IIPBNXX- 111517
POWER INLET BOX
CAT. NO. PBN-Series
INSTALLATION INSTRUCTIONS
IMPORTANT: Installation of this power inlet box and related wiring must be done by a qualified electrician in compliance
with all applicable electrical codes. When used to power a structure, this inlet must be used in conjunction with a transfer
switch. Not for indoor use. When using an engine driven generator, locate the power inlet box away from doors and
windows to avoid the build up of carbon monoxide from the engine exhaust in enclosed areas.
INSTALLING A REMOTELY LOCATED POWER INLET BOX FOR SUPPLYING
POWER TO THE POWER INLET OF A TRANSFER SWITCH OR PANEL
GENERATOR TO THE POWER INLET BOX and CONNECTING THE POWER
INLET BOX TO THE TRANSFER SWITCH
Using a generator cord suitable for the purpose, attach the male plug into the generator outlet and the female connector
into the power inlet in the power inlet, and turn to lock if the plug is a locking type.
Model
Number
Amps/VAC
Building
Wire Gauge
Gen
Outlet
PBN
Inlet
PBN15
15A 125VAC
Min #14
Max #12
5-15R
5-15F
PBN20
20A 125/250VAC
Min #12
Max #10
L14-20R
L14-20F
PBN21
20A 125VAC
Min #12
Max #10
L5-20R
L5-20F
PBN30
30A 125/250VAC
Min #10
Max #8
L14-30R
L14-30F
PBN31
30A 125VAC
Min #10
Max #8
L5-30R
L5-30F
PBN50
50A 125/250VAC
Min #8
Max #4
14-50R
CS6369
CS6375
PBN51
50A 125VAC
Min #8
Max #4
CS6370
CS6377
PBN52
50A 125/250VAC
Min #8
Max #4
14-50R
14-50F
RELIANCE CONTROLS
CORPORATION
2001 YOUNG COURT
RACINE, WI 53404
800-634-6155
Remove the cover from the
Outdoor Power Inlet Box
by unscrewing
the two screws on the front of the box with a #2 Phillips
screwdriver. Temporarily slide out the wiring tray. Mount the back
plate of the power inlet box on the outside of the building in a
convenient location, using the three holes provided. Remove one
of the POP-FAST reusable knockouts from the box by pushing out
from the inside of the inlet box. Using
copper building wire only
and approved wiring methods, run the appropriate wires from the
transfer switch wiring compartment through the removed knockout
in the power inlet box
.
3/4-inch fittings can be installed directly into
the knockout hole in the Power Inlet Box. To use 1/2-inch fittings,
insert the plastic knockout washer (provided in the power inlet box)
into the open hole, and then install the fitting.
Strip the wire insulation 5/8" and connect the wires to the wire ports
on the back of the power inlet in the power inlet box tray as follows
making sure there is no wire insulation in any terminal and the inlet
terminal screws are tightened to 20 inch-pounds torque:
Hot red wire to the terminal marked “X”
Hot black wire to the terminal marked "Y".
Neutral wire to the nickel-plated neutral terminal marked "W".
Ground inlet wire to green screw terminal marked “G.”
* On 125VAC only inlets, the terminals may be identified by the
screws; the brass screw is hot, silver screw is neutral, and green
screw is ground.
Slide the power inlet tray back into the
power inlet box and tuck the
wires in neatly. Replace the inlet box cover using the two screws.
These inlet boxes are rated for use
with wires having insulation rated at
60° C or at 75° C.