Technical Data
Sprinkler
Model
Thread
Size
Ori
fi
ce
Size
Temperature
Rating
Max. Ambient
Temp.
Maximum
Sprinkler
Spacing
Maximum
Bay
Spacing
Maximum
Coverage
Area
Approvals
Sprinkler
Identi
fi
cation
Number
(SIN)
°F
°C
°F
°C
MBEC-14
HSW
¾” NPT
(R¾)
0.70”
(18mm)
165
74
100
38
14ft (4.3m)
14’ - 0 x 12’ - 6
25ft.
(7.6m)
175ft.
2
(16.3m
2
)
cULus
FM
NYC
R6932
212
100
150
66
Maintenance
Model MBEC-14 Sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gentle
vacuuming. Remove any sprinkler that has been painted (other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation.
Model MBEC-14 Sprinkler Speci
fi
cation
Sprinklers shall be a control-mode, standard response, ex-
tended coverage horizontal sidewall sprinkler specifically listed/
approved for installation on primary structural members (I-
beams) of pre-engineered metal buildings, up to 32 ft (9.8 m)
in height and having 25 ft. (7.6 m) wide bays. Sprinklers shall
be [(cULus Listed) (New York City MEA Approved, 258-93-E)
to protect ordinary and extra hazard] [FM Approved to protect
ordinary hazard] occupancies as well as for miscellaneous and
in-process storage as permitted by [NFPA 13] [FM Global Data
Sheet 3-26]. Sprinklers shall be capable of covering an area of
175 ft
2
and being installed below the ceiling between 12” (305
mm) and 16” (406 mm). If there is an interior liner panel installed
on the bottom side of the roof purlins, the acceptable deflector
distance is 4”- 6” below the liner panel. Roof/ceilings shall have
slopes not exceeding a pitch of 2/12 (a roof /ceiling slope of
16.7%). Sprinkler frame and deflector to be of bronze construc-
tion. Fusible solder link assembly shall utilize the strut and lever
principle of operation with a [black-painted, 165°F (74°C)] [gray-
painted 212°F (100°C)] beryllium-nickel thermal element. Water
seal assembly shall consist of a Teflon™-coated Bellville spring
washer and brass cap assembly containing no plastic parts.
Extended coverage horizontal sidewall sprinklers shall have a
nominal K-factor of 14.0 (202) and ¾” NPT threaded end con-
nections. Sprinkler temperature rating shall be [Ordinary 165°F
(74°C)] [Intermediate 212°F (100°C)]. Extended coverage hori-
zontal sidewall sprinklers shall be Reliable Model MBEC-14, SIN
R6932 (Bulletin 169).
Ordering Information
Specify:
1. Sprinkler
Model
2. Temperature
Rating
3. Sprinkler
Finish
Finishes
(1)
Standard Finishes
Bronze
Chrome Plated
(1)
Other colors and finishes are available on
special order. Consult factory for details.
Model H Sprinkler Wrench
Use Model H Wrench for Model
MBEC-14 HSW Sprinkler
removal and installation.