3.
Maintenance
Model RFC43 and RFC49 Concealed Sprinklers should
be inspected quarterly and the sprinkler system main-
tained in accordance with NFPA 25. Do not clean sprin-
klers with soap and water, ammonia or any other clean-
ing fluids. Remove dust by using a soft brush or gentle
vacuuming. Remove any sprinkler cover plate assembly
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
Model RFC43 and RFC49 Residential
Concealed Sprinkler Speci
fi
cation
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft
2
. Sprinkler frame and deflector
shall be of bronze frame construction having a ½” NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler
K-factor shall be nominal 4.3 (62.4), having a
7
/
16
” orifice.
Temperature rating shall be Ordinary 165°F (74°C); cover
plate temperature rating to be 135°F (57°C). Cover plate
assembly shall consist of a brass cover plate and copper
alloy retainer flange allowing a ½” cover plate adjust-
ment. Any secure engagement between the cover plate
and the cup will assure that the drop-down deflector is
properly located below the ceiling. A plastic protective
cap shall be provided and factory installed inside the
sprinkler cup to protect the drop-down sprinkler deflec-
tor from damage, which could occur during construction
before the cover plate is installed. Standard cover fin-
ish: [Chrome] [White] [Specialty – specify]. Residential
concealed sprinklers shall be Reliable Model RFC43,
SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616
(Bulletin 006).
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On Feature
1.
2.
3.
Cover Plate Finishes
(1)
Standard Finishes
Chrome
White
Special Application
Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
(1)
Other colors and finishes avail-
able. Consult factory for details.
Note:
Paint or any other coatings
applied over the factory finish will
void all approvals and warran-
ties.