Maintenance

Model RFC43 and RFC49 Concealed Sprinklers should 

be inspected quarterly and the sprinkler system main-
tained in accordance with NFPA 25.  Do not clean sprin-
klers with soap and water, ammonia or any other clean-
ing fluids.  Remove dust by using a soft brush or gentle 
vacuuming. Remove any sprinkler cover plate assembly 
which has been painted (other than factory applied) or 
damaged in any way.  A stock of spare sprinklers should 
be maintained to allow quick replacement of damaged or 
operated sprinklers.  Prior to installation, sprinklers should 
be maintained in the original cartons and packaging until 
used to minimize the potential for damage to sprinklers 
that would cause improper operation or non-operation.

Model RFC43 and RFC49 Residential
Concealed Sprinkler Speci

fi

 cation

Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design 
density of 0.05 gpm/ft

2

.   Sprinkler frame and deflector 

shall be of bronze frame construction having a ½” NPT 
thread.  Thermal element shall consist of an approved 
black-painted beryllium-nickel fusible solder link with 
symmetric lever mechanism, maintaining a Teflon-coated 
Belleville spring washer and machined brass cap water 
seal assembly containing no plastic parts.  Sprinkler 
K-factor shall be nominal 4.3 (62.4), having a 

7

/

16

” orifice. 

Temperature rating shall be Ordinary 165°F (74°C); cover 
plate temperature rating to be 135°F (57°C).  Cover plate 
assembly shall consist of a brass cover plate and copper 

alloy retainer flange allowing a ½” cover plate adjust-
ment.  Any secure engagement between the cover plate 
and the cup will assure that the drop-down deflector is 
properly located below the ceiling.  A plastic protective 
cap shall be provided and factory installed inside the 
sprinkler cup to protect the drop-down sprinkler deflec-
tor from damage, which could occur during construction 
before the cover plate is installed.  Standard cover fin-
ish:  [Chrome] [White] [Specialty – specify].  Residential 
concealed sprinklers shall be Reliable Model RFC43, 
SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 
(Bulletin 006).

Ordering Information

Specify:

Sprinkler Model
Cover Plate Finish
Thread-On or 
Push-On Feature

1.
2.
3.

Cover Plate Finishes 

(1)

Standard Finishes

Chrome
White

Special Application 
Finishes

Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome

(1)

 Other colors and finishes avail-

able. Consult factory for details.

Note:

 Paint or any other coatings 

applied over the factory finish will 
void all approvals and warran-
ties.