Problem display by blinker code
Display
LED in AT
Fault description
Checks
Remedial measures
No.
16
red
No.
17
yellow
No.
18
green
ER01 flashes
-
-
-
Air circulation sensor on
indoor unit is defective /
triggered
Check resistance (see p. 19)
Replace defective sensor
ER02 flashes
-
-
-
Indoor unit power supply
defective
Check power supply
Repair power supply
ER03 flashes
-
-
-
Frost protection sensor on
indoor unit faulty/tripped
Check resistance (see p. 19)
Replace defective sensor
ER04 flashes
-
-
-
Vaporiser fan motor speed
too low / defective
Check fan motor, fan blade
Replace motor or blade
ER05 flashes
-
-
-
EEPROM indoor unit control
board error
ER06 flashes
-
-
-
Communication error
between IT and AT
ER07 flashes
-
-
-
Refrigerant fill quantity
incorrect
Check refrigerant pressure.
ER08 flashes
O
•
•
AT condenser sensor faulty /
tripped
Check resistance (see p. 19)
Replace defective sensor
ER09 flashes
•
O
•
Communication error
between IT and AT
Check wiring and connections
ER10 flashes
O
O
•
Compressor speed too low
Check cable connections, pipe connections,
shut-off valves, compressor
ER11 flashes
O
•
O
Over-current error
Check voltage, cable connections,
refrigerant pressure, ambient conditions
ER12 flashes
•
O
O
PFC error
Check cable connections, pipe connections,
shut-off valves, compressor
ER13 flashes
×
•
•
Inverter-control board
communication error
Check cable connections, pipe connections,
shut-off valves, compressor
ER14 flashes
•
•
×
Inverter board safety shut-off Check cable connections, pipe connections,
shut-off valves, compressor
ER15 flashes
O
•
×
Indoor unit outdoor air sensor
defective
Check resistance (see p. 19)
Replace defective sensor
ER16 flashes
×
O
•
Compressor temperature too
high
Check condenser for dirt, check refrigerant
pressure Check fan
ER18 flashes
×
O
O
EEPROM Outdoor unit
control board error
ER19 flashes
×
×
×
Compressor start error
Check cable connections, pipe connections,
shut-off valves, compressor
ER20 flashes
×
×
•
Outdoor unit system error
•
×
×
Incorrect setting type for unit Contact specialist firm
HL
O
×
•
Power supply fault
Check voltage, cable connections,
refrigerant pressure, ambient conditions
OT
×
×
O
Ambient temperature too
high
Switch unit off, switch unit back on when
ambient temperature is lower
OP
×
•
O
Liquid temperature too high
Check condenser for dirt, check refrigerant
pressure Check fan
OD
×
O
×
Hot gas temperature too high Check condenser for dirt, check refrigerant
pressure Check fan
OH
O
×
×
Inverter board overheat
• = Off
O = On
× = flashes
REMKO ATY