background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

7

Number of sections

2 x 10

2 x 12

2 x 14

2 x 16

2 x 18

Nominal heat

output

kW

139-556

170-680

202-806

233-932

265-1058

Hi /

NCV

kW

160-618

195-756

232-896

266-1036

301-1176

Nominal

heat input

Hs /

GCV

kW

177-686

217-840

256-996

296-1152

335-1306

Gas consumption

m

3

/h

66

80

94

110

124

B

mm

1240

1460

1680

1900

2120

Dimensions

Ø D

mm

450*

500*

600*

650

650*

Water contents

litre582

698

814

930

1046

Boiler weight (dry)

kg

2900

3390

3880

4370

4620

Flue gas flow rate

kg/h

1385

1694

2066

2478

2752

Table 02  Technical data Remeha Gas 550 Duo
* Supplied with a flue gas pipe adapter

APPLICATION INFORMATION

4.1  L.P.H.W. system 
4.1.1  Water temperature

Maximum water temperature is 110°C (high limit ther-
mostat).
Highest boiler water temperature is 95°C (control ther-
mostat).
Minimum return water temperature is 20°C at a flow rate 
related to a 

t of 20°C (flow/return temp).

4.1.2  Water pressure

Boiler sections are factory pressure tested at 10 bar.
Maximum pressure test boiler block is 7,8 bar.
Maximum working pressure is 6 bar 
Minimum working pressure is 0,8 bar at a maximum 
working temperature of 110°C or 0,3 bar at a maximum 
working temperature of 95°C.

4.1.3  Water flow

The minimum water flow through the boiler on shut down 
is:
 

Output boiler in kW  = m

3

/h

93 

 

This minimum flow must be maintained for approxima-
tely 5 minutes after the burner stops firing to avoid high 
temperature shut down due to residual heat gain.
Due to the design and manufacture of the boiler no 

specific minimum water flow requirements exist other 
then for overheating protection.

4.1.4  Water treatment

The system should be filled with mains cold water (for 
the UK this will usually have a pH of between 
7 and 8).
Pressurised installations with a boiler/system content 
ratio of 1:10 or less should not require water treatment, 
provided that the following conditions apply:
1. The system is flushed thoroughly to remove all fluxes 

and debris and then filled completely once.

2. Make up water is limited to 5 % per annum.
3. The hardness of the water does not exceed 360 ppm 

(20°D).

All scale deposits will reduce the efficiency of the boiler 
and should be prevented. However provided the above 
is complied with any scale produced will not be too 
detrimental to the boiler efficiency and will not reduce 
the anticipated life expectancy of the boiler.

Note:

  Scale deposits in excess of 3 to 5 mm will reduce 

boiler efficiency and greatly increase the risk of prema-
ture casting failure.

Summary of Contents for Gas 550

Page 1: ...Supplied By www heating spares co Tel 0161 620 6677 1 Atmospheric gas boiler 278 1058 kW R e m e h a G a s 5 5 0 5 5 0 D u o Technical information Remeha Gas 550 550 Duo...

Page 2: ...6 3 3 Specification control box 11 6 3 4 Specification Ignition transformer 12 6 4 Functions 12 6 4 1 Flame control lock out 12 6 4 2 Thermostats shutdown lock out 12 6 4 3 Water level control lock ou...

Page 3: ...high low atmospheric gas burners suitable for natural gas cat I 2 H 20 mbar It is supplied in sections for delivery and on site assem bly The boiler meets the requirements of the CE regulations at th...

Page 4: ...heating spares co Tel 0161 620 6677 Remeha Gas 550 550 Duo 4 3 DIMENSIONS AND TECHNICAL DATA 3 1 Dimensions Remeha Gas 550 Fig 01 Dimensions Remeha Gas 550 00 05F 79 00002 Flow 107 int Return 107 int...

Page 5: ...47 55 62 70 77 B mm 1240 1460 1680 1900 2120 2340 2560 D mm 300 350 400 450 450 500 500 E mm 1295 1295 1295 1295 1295 1295 1245 Dimensions H mm 1730 1730 1730 1610 1730 1610 1730 Flue temperature C 15...

Page 6: ...plied By www heating spares co Tel 0161 620 6677 Remeha Gas 550 550 Duo 6 3 2 Dimensions Remeha Gas 550 Duo Fig 02 Dimensions Remeha Gas 550 Duo 00 05F 79 00003 Flow 107 int Return 107 int Gas 2 Flue...

Page 7: ...or 0 3 bar at a maximum working temperature of 95 C 4 1 3 Water flow The minimum water flow through the boiler on shut down is Output boiler in kW m3 h 93 This minimum flow must be maintained for app...

Page 8: ...ween 7 9 when using additives Maximum chlorine content of 200 mg l Take advice on the suitability of inhibitors 4 1 5 Noise level The noise level measured around the boiler depending on boiler room co...

Page 9: ...lation measure ments in mm centre of nipple holes floor area Fig 03 Remeha Gas 550 00 05F 79 00004 number of sections 10 12 14 16 18 20 22 Size A 965 1185 1405 1625 1845 2065 2285 Size D 300 350 400 4...

Page 10: ...2 Installation 2 Recommended layout for boiler installation measure ments in mm centre of nipple holes floor area number of sections Fig 04 Remeha Gas 550 Duo 00 05F 79 00005 size A size D number of s...

Page 11: ...on 5 Hour run meter full load hours option 6 Analogue thermometer for flow temperature 7 High limit thermostat preset to 110 C 8 Lock out warning lamp 9 Option for rematic weather compensator 10 Reset...

Page 12: ...esets after 3 minutes provided that the temperature also falls Type Honeywell L6068A fixed setpoint is 70 C Note The Gas 550 Duo requires two 6 3 3 Specification control box Control box Satronic MMI 8...

Page 13: ...Duo has two sets 7 5 Water pressure Each section is hydraulically tested at 10 bar Maximum test pressure for the assembled boiler block is 7 8 bar Minimum working pressure is 0 8 bar at a maximum wor...

Page 14: ...e gas train Note The Gas 550 Duo has two control panels and requires two sets of operating controls and has two sets of function indication 9 4 Electrical connections The boiler is pre wired Only the...

Page 15: ...Supplied By www heating spares co Tel 0161 620 6677 15 9 7 Wiring diagrams Fig 08 Electrical principle diagram 04 05F SC 00001...

Page 16: ...tats to about 85 C 8 If a control system is built in put the selector switch on manual operation 9 Switch on the boiler If a valve leakage control is installed the following will take place A membrane...

Page 17: ...nt disc of the pressure switch until the pressure control operates The control box shuts down the gas supply and will restart 15 Adjustment of the gas pressure switch HD optional Switch the boiler to...

Page 18: ...e Maintenance Isolate power controls and gas supply Remove front top casings and flue hood covers Remove gas manifold Remove the burners and floor plates Clean the internal flue ways of the boiler Cle...

Page 19: ...begin of red zone no flame signal of pilot burner no spark red zone failing or unstable flame of pilot burner end of yellow zone begin of green zone no flame signal of main burner Green zone end of g...

Page 20: ...Office Unit 3 Kestrel Close Quarry Hill Ind Estate Ilkeston Derbyshire DE7 4RD Tel 0115 9440778 Fax 0115 9440588 Copyright All technical and technological information contained in these technical inst...

Reviews: