background image

Bulletin 044
December 2022

Page 8 of 9

www.reliablesprinkler.com

CEILING

FULL DEPTH BLOCKING OF SAME MATERIAL AS JOIST
(OR NONCOMBUSTIBLE MATERIAL). MAXIMUM 32 ft (9.75 m)
BETWEEN ROWS OF BLOCKING.

UPPER
DECK

SEE NOTE 1

AND 1A

SEE NOTE 2

6 in. (150 mm) OR

1/3 DEPTH OF SPACE

(WHICHEVER IS GREATER)

MINIMUM 1/4 in. PLYWOOD
DRAFT CURTAIN AT MAXIMUM
31 ft (9.45 m) SPACING

LOCATION OF STEEL PIPE
IN CONCEALED SPACE IS
NOT RESTRICTED

NOTE 3

INSTALLATION NOTES:

1.

DISTANCE EVALUATED AS PART OF THE cULus LISTING: 12 in. TO 36 in. (300 mm TO 900 mm). NFPA 13 PERMITS INSTALLATION OF THE
SPRINKLER WHERE THIS DISTANCE IS LESS THAN 12 in. (300 mm).

1A.   WHERE CEILING IS NOT SUPPORTED BY JOISTS (EXAMPLE: SUSPENDED A.C.T.) MEASUREMENT POINT IS TOP OF CEILING.

2.

DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1-1/2 in.  TO 4 in. (38  mm TO 100 mm) BELOW BOTTOM OF TOP CHORD. IN NO
CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE SOLID OR COMPOSITE WOOD JOIST.

3.

INSTALL SPRINKLER WITH FRAME ARMS PARALLEL TO PIPE.

HYDRAULIC DESIGN AREA REQUIREMENTS

1.

WET OR DRY SYSTEM:  BLOCKING AND DRAFT CURTAINS (OR FULL HEIGHT WALLS) MUST BE PROVIDED AT 1000 ft

2

 (93 m

2

)

MAXIMUM AREAS. CALCULATE ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA.

SPRINKLER SPACING AND COVERAGE AREA

A. 14 ft (4.3 m) MAXIMUM BETWEEN SPRINKLERS

B.

6 ft (1.8 m) MINIMUM BETWEEN SPRINKLERS

C. 196 ft

2

 (18.2 m

2

) MAXIMUM COVERAGE AREA PER SPRINKLER

12 in. (300 mm)

MAX JOIST

DEPTH

Figure 6

Solid Wood Joist (Non-Filled), Steel Pipe

Draft Curtain and Blocking: Required at 1000 Ft

2

 (93 m

2

)

Summary of Contents for KFR-CCS

Page 1: ...damage the sprinkler and will void the manufacturer s warranty Damaged sprinklers must be immediately replaced A leak tight NPT R1 2 sprinkler joint can be obtained with an installation torque of appr...

Page 2: ...onal sprinklers that are required for protection of CPVC piping that is offset over an obstruction Maximum Distance Spacing Between Sprinklers Refer to Figures 2 through 7 Maximum Coverage Area Per Sp...

Page 3: ...whichever is smaller Where the members at the bottom of the concealed space are greater than 6 in 150 mm tall installing CPVC piping directly on top of those members shall be permitted When using 1 i...

Page 4: ...NCEALED SPACE ABOVE THE TOP OF THE CEILING WHICHEVER IS SMALLER SEE NOTE 1 HYDRAULIC DESIGN AREA REQUIREMENTS A WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE PROVIDED AT MAXIMUM AREAS OF 10...

Page 5: ...E PROVIDED AT MAXIMUM AREAS OF 1000 ft2 93 m2 OR LESS CALCULATE ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA 2 WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE NOT PROVIDED OR PROVIDED AT AREA...

Page 6: ...R WHERE THIS DISTANCE IS LESS THAN 12 in 300 mm 1A WHERE CEILING IS NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1...

Page 7: ...S THAN 12 in 300 mm 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE SOLID OR COMPOSITE WO...

Page 8: ...NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE...

Page 9: ...C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE S...

Reviews: