21.
Custom Program #1
(For New York City Compliance)
Single Interlock Programming Instructions for
New York City Compliance (Single Hazard, 2 Alarm
Zones, 1 Water
fl
ow Zone, and 2 Supervisory Zones)
1. Apply power to the panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads “PASS-
WORD=000.”
4. To enter a password, press the SELECT button until the proper
number is displayed above the “^” symbol; then press the SET
button to move to the next digit. After entering the third num-
ber, the display will change (All panels are shipped with a “000”
password).
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##” (the second “#” character refers to the current pro-
gram number between “0” and “24”).
6. Press the SELECT button until the display reads “PROGRAM
#6.”
7. Press the SET button.
8. Slide the program switch up.
9. Slide the program switch down.
10. Apply steps 3 to 5.
11. Press the SELECT button until the display reads “PROGRAM
#0.”
12. Press the SET button.
13. Press the FUNCTION button until the display reads “OUTPUT
1: INDICATING.”
14. Press the SET button until the display reads “OUTPUT #2: IN-
DICATING.”
15. Press the SELECT button until the display reads “TROUBLE
BELL.” Press the SET button.
16. Press the FUNCTION button until the display reads “ZONE 1
OUTPUTS.” The “v” is pointing to the first available output for
the zone indicated on the display. If the number is displayed,
it is turned on for that zone. If the number is not displayed, the
zone is turned off.
17. Press the FUNCTION button until the display reads “ZONE 3
OUTPUTS.”
18. Press the SELECT button. The “1” should appear under the
“v”.
19. Press the SET button twice. The panel is completely pro-
gramed except for the custom banner and zone messages. If
these messages are not desired, then slide the program switch
back up.
INPUTS:
1 conventional zones, 1 manual release zone, 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS:
1 general alarm bell, 1 trouble bell, 1 supervisory bell, and 1 solenoid release circuit.
OPERATION: Activation of either the conventional zone or the manual release will operate the solenoid release
circuit and the general alarm bell.
Activation of the waterflow zone will operate the general alarm bell.
Activation of either the low air zone or the supervisory zone will operate the supervisory bell.
A trouble condition (low battery, wiring problem, etc.) will operate the trouble bell.
When either Zone #1 or #2 is in alarm, Output #1 (general alarm) and Output #4 (solenoid release)
will
operate.
When Zone #3 is in alarm, Output #1 (alarm bell) will operate.
When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory bell) will operate.
When the panel is in a trouble condition, Output # 2 (trouble bell) will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel.
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #1
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Manual release
#3
Water
fl
ow
#4
Low Air
Supervisory
#1 ALARM
X
X
X
#2 WATERFLOW
#3 SUPERVISORY
X
X
#4 RELEASE
X
X
Summary of Contents for H PrePak
Page 3: ...Figure1 InstallationDimension 3 ...
Page 6: ...6 Figure3 WiringDiagram ...
Page 10: ...Figure5 WiringDiagram 10 ...
Page 11: ...11 Figure6 WiringDiagram ...
Page 12: ...Figure7 WiringDiagram 12 ...
Page 14: ...14 Figure8 WiringDiagram ...
Page 16: ...16 Figure9 WiringDiagram ...
Page 18: ...18 Figure10 WiringDiagram ...
Page 20: ...Figure6 DoubleInterlockPreaction ComponentIdentification 20 ...
Page 22: ...22 Figure12 WiringDiagram ...