70
EN
F216: No connection with base station (iSense RF only)
Fault indication
Fault code F216
w
and
c
are lite up
Display text
Wireless communication fault.
Solution
Check whether the iBase for the boiler is on and is functioning correctly
(consult the transmitter manual if necessary).If there is no connection
between the iSense and iBase, then restore the connection as follows:
- Put the iBase in connection mode. Consult the iBase manual for this.
- On the iSense select
Menu > Settings > Users > Connection.
If this does not solve the problem, look for another location for the
iSense and/or iBase or remove “obstacles” that could interfere with the
RF signal.