background image

4.

2.  A minimum of two (2) detectors must be installed for each zone 

in the protected area.

3.  Only Class A method of wiring detectors shall be used.
For Double-Interlock Preaction Systems: 
1.  Are required for freezer or refrigerated room applications, or 

where conditions will allow water to freeze in the system piping 
prior to sprinkler actuation.

2.  Cross-zoning of preaction system detectors is prohibited, ex-

cept where used as a secondary system to a gaseous sup-
pression system.

3.  A minimum of two (2) detectors must be installed for each zone 

in the protected area.

4.  Only Class A method of wiring detectors shall be used.

Electrical devices and control panel must be specified to 

meet  Canadian requirements.  This option is available. 

Note: 

 Although PrePak units are UL Listed, custom built units are 

sometimes supplied upon request.  The components within these 
special units maintain their individual Listings, whereas the assem-
bled units do not.

PrePak units are also available without their door-mounted Potter 

PFC-4410-RC Releasing/Control Panel and Air Compressor.  These 
units will still retain their Listings, however the installing contractor 
should make sure that any remote controlled Releasing/Control Pan-
els used with these units are Listed and programmed to handle the 
required sequence of operation necessary to operate the automatic 
sprinkler system.

Any unauthorized modification or addition made on-site to a fac-

tory built Listed unit will void the Listing.  Such modifications or addi-
tions may void the units warranty as well.  Consult Reliable’s Techni-
cal Services Department before proceeding with such modifications 
or additions.

Technical Data 

The Reliable Model H 1½” (40mm) PrePaK is rated for a minimum 

supply pressure of 20 psi (1.4 bar) and a maximum supply pressure 
of 175 psi (12 bar). 

Friction loss, expressed in equivalent length of Sch. 40 pipe and 

based on Hazen-Williams formula with C=120 and a flowing velocity 
of 15 ft/s (4.6m/s), is 36 ft. (11m).  This friction loss value includes all 
components of the Model H Riser Assembly and Model G Right-
Check™ Check Valve.

Shipping Weight:            460 lbs. (209 kg)
Enclosure Dimensions:  64” H x 24” W x 27” D
                             (162.6cm H x 61cm W x 68.6cm D)
The following is a list of Technical Data Bulletins which describe the 

valves and devices which in this system:

Deluge Valve

507

Right-Check™ Riser Valve

806

Low Air Pressure Switch

5400928 (Potter)

Hydraulic Emergency Station                    

506

Mechanical Sprinkler                              

612/613

Solenoid Valve

718

Water Flow Pressure Alarm

5400928 (Potter)

Pressure Maintenance Device                  

252

Releasing Control Panel             

 (Potter Manual #5403550)

Detectors                                                      

722

Fire Alarm Devices                                      

700

System Design Considerations 

The automatic sprinklers, releasing devices, fire detection devices, 

manual pull stations, and signaling devices which are utilized with 
the Reliable Model H 1½” (40mm) PrePaK must be UL and/or ULC 
Listed, as applicable. 

The steel enclosure and all interconnecting piping must be locat-

ed in a readily visible and accessible location and in an area that can 
be maintained at a minimum temperature of 40°F (4°C). 

Note:

 Heat 

tracing is not permitted.

The solenoid valve is operated and supervised by the Potter Elec-

tric Releasing Control Panel.  Details on the electrical connections of 
this system to a Potter Model PFC-4410-RC Releasing Control Panel 
can by found in Potter Manual #5403550, Installation, Operation and 
Instruction of PFC-4410 Fire Alarm/Releasing Panel (this manual is 
included with other pertinent manuals and shipped inside the enclo-
sure).  This panel is fully zone and output programmable and may 
be adapted to several applications.  The following table provides a 
quick reference to various programs (found in this Bulletin and Potter 
Manual #5403550) that may be utilized with the Model H PrePaK:

Desired

Application

(1)

 

Description

Program No.

Single Interlock

Single Hazard,  2 Alarm Zones 

with 1 Waterflow Zone and 2 

Supervisory Zones

Potter Program #6

Custom Program

#1 (NYC)

Single Interlock, 

Cross-Zoned

Single Hazard, Cross-Zoned, 2 

Alarm Zones with 1 Waterflow 

Zone and 2 Supervisory Zones

Potter Program 

#7 

(2)

Double Interlock,

2 Independent 

Events 

Single Hazard, 2 Alarm Zones 

with 1 Waterflow Zone and 1 

Supervisory Zone

Potter Program

#9

Double Interlock, 

Cross-Zoned 

3 Independent  

Events 

Single Hazard, Cross-Zoned, 3 

Alarm Zones with 1 Waterflow 

and 1 Supervisory Zone

Potter Program 

#10

(1)

 Refer to Potter Manual #5403550, included with the

    PrePaK, for other programming options.

(2)

 Factory Program Setting.

System Supervising Pressure Requirements 

In accordance with NFPA 13 (1996), when using the Reliable 

Model H 1½” (40mm) PrePaK in double interlock applications, a 
minimum of 7 psi (0,5 bar) pneumatic pressure is required to super-
vise the sprinkler system. When initially filling the system with air, the 
enclosure door should remain open to provide maximum air flow 
to the compressor.  The Model A-2 Pressure Maintenance Device, 
supplied with the system, is factory set to maintain system pneu-
matic pressure at approximately 10 psi (0.7 bar).  

Readjusting system pressure to approximately 10 psi (0.7 bar) is 

accomplished by referring to Reliable Bulletin 251 for adjustment 
procedure.  The low pneumatic pressure supervisory switch is 
factory set to operate between 8 and 4 psi (0.6 bar to 0.3 bar) with 
decreasing pressure.  Adjustment, if required, should be made ac-
cording to Potter Bulletin 5400928 included with the switch.

System Electrical Requirements 

All releasing, alarm, and detection devices in the Reliable Model H 

1½” (40mm) PrePaK are supervised by a Potter Model PFC-4410-
RC Releasing Control Panel.  To utilize the door of the steel enclosure 
as a mount for the releasing control panel, all of the terminals are 
translated to two water-tight terminal boxes mounted on the interior 
wall of the enclosure.  

Note:

  The EOL resistors have also been relo-

cated.  It is from these terminal boxes that all field wiring is connect-

Summary of Contents for H PrePak

Page 1: ...iew Park Drive Elmsford New York 10523 ModelHPrePak PreactionSystem 1 40mm Bulletin 723 Rev H Bulletin723Rev H Instructionsfor Installation Operation CareandMaintenance 10 PSI 0 7 bar Pneumatic Supervising Pressure SingleInterlock DoubleInterlock ...

Page 2: ...e operation of two detectors before the solenoid valvecanopen Note Cross zoneddetectionsystemsarenotper mittedinNewYorkCityandarenotFactoryMutualApproved The solenoidvalve whenclosed ispreservingsupplywaterpressurein theinletoftheReliableModelHDelugeRiserAssembly Actuating the solenoid valve releases that water pressure allowing water flow into the sprinkler system in readiness for the subsequent ...

Page 3: ...Figure1 InstallationDimension 3 ...

Page 4: ...e steel enclosure and all interconnecting piping must be locat edinareadilyvisibleandaccessiblelocationandinanareathatcan bemaintainedataminimumtemperatureof40 F 4 C Note Heat tracingisnotpermitted ThesolenoidvalveisoperatedandsupervisedbythePotterElec tricReleasingControlPanel Detailsontheelectricalconnectionsof thissystemtoaPotterModelPFC 4410 RCReleasingControlPanel canbyfoundinPotterManual 540...

Page 5: ...YSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST Figure2 WiringDiagram ...

Page 6: ...6 Figure3 WiringDiagram ...

Page 7: ... annunciate andwillnotfillthesprinklersystempipingwithwater Withcoexisting initiating signals one electric and one pneumatic the control panel will now energize the solenoid valve to release water through the PrePaK into the system piping and out the open sprinkler for com pleteoperationofthesystem When the releasing control panel energizes the solenoid valve open water flows from the supply throu...

Page 8: ...te gauges There should be no pressure reading on the water gauge directly above the manual emer gencyreleasingstationwhenthesystemisproperlyreset Resetting Double Interlock Systems Refer to Figure 1 1 ClosethesupervisedvalvecontrollingwatersupplytotheMod el H Riser Assembly and shut off the system s air supply at the ModelA 2Device 2 Openalldrainvalvesandthemanualemergencystationvalve todrainthesy...

Page 9: ...E AC POWER POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST ...

Page 10: ...Figure5 WiringDiagram 10 ...

Page 11: ...11 Figure6 WiringDiagram ...

Page 12: ...Figure7 WiringDiagram 12 ...

Page 13: ... 4 Low Air Supervisory 1 ALARM X X 2 WATERFLOW X 3 SUPERVISORY X X 4 RELEASE X X INPUT 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUT 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release circuit and the gene...

Page 14: ...14 Figure8 WiringDiagram ...

Page 15: ...ell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and the general alarm bell Activation of either conventional zone will operate the general alarm bell Activation of the waterflow zone will operate the waterflow bell Activation of either the low air zone or the supervisory zone will operate the supervisory bell...

Page 16: ...16 Figure9 WiringDiagram ...

Page 17: ...nd the low air alarm zone at the same time will operate the solenoid release circuit and the general alarm bell Activation of the conventional zone only will operate the general alarm output Activation of the low air supervisory zone will operate the bsupervisory bell output Activation of the waterflow zone will operate the waterflow bell output Activation of the low air alarm zone will operate th...

Page 18: ...18 Figure10 WiringDiagram ...

Page 19: ... OPERATION Activation of both conventional zones and the low air alarm zone at the same time will operate the solenoid release circuit and the general alarm bell Activation of either conventional zone only will operate the general alarm output Activation of the waterflow zone will operate the waterflow bell output Activation of the low air alarm zone will operate the supervisory bell output It wil...

Page 20: ...Figure6 DoubleInterlockPreaction ComponentIdentification 20 ...

Page 21: ...on until the display reads ZONE 3 OUTPUTS 18 Press the SELECT button The 1 should appear under the v 19 Press the SET button twice The panel is completely pro gramed except for the custom banner and zone messages If thesemessagesarenotdesired thenslidetheprogramswitch backup INPUTS 1 conventional zones 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm...

Page 22: ...22 Figure12 WiringDiagram ...

Page 23: ...SERVICE MAY ELIMINATE THE FIRE PROTECTION OF THAT SYS TEM PRIOR TO PROCEEDING NOTIFY ALL AUTHORITIES HAVING JURISDICTION CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREA WARNING PRIOR TO OPERATING THE SOLENOID VALVE BE SURE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE 1 Inspections It is imperative that the system be inspec...

Page 24: ...sh automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrical sprinkler alarm switches Water flow detectors Deluge valves Detector check val...

Reviews: