Supplied By www.heating spares.co  Tel. 0161 620 6677

Remeha Gas

550/550 Duo

8

As most systems contain a variety of metals which can 
react with each other to cause corrosion.  It is con-
sidered good practice to provide some form of water 
treatment (especially in open vented systems) in order to 
prevent or reduce the following:
-  Metallic corrosion;
-  Formation of scale and sludge;
-  Microbiological contamination;
-  Chemical changes in the untreated system water.

Suitable chemicals and their use should be discussed 
with a specialist water treatment company prior to car-
rying out any work. The specification of the system 
and manufacturers recommendations must be taken into 
account, along with the age and condition of the system. 
New systems should be flushed thoroughly to remove all 
traces of flux, debris, grease and metal swarf generated 
during installation.  Care to be taken with old systems 
to ensure any black metallic iron oxide sludge and other 
corrosive residues are removed, again by thoroughly 
flushing, ensuring that the system is drained completely 
from all low points.

Note:

  Please ensure that the new boiler plant is not 

in circuit when the flushing takes place, especially if 
cleansing chemicals are used to assist the process.

Under no circumstances is the boiler to be operated 
with cleaning chemicals in the system.

To Summarise:

-  Minimise water loss;
-  Prevent pumping over in open vented systems;
-  Provide adequate air venting at all high points;
-  Keep pH level between 7 - 9 when using additives;
-  Maximum chlorine content of 200 mg/l;
Take advice on the suitability of inhibitors.

4.1.5  Noise level

The noise level measured around the boiler depending 
on boiler room construction is about 50-55 dBA. Noise 
levels taken at 1 meter from the boiler.

4.2  Chimneys

The average flue gas temperature is so low that the 
chimney must be made in accordance with the guide-
lines of British Gas (BS 6644).

4.3  Installation standards

The following instructions must be adhered to when the 
Remeha Gas 550/550 Duo is installed:
Gas Safety (installation and use) Regulations 1984 (as 
amended).
In addition to the above regulations, this boiler must be 
installed in compliance with:
-  Current I.E.E. Regulations for electrical installations
-  Local building regulations
-  The Building Standards (Scotland)
-  (Consolidation) Regulations
-  By-laws of the local water undertaking
-  Health and Safety Document No 635 ‘The Electricity 

at Work Regulations 1989’.

It should also be in accordance with the relevant recom-
mendations in the current editions of the following British 
Standards and Codes of Practice, viz. BS 5440 Pt 1 and 
2, BS 5449, BS 5546, 
BS 6798, BS 6891 and BG.DM2.

Lawfully all gas appliances must be installed by compe-
tent persons (e.g. Corgi, ACOPS).
Failure to install appliances correctly could lead to 
prosecution.
It is in your own interest and that of safety to ensure that 
the law is complied with.

Important:

The Remeha Gas 550/550 Duo is a certified appliance 
and must not be modified or installed in any way con-
trary to these ‘Installation and Servicing Instructions’. 
Manufacturer instructions must NOT be taken in any way 
as when overriding statutory obligations.

Summary of Contents for Gas 550

Page 1: ...Supplied By www heating spares co Tel 0161 620 6677 1 Atmospheric gas boiler 278 1058 kW R e m e h a G a s 5 5 0 5 5 0 D u o Technical information Remeha Gas 550 550 Duo...

Page 2: ...6 3 3 Specification control box 11 6 3 4 Specification Ignition transformer 12 6 4 Functions 12 6 4 1 Flame control lock out 12 6 4 2 Thermostats shutdown lock out 12 6 4 3 Water level control lock ou...

Page 3: ...high low atmospheric gas burners suitable for natural gas cat I 2 H 20 mbar It is supplied in sections for delivery and on site assem bly The boiler meets the requirements of the CE regulations at th...

Page 4: ...heating spares co Tel 0161 620 6677 Remeha Gas 550 550 Duo 4 3 DIMENSIONS AND TECHNICAL DATA 3 1 Dimensions Remeha Gas 550 Fig 01 Dimensions Remeha Gas 550 00 05F 79 00002 Flow 107 int Return 107 int...

Page 5: ...47 55 62 70 77 B mm 1240 1460 1680 1900 2120 2340 2560 D mm 300 350 400 450 450 500 500 E mm 1295 1295 1295 1295 1295 1295 1245 Dimensions H mm 1730 1730 1730 1610 1730 1610 1730 Flue temperature C 15...

Page 6: ...plied By www heating spares co Tel 0161 620 6677 Remeha Gas 550 550 Duo 6 3 2 Dimensions Remeha Gas 550 Duo Fig 02 Dimensions Remeha Gas 550 Duo 00 05F 79 00003 Flow 107 int Return 107 int Gas 2 Flue...

Page 7: ...or 0 3 bar at a maximum working temperature of 95 C 4 1 3 Water flow The minimum water flow through the boiler on shut down is Output boiler in kW m3 h 93 This minimum flow must be maintained for app...

Page 8: ...ween 7 9 when using additives Maximum chlorine content of 200 mg l Take advice on the suitability of inhibitors 4 1 5 Noise level The noise level measured around the boiler depending on boiler room co...

Page 9: ...lation measure ments in mm centre of nipple holes floor area Fig 03 Remeha Gas 550 00 05F 79 00004 number of sections 10 12 14 16 18 20 22 Size A 965 1185 1405 1625 1845 2065 2285 Size D 300 350 400 4...

Page 10: ...2 Installation 2 Recommended layout for boiler installation measure ments in mm centre of nipple holes floor area number of sections Fig 04 Remeha Gas 550 Duo 00 05F 79 00005 size A size D number of s...

Page 11: ...on 5 Hour run meter full load hours option 6 Analogue thermometer for flow temperature 7 High limit thermostat preset to 110 C 8 Lock out warning lamp 9 Option for rematic weather compensator 10 Reset...

Page 12: ...esets after 3 minutes provided that the temperature also falls Type Honeywell L6068A fixed setpoint is 70 C Note The Gas 550 Duo requires two 6 3 3 Specification control box Control box Satronic MMI 8...

Page 13: ...Duo has two sets 7 5 Water pressure Each section is hydraulically tested at 10 bar Maximum test pressure for the assembled boiler block is 7 8 bar Minimum working pressure is 0 8 bar at a maximum wor...

Page 14: ...e gas train Note The Gas 550 Duo has two control panels and requires two sets of operating controls and has two sets of function indication 9 4 Electrical connections The boiler is pre wired Only the...

Page 15: ...Supplied By www heating spares co Tel 0161 620 6677 15 9 7 Wiring diagrams Fig 08 Electrical principle diagram 04 05F SC 00001...

Page 16: ...tats to about 85 C 8 If a control system is built in put the selector switch on manual operation 9 Switch on the boiler If a valve leakage control is installed the following will take place A membrane...

Page 17: ...nt disc of the pressure switch until the pressure control operates The control box shuts down the gas supply and will restart 15 Adjustment of the gas pressure switch HD optional Switch the boiler to...

Page 18: ...e Maintenance Isolate power controls and gas supply Remove front top casings and flue hood covers Remove gas manifold Remove the burners and floor plates Clean the internal flue ways of the boiler Cle...

Page 19: ...begin of red zone no flame signal of pilot burner no spark red zone failing or unstable flame of pilot burner end of yellow zone begin of green zone no flame signal of main burner Green zone end of g...

Page 20: ...Office Unit 3 Kestrel Close Quarry Hill Ind Estate Ilkeston Derbyshire DE7 4RD Tel 0115 9440778 Fax 0115 9440588 Copyright All technical and technological information contained in these technical inst...

Reviews: