2.

Technical Data

Sprinkler 

Model

Thread

Size

Ori

fi

 ce 

Size

Temperature

Rating

Max. Ambient

Temp.

Maximum 

Sprinkler 

Spacing

Maximum

Bay

Spacing

Maximum

Coverage 

Area

Approvals

Sprinkler 

Identi

fi

 cation 

Number

(SIN)

°F

°C

°F

°C

MBEC-14 

HSW

¾” NPT 

(R¾)

0.70” 

(18mm)

165

74

100

38

14ft (4.3m)

14’ - 0 x 12’ - 6

25ft.

(7.6m)

175ft.

2

 

(16.3m

2

)

cULus

FM

NYC

R6932

212

100

150

66

Maintenance

Model MBEC-14 Sprinklers should be inspected and the 

sprinkler system maintained in accordance with NFPA 25.  Do 
not clean sprinklers with soap and water, ammonia or any other 
cleaning fluids.  Remove dust by using a soft brush or gentle 
vacuuming.  Remove any sprinkler that has been painted (other 
than factory applied) or damaged in any way.  A stock of spare 
sprinklers should be maintained to allow quick replacement of 
damaged or operated sprinklers.  Prior to installation, sprinklers 
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that 
would cause improper operation or non-operation.

Model MBEC-14 Sprinkler Speci

fi

 cation

Sprinklers shall be a control-mode, standard response, ex-

tended coverage horizontal sidewall sprinkler specifically listed/
approved for installation on primary structural members (I-
beams) of pre-engineered metal buildings, up to 32 ft (9.8 m) 
in height and having 25 ft. (7.6 m) wide bays.  Sprinklers shall 
be [(cULus Listed) (New York City MEA Approved, 258-93-E) 
to protect ordinary and extra hazard] [FM Approved to protect 
ordinary hazard] occupancies as well as for miscellaneous and 
in-process storage as permitted by [NFPA 13] [FM Global Data 
Sheet 3-26].  Sprinklers shall be capable of covering an area of 
175 ft

2

 and being installed below the ceiling between 12” (305 

mm) and 16” (406 mm).  If there is an interior liner panel installed 
on the bottom side of the roof purlins, the acceptable deflector 
distance is 4”- 6” below the liner panel. Roof/ceilings shall have 
slopes not exceeding a pitch of 2/12 (a roof /ceiling slope of 
16.7%).  Sprinkler frame and deflector to be of bronze construc-
tion.  Fusible solder link assembly shall utilize the strut and lever 
principle of operation with a [black-painted, 165°F (74°C)] [gray-
painted 212°F (100°C)] beryllium-nickel thermal element. Water 
seal assembly shall consist of a Teflon™-coated Bellville spring 
washer and brass cap assembly containing no plastic parts.  
Extended coverage horizontal sidewall sprinklers shall have a 
nominal K-factor of 14.0 (202) and ¾” NPT threaded end con-
nections.  Sprinkler temperature rating shall be [Ordinary 165°F 
(74°C)] [Intermediate 212°F (100°C)].  Extended coverage hori-
zontal sidewall sprinklers shall be Reliable Model MBEC-14, SIN 
R6932 (Bulletin 169).

Ordering Information

Specify:

1. Sprinkler 

Model

2. Temperature 

Rating

3. Sprinkler 

Finish

Finishes

(1)

 

Standard Finishes

Bronze
Chrome Plated

(1)

 Other colors and finishes are available on

    special order. Consult factory for details.

Model H Sprinkler Wrench

Use Model H Wrench for Model 
MBEC-14 HSW Sprinkler
removal and installation.