General Description 

The Reliable Model DDX-LP PrePaK system with integrated 

nitrogen generation (Sizes 2” (50mm), 2½” (65 mm), 3” (80 
mm) and 4” (100 mm)) is a completely self-contained, super-
vised dry pipe system that can be readily installed within a floor 
space of less than 7 ft

2

 (0.65 m

2

). Refer to Fig. 1 for cabinet 

dimensions. Installation of the DDX-LP PrePaK system requires 
just three piping connections: the water supply, the sprinkler 
system and the drain. Reference locations of these piping con-
nections are shown in Fig. 1. Independent electrical supplies 
are required for the optional system air compressor (115 or 220 
VAC) and the nitrogen generator (115 VAC).

Full assembly drawings for the units are available on the Reli-

able Automatic Sprinkler Company website (www.reliablesprin-
kler.com).

The Reliable Model DDX-LP N2-Blast

®

 PrePaK system incor-

porates a South-Tek Systems FPS-900 pressure swing adsorp-
tion N2-Blast

®

 nitrogen generator, complete with independent 

air compressor, nitrogen storage tank, and control system. The 
nitrogen generator is completely wired, tested, and integrated 
with the Model DDX-LP PrePaK system, and supplies 98% pure 
nitrogen to the piping network to limit electrochemical, galvanic, 
and micro-biologically influenced corrosion (MIC). Operation 
and maintenance information can be found in this bulletin as 
well as the South-Tek Systems website (www.southteksystems.
com).

The heart of the Reliable Model DDX-LP PrePaK system is 

the Model DDX-LP Dry Pipe Valve. The Reliable Model DDX-
LP Dry Pipe Valve is a hydraulically operated, mechanical valve 
designed for use as a primary control valve in a low pressure 
dry pipe valve system. The trim set used with the Model DDX-
LP Dry Pipe Valve contains the Reliable Model LP Dry Pilot Ac-
tuator releasing device. This Actuator allows the system air or 
nitrogen pressure to be considerably less than the water supply 

pressure (see Table A). The following benefits are a direct result 

of lower air pressure:
1.  In refrigerated area systems, lower air pressure decreases 

the possibility of ice plugs that could impede or prevent 

the flow of water to fire sprinkler heads in the event of fire.

Note:

 N2-Blast

®

 and Blast-off

®

 are registered trademarks of South-Tek Systems, LLC.

Summary of Contents for N2-Blast DDX-LP PrePaK

Page 1: ...rePaK system incor porates a South Tek Systems FPS 900 pressure swing adsorp tion N2 Blast nitrogen generator complete with independent air compressor nitrogen storage tank and control system The nitr...

Page 2: ...ar The 2 2 1 2 3 and 8 sizes are rated for a maximum pressure of 250 psi 17 2 bar and the 4 and 6 sizes are rated for a maximum pressure of 300 psi 20 7 bar Water temperature must be maintained betwee...

Page 3: ...3 Fig 1...

Page 4: ...nal box mounted on the inside of the enclosure All field wiring connec tions are made at this terminal box A separate power connection is provided for the optional air compressor Note The air compress...

Page 5: ...16 Secure the handle of the Model B Manual Emergency Station in the OFF position with a nylon tie supplied with the assembly Inspection And Testing Of The DDX LP PrePaK Systems Refer to Figure 2 1 Wat...

Page 6: ...6 Fig 2 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity...

Page 7: ...7 Fig 3...

Page 8: ...er has drained then close Note Leaving the condensate drain open for an extended pe riod of time may allow excess air nitrogen to bleed off and result in accidental release of the Model LP Dry Pilot A...

Page 9: ...r can lead to incorrect gas supply The nitrogen generator produces nitrogen at a low flow rate which quickly dissipates into the air Nitrogen is not poison ous but do not directly inhaled since high c...

Page 10: ...not adjust the factory preset cut in and out pressure without first consulting with South Tek Systems Patented BlastOff Leak Detection System The BlastOff Leak Detection is a patented feature which se...

Page 11: ...r further troubleshoot ing Low System Pressure Alarm Mode Lo n2 The low system pressure alarm activates when a sys tem pressure is detected below the normal functioning limits of the nitrogen generato...

Page 12: ...esponding filter housings Hand tighten only After replacing the filters check the filter bowls for leaks by turn ing on the unit momentarily Turn the unit off to reinstall the front cover and then pow...

Page 13: ...Fig 5 Nitrogen Generator Filter Locations 13...

Page 14: ...o 580 gallons 9 Nitrogen Generator Model B1 Accelerator 3 3 2 1 HP 115 VAC Systems up to 1170 gallons 4 4 3 1 2 HP 220 VAC 60 Hz Systems up to 580 gallons A 2 w System Side Control Valve 4 1 HP 220 VA...