Climatic region: -14°C
Old house with domestic hot-water heating (share 18%)
Type
COP by compressor rated
frequency
Annual performance
number with inlet/outlet
temperature differential: 7K
and inlet temperature...
Annual performance
number with inlet/outlet
temperature differential:
10K and inlet temperature...
A-7/
W35
A2/W35
A10/
W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120
2,48
3,44
4,41
3,89
3,77
3,65
3,61
3,48
3,36
CMF/CMT 160
2,57
3,24
4,72
3,79
3,67
3,56
3,52
3,40
3,27
New construction with hot-water heating (share 18%)
Type
COP by compressor rated
frequency
Annual performance
number with inlet/outlet
temperature differential: 7K
and inlet temperature...
Annual performance
number with inlet/outlet
temperature differential:
10K and inlet temperature...
A-7/
W35
A2/W35
A10/
W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120
2,48
3,44
4,41
3,77
3,56
3,52
3,48
3,35
3,22
CMF/CMT 160
2,57
3,24
4,72
3,64
3,52
3,40
3,37
3,24
3,12
Climatic region: -16°C
Old house with domestic hot-water heating (share 18%)
Type
COP by compressor rated
frequency
Annual performance
number with inlet/outlet
temperature differential: 7K
and inlet temperature...
Annual performance
number with inlet/outlet
temperature differential:
10K and inlet temperature...
A-7/
W35
A2/W35
A10/
W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120
2,48
3,44
4,41
3,79
3,67
3,56
3,52
3,40
3,27
CMF/CMT 160
2,57
3,24
4,72
3,71
3,59
3,48
3,45
3,33
3,20
New construction with hot-water heating (share 18%)
Type
COP by compressor rated
frequency
Annual performance
number with inlet/outlet
temperature differential: 7K
and inlet temperature...
Annual performance
number with inlet/outlet
temperature differential:
10K and inlet temperature...
A-7/
W35
A2/W35
A10/
W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120
2,48
3,44
4,41
3,66
3,54
3,42
3,38
3,26
3,13
CMF/CMT 160
2,57
3,24
4,72
3,55
3,43
3,32
3,28
3,17
3,04
Note: A differential of 7K has a standard floor-heating layout, a differential of 10K is typical for a radiator
system
Additional key data: a heating-threshold temperature of 15°C for old construction and 12°C in new construc-
tion, a differential at the condenser (test-bench measurements: 5K)
REMKO CMF/CMT