Fault indication
Green status LED flashes as follows:
Problem
No connection with
iSense RF
.
Solution
- Check whether the
iSense RF
indicates a fault or is on.
- Try to re-establish the connection between the
iSense RF
and
the
Base station;
see Chapter 5.
- If this does not solve the problem, relocate the
iSense RF
or the
Base station
or remove obstacles that can interfere with the RF
signal; see
paragraph 3.1.
Fault indication
Green LED flashes as follows:
Problem
Power problem
Solution
Check whether the boiler is on and whether the
Base station
is
correctly connected. If the boiler does not support OpenTherm Smart
Power, then connect an external (5 V DC 300mA) adapter.
Fault indication
Green LED flashes as follows:
Problem
There is no OpenTherm communication for 60 seconds.
Solution
- Check whether the boiler is on and whether the
Base station
is
correctly connected.
tabel 02 Fault indications green status LED