10
Tech n i ca l Da t a
Series CLA 25 CLA 40 CLA 50 CLA 100
rated heat power max. kW 29 36 58 106
ratedheat output kW 26,5 30 50 91
rated air output m³/h 1150 1600 3200 5200
fuel h e a t i n g o i l E L o r l i q u i d g a s
fuel consumption, max. kg/h 2,6 3,0 5,0 9,0
nozzle (Steinen)
2)
USG/°S 0,65/60° 0,75/60° 1,25/60° 2,25/60°
pump-pressure (mit ÖV)
2)
bar 11-12 11-12 11-12 11-12
flue gas loss % 9,4 10 10 10
electrical connection 1~ V 230 230 230 230
frequency Hz 50 50 50 50
rated current A 1,95 1,95 3,3 4,7
power take-up kW 0,4 0,4 0,7 1,0
capacitor (fan) µF 3 3 8 14
fuse protection (required) A 10 10 10 10
sound pressure level L
pA
1m
1)
dB(A) 54 56 66 64
air outlet Ø mm 285 285 345 500
waste gas connection Ø mm 180 180 180 200
weight (without burner) kg 110 110 153 260
dimensions: length, total mm 1385 1385 1685 1955
width, total mm 640 640 770 1020
hight, total mm 930 930 1030 1240
Dimensions and specifications subject to change
1) noise measuring (without burner) DIN 45635 - 01 - KL 3
2) The mentionend nozzle-sizes and pump-pressures result from coordination tests on the test bench. The fuel consumption had been
measured out.
On account of tolerances and oil-temperature these specifications must be considered as guiding values.
S = operating switch
KL = terminal strip
SK = switch box, cpl.
C = capacitor
(CLA 100: capacitor in
terminal box of fan)
RT = room thermostat socket
M = fan motor
TR = fan control thermostat
STB = safety temperature limiter
TW = burner temperature monitor
KB = triple combination control, cpl.
WS = plug to burner, 7 poles
(only if burner has been
installed by our works)
blau = blue
braun = brown
schwarz = black
Wi r i n g Di a g r a m