Parameter
Description
Adjustment range
Quinta Ace160
Gas leakage control VPS
0 = not connected
1 = connected
0
Minimum anti-cycle time of burner
0 to 20 minutes
3
CH part load time
5 to 180 seconds
30
Post-circulation of the pump (CH)
1 to 98 minutes
99 = Continuous
1
Maximum pump speed for CH
2 - 10 (x 10%)
100
Minimum pump speed for CH
2 - 10 (x 10%)
20
CH hysteresis
1 to 25ºC
10
Factory setting
To restore the factory settings or when replacing the
control unit, enter the values CN1 and CN2 from the
data plate for parameters
and
Detection of (optional) PCBs connec
ted (auto-detect)
Carry out an auto-detect after removing a PCB
-
Tab.5
Factory settings for PCB SCB-01 parameters
Parameter
Description
Adjustment range
Quinta Ace160
Relay 1 status message
0 = Off
1 = Switched if boiler is locked out
2 = Switched if boiler is not locked out
3 = Switched if boiler is running
4 = Switched if boiler is not running
5 = Reserve setting
6 = Reserve setting
7 = Switched in the event of boiler maintenance mes
sage
8 = Switched if boiler is running for CH
9 = Switched if boiler is running for DHW
10 = Switched if CV pump is running
11 = Switched if boiler is locked out or shuts down
0
Relay 2 status message
0 = Off
1 = Switched if boiler is locked out
2 = Switched if boiler is not locked out
3 = Switched if boiler is running
4 = Switched if boiler is not running
5 = Reserve setting
6 = Reserve setting
7 = Switched in the event of boiler maintenance mes
sage
8 = Switched if boiler is running for CH
9 = Switched if boiler is running for DHW
10 = Switched if CV pump is running
11 = Switched if boiler is locked out or shuts down
0
0–10V signal function
0 = pump modulation signal (set parameter EP028 to
0, 1 or 2; depending on the pump used)
1 = required boiler power (set parameter EP028 to 0)
2 = current boiler power (set parameter EP028 to 0)
3 to 9 = No signal
0
0-10 V signal function for PWM pump
or GBS (building management system)
0 = 0-10 V linear or Wilo pump
1 = 0-10 V offset or Grundfos pump
2 = PWM pump
3 = Do not use
4 = Do not use
5 = Do not use
6 = Do not use
7 to 9 = No signal
0
7 Settings
14