Parameter
Description
Adjustment range
Quinta Ace160
Minimum water pressure WPS
0 - 7 bar
0 = No minimum
0.7
Release waiting time
0 to 255 seconds
0
Service burning hours
0 - 51,000
17,400
Maintenance message
0 = maintenance message off
1 = maintenance message on
2 = maintenance message A, B, C
2
Service operating hours
0 - 51,000
17,400
Outside temperature; upper limit for
heating
15 to 30.5ºC
22
Forced summer mode
0 = Off
1 = On
0
Reserve parameter
Do not change
0
Start frost protection on basis of out
side temperature
-3 to 3 ºC
0
Start boiler pump
0 = pomp on for each heat demand
1 = pomp on for heat demand directly to boiler
0
Reserve parameter
Do not change
90
Maximum flow temperature for CH op
eration
0 to 90ºC
80
Reserve parameter
Do not change
1
Holiday set point for CH operation
5 to 20ºC
6
Night time set point for CH operation
5 to 30ºC
16
Comfort base point for CH operation
15 to 90ºC
15
Night time base point for CH operation 5 to 90ºC
15
Heating curve gradient
0 to 4 (only with outside sensor)
2.5
Reserve parameter
Do not change
101
Reserve parameter
Do not change
0
Reserve parameter
Do not change
0
Reserve parameter
Do not change
20
Reserve parameter
Do not change
20
Maximum speed for DHW operation
rpm
6800
DHW hysteresis
0 to 60 ºC
7
DHW offset temperature
0 to 60 ºC
5
Hysteresis load
0 to 60 ºC
0
DHW extra offset temperature
0 to 60 ºC
0
Reserve parameter
Do not change
50
Reserve parameter
Do not change
20
0-10 V input signal
0 = Off
1 = temperature regulator
2 = Heat output control
1
Fan speed for CH (maximum)
rpm
6800
Fan speed for CH (minimum)
rpm
1900
Fan start up speed for CH
rpm
2200
Gas pressure control GPS
0 = not connected
1 = connected
0
ΔT modulate down
5 to 25 ºC
25
Average flow temperature factor
0 - 255 seconds
1
7 Settings
7616014 - v.03 - 15022016