background image

Bulletin 044
December 2022

Page 5 of 9

www.reliablesprinkler.com

UPPER

DECK

CEILING

TOP CHORD DEPTH 4 in.
(100 mm) OR LESS

SEE NOTE 1

LOCATION OF STEEL PIPE
IN CONCEALED SPACE IS
NOT RESTRICTED

SEE NOTE 2

INSTALLATION NOTES:

1.

DISTANCE EVALUATED AS PART OF THE cULus LISTING: 12 in. TO 60 in. (300 mm TO 900 mm). NFPA 13 PERMITS INSTALLATION OF

THE SPRINKLER WHERE THIS DISTANCE IS LESS THAN 12 in. (300 mm).

2.

DEFLECTOR TO BE NO MORE THAN 2 in. (50 mm) MAXIMUM BELOW BOTTOM OF TOP CHORD. IN NO CASE SHALL DEFLECTOR BE

ABOVE THE BOTTOM OF THE TOP CHORD.

3.

INSTALL SPRINKLER WITH FRAME ARMS PARALLEL TO PIPE.

HYDRAULIC DESIGN AREA REQUIREMENTS

1.

WET OR DRY SYSTEM:  WHERE DRAFT CURTAINS (OR FULL HEIGHT WALLS) ARE PROVIDED AT MAXIMUM AREAS OF 1000 ft

2

 (93 m

2

)

OR LESS, CALCULATE ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA.

2.

WET SYSTEM:  WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE NOT PROVIDED, OR PROVIDED AT AREAS EXCEEDING 1000 ft

2

(93 m

2

), CALCULATE AN AREA OF 1000 ft

2

 (93 m

2

) OR SIX SPRINKLERS, WHICHEVER CREATES THE GREATER DEMAND.

3.

DRY SYSTEM: WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE NOT PROVIDED, OR PROVIDED AT AREAS EXCEEDING 1000 ft

2

(93 M

2

), CALCULATE AN AREA OF 1000 ft

2

 (93 m

2

) OR NINE SPRINKLERS, WHICHEVER CREATES THE GREATER DEMAND.

4-1/2 in. (114 mm) MINIMUM FROM
CENTERLINE OF SPRINKLER TO

FACE OF TOP CHORD OF WOOD

TRUSS OR BAR JOIST

NOTE 3

SPRINKLER SPACING AND COVERAGE AREA

A. 16 ft (4.9 m) MAXIMUM BETWEEN SPRINKLERS

B.

6 ft (1.8 m) MINIMUM BETWEEN SPRINKLERS

C.

256 ft

2

 (23.8 m

2

) MAXIMUM COVERAGE AREA PER SPRINKLER

Figure 3

Unobstructed Wood Truss or Bar Joist, Steel Pipe 

Draft Curtains: Optional

Summary of Contents for KFR-CCS

Page 1: ...damage the sprinkler and will void the manufacturer s warranty Damaged sprinklers must be immediately replaced A leak tight NPT R1 2 sprinkler joint can be obtained with an installation torque of appr...

Page 2: ...onal sprinklers that are required for protection of CPVC piping that is offset over an obstruction Maximum Distance Spacing Between Sprinklers Refer to Figures 2 through 7 Maximum Coverage Area Per Sp...

Page 3: ...whichever is smaller Where the members at the bottom of the concealed space are greater than 6 in 150 mm tall installing CPVC piping directly on top of those members shall be permitted When using 1 i...

Page 4: ...NCEALED SPACE ABOVE THE TOP OF THE CEILING WHICHEVER IS SMALLER SEE NOTE 1 HYDRAULIC DESIGN AREA REQUIREMENTS A WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE PROVIDED AT MAXIMUM AREAS OF 10...

Page 5: ...E PROVIDED AT MAXIMUM AREAS OF 1000 ft2 93 m2 OR LESS CALCULATE ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA 2 WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE NOT PROVIDED OR PROVIDED AT AREA...

Page 6: ...R WHERE THIS DISTANCE IS LESS THAN 12 in 300 mm 1A WHERE CEILING IS NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1...

Page 7: ...S THAN 12 in 300 mm 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE SOLID OR COMPOSITE WO...

Page 8: ...NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE...

Page 9: ...C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE S...

Reviews: