
40
Exclusively residential areas
50
35
Spa areas, hospitals and mental institutions
45
35
Isolated noise peaks of short duration may not exceed 30 dB(A) during the day and 20 dB(A) at night.
Minimum distances in mm for the outdoor modules for CMF/CMT 120/160
1
2
3
4
5
6
>= 100 (150)
>= 500 (1000)
>= 200 (200)
>= 1000
>= 200 (200)
>= 500 (1000)
>= 100 (150)
>= 100 (200)
>= 100 (200)
>= 200
(200)
>= 1000 (1000)
max. 500
max.
500
Fig. 39: Minimum distances in mm for the outdoor modules for CMF/CMT 120 and in brackets for the CMF/
CMT 160
1:
Against a wall, free flow air forward, backward
flow restriction
2:
Against a wall, facing the wall air outlet, flow
front restriction
3:
Freely between two walls, facing the wall outlet,
Sides: flow restrictions in front and rear
4:
In a niche, free flow air to the front, flow restric-
tion rear and on both sides.
5:
Before a covered wall, free flow air to the front,
rear and top of flow restrictions
6:
Before a covered wall, free flow air to the front,
flow restrictions behind, above and on both
sides
39