In the air circulation mode, the air in the room is only circulated.
The room temperature cannot be changed in this mode. The cooling
or heating operation is not activated. The fan has four speeds. Neither
the ion generator nor turbo mode can be selected in this mode.
Air circulation MODE
AIR CIRCULATION
MODE
In the heating mode, you can heat the room in spring or fall. The desired
room temperature is set with buttons
/
in 1 °C increments. If the
room temperature is 1 °C below the selected nominal temperature, then
the indoor unit starts to warm up the air in the room. If the adjusted
room temperature is exceeded by approx. 0.5°C, then the controller
turns the heater function off. To protect the compressor, the controller
will not switch the heating on again until
it has waited for 3 minutes.
Heating MODE
> 6 Min.
> 3 Min.
> 6 Min.
30 sec.
30 sec.
Nominal tempe5
°C
Nominal tempe2
°C
Fan operation IT
Fan operation AT
Compressor operation AT
Actual temperature
Stop heating operation
Heating mode
Start heating mode
Functional diagram
Operation
Stop
Reverse flow valve
30 sec.
30 sec.
During the defrosting cycle, the indoor unit vaporiser fan and
the outdoor unit condenser fan are switched off.
After the cycle is concluded, the fans are switched to their previous
settings.
< 7 Min.
Defrost period
15 sec.
60 sec.
Fan operation IT
Fan operation AT
Compressor operation AT
Operation
Stop
Reverse flow valve
30 sec.
30 sec.
30 sec.
3 Min.
HEATING
OPERATION
MODE
MODE
REMKO ATY