Minimum clearances
E
C
B
A
D
Air intake
Air outlet
Air intake
Air outlet
All dimensions are given in mm
Installation inside buildings
■
Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
lofts, adjoining rooms or halls
(figure 4)
.
■
Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room
and which can compensate
any additional pressure loss in
ventilation ducts
(figure 4)
.
■
Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes
placed opposite each other
(figure 4)
.
Minimum clearances
Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.
BL 261 AT, BL 351 AT
A
150 mm
B
700 mm
C
400 mm
D
150 mm
E
200 mm
■
Comply with any regulations
and conditions affecting
the statics of the building.
If necessary, fit acoustic
installation.
Warm air
Fresh
cold air
Light
well
Outdoor component
Warm air
Light
well
additional
fan
4 Installation inside buildings
REMKO BL
18