background image

2.

ing temperature rises, the solder holding the cover plate 
releases the cover allowing the deflector to drop into posi-
tion and exposing the sprinkler inside to ceiling tempera-
ture.  The subsequent operation of the solder link opens 
the waterway and causes the deflector to drop into posi-
tion to distribute the discharging water in a hemispherical 
pattern below the sprinkler deflector.  Any adjustment of 
thread engagement between the cover plate and cup will 
assure that the drop-down deflector is properly located 
below the ceiling.  The residential distribution pattern con-
tains a finer droplet size than a standard sprinkler, and the 
pattern produces significantly higher wall wetting.  

After a 2

5

/

8

 inch diameter hole is cut in the ceiling, the 

sprinkler is to be installed with the Model FC Wrench.  
When installing a sprinkler, the wrench is first positioned 
into the sprinkler/cup assembly and around the hexagonal 
body of the sprinkler frame.  The Wrench must bottom out 
against the cup in order to ensure proper, safe installation.  
The sprinkler is then tightened into the pipe fitting.  When 
inserting or removing the wrench from the sprinkler/cup 
assembly, care should be taken to prevent damage to the 
sprinkler.  DO NOT WRENCH ON ANY OTHER PART OF 
THE SPRINKLER/CUP ASSEMBLY.  MODEL RFC43 AND 
RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED 
ONLY WITH 135°F RATED COVERS.

Note:

 A leak tight ½” NPT (R1/2) sprinkler joint can be ob-

tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m).  Do not 
tighten sprinklers over maximum recommended torque.  It 
may cause leakage or impairment of the sprinklers.

Cover assemblies provide up to 

1

/

2

” (13mm) of adjust-

ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option, the 
cover assembly is pushed onto the cup and final adjust-
ment is made by turning the cover clockwise until the skirt 
flange makes full contact with the ceiling.  Cover removal 
requires turning in the counter-clockwise direction.

In ceilings that have a plenum space above the sprinkler,  

the plenum space may have neutral or negative pressur-
ization but must not be positively pressurized.  Inspect all 
sprinklers after installation to ensure that the gap between 
the cover plate and ceiling and the 4 slots in the cup are 
all open and free from any air flow impediment.

Temperature Rating

Sprinkler

Cover Plate

Max. Ambient Temp.

165°F/74°C

135°F/57°C

100°F/38°C

Installation Data: RFC43 (SIN RA0612)

Thread

Size

inch (mm)

K Factor

Sprinkler

Spacing

ft. (m)

Maximum

Distance to 

Wall

ft. (m)

Minimum

Distance between 

sprinklers

 ft. (m)

Minimum Required

Sprinkler Discharge

Flow

gpm (Lpm)

Press.

psi (bar)

½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)

4.3
4.3
4.3
4.3
4.3

12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)

  6 (1.83)

7 (2.13)
8 (2.43)
9 (2.74)

10 (3.05)

8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)

12 (45)
13 (49)
13 (49)
18 (68)
21 (79)

  7.8 (0.54)

9.1 (0.63)
9.1 (0.63)

17.5 (1.21)
23.8 (1.64)

Note: 1 bar = 100 Kpa

Installation Data: RFC49 (RA0616)

Thread

Size

inch (mm)

K Factor

Sprinkler

Spacing

ft. (m)

Maximum

Distance to 

Wall

ft. (m)

Minimum

Distance between 

sprinklers

ft. (m)

Minimum Required

Sprinkler Discharge

Flow

gpm (Lpm)

Press.

psi (bar)

½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)

4.9
4.9
4.9
4.9
4.9

12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)

  6 (1.83)

7 (2.13)
8 (2.43)
9 (2.74)

10 (3.05)

8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)

13 (49)
13 (49)
13 (49)

17 (64.3)
20 (75.7)

  7.0 (0.48)

7.0 (0.48)
7.0 (0.48)

12.0 (0.83)
16.7 (1.14)

Note: 1 bar = 100 Kpa

FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.

Reviews: