background image

4.

1½” DELUGE RISER  ASSEMBLY, P/N 6503003001 and P/N 6503003007

(*)

, PARTS LIST

ITEM

NO.

PART NO.

DESCRIPTION

Number 

REQ’D

1

6201201500

Valve, Butterball, 1½” (BB-SCS02)

1

2

6201001500

Valve, Butterball, 1½” (BB-SC100)

1

3

98840170

Valve, Globe, ¾”

1

4

6871080000

Valve, Solenoid, 2”

1

5

98840160

Valve, Gauge, 3-Way, ¼”

2

6

98248001

Gauge, Pressure, Water

2

7

98543230

Nipple, ½” X 3” Lg. (Galv.)

1

8

96606607

Tee, ½” X ½” X ¼” (Galv.)

1

9

96606601

Tee,  ¾” (Galv.)

1

10

96606622

Tee, 1½” X ½” X 1½” (Galv.)

1

11

96606621

Tee, 1½” X ¾” X 1½” (Galv.)

1

12

96606625

Tee, 2” X 1½’  X 1½” (Galv.)

1

13

98543238

Nipple, 2” X Close (Galv.)

1

14

98543275

Nipple, 1½” X 2½” Lg. (Galv.)

1

15

98543274

Nipple, 1½” (thd X grv) X 4” Lg. (Galv.)

2

16

98543276

Nipple, 1½” X 3½” Lg. (Galv.)

2

17

98543288

Nipple, 1½” X 9½” Lg. (Galv.)

1

18

98543290

Nipple, ¾” X 8½” Lg. (Galv.)

1

19

98543279

Nipple, ¾” X Close (Galv.)

5

20

98543212

Nipple, ½” X Close (Galv.)

4

21

98543227

Nipple, ¼” X Close (Galv.)

2

22

95306209

Clamping Ring (OETIKER #515)

2

23

95306210

Clamping Ring (OETIKER #575)

2

24

95106905

Plate, Base

1

25

98543204

Nipple, ½” X 6” Lg. (Galv.) 

1

26

94616910

Nameplate, 1½” Deluge System 

1

27

94606910

Name Plate, Manual Emergency Station

1

28

6999991339

Switch, Pressure (Eps10-1)

1

6999992366

Switch, Pressure (Epsa10-2)

(*)

30

98614403

Plug, ¼” (Galv.)

2

31

98614401

Plug, ¾” (Galv.)

1

32

98750025

Cross, 2” X 1½”  (Zinc Coated)

1

33

98085680

Coupling, 1½” Grooved With ¾” npt Outlet

1

35

95200002

Plug, 1½” (Galv.)

1

36

95106904

Plate, Base, Manual Emer.  Station

1

37

98840109

Valve, Ball ½” 

1

38

78653100

Valve, Ball Drip,  Automatic Drain

1

39

75000075

Cup, Priming, ¾”  

1

40

98174400

Elbow, ½” Street (Galv.)

2

41

98048022

Bushing, ¾” X ½”  (Galv.)

1

42

98048025

Bushing, ¾” X ¼” (Galv.)

1

43

98174402

Elbow, ¾” (Galv.)

1

44

98174401

Elbow, ½” (Galv.)

1

45

98761651

Tee, ½” (Galv.)

2

46

98815200

Union, ½” (Galv.)

1

47

98750005

Cross, ¾” (Galv.)

1

48

98543216

Nipple, ½” X  3½” Lg. (Galv.)

1

49

98543228

Nipple, ½” X 4½” Lg. (Galv.)

1

50

98543209

Nipple, ½” X 2” Lg. (Galv.)

1

51

98840180

Valve, Check, ¾” 

1

52

98840181

Valve, Check, ½” 

1

53

98085668

Couping, Reducer 2” X 1½” (Galv.)

1

(*)

 Canadian Type

Summary of Contents for H Deluge Riser

Page 1: ...prinkler Co Inc 103 Fairview Park Drive Elmsford New York 10523 Model H Deluge Riser Assembly Bulletin 507 Rev D Bulletin 507 Rev D Instructions for Installation Operation Care and Maintenance 11 2 40mm Size Electric Actuation ...

Page 2: ...lve has opened water flows from the supply through the Deluge Riser into the piping system and to the alarm initiating water flow pressure switch After system shutdown and draining the Deluge Riser is eas ily reset without special tools by first restoring detection devic es to the ready condition Once the detection system is ready the releasing control panel can be reset which automatically resets...

Page 3: ...d and not leaking by performing Step 6 above The automatic drain valve Item 38 monitors internal leakage Push in on its plunger to be sure ball check is off its seat If no water appears the Deluge Riser Assembly is leak tight 1 2 3 4 5 6 7 1 2 3 Operation test Open the solenoid valve Item 4 us ing the procedure in Step 5 above Note Operation test will cause full flow into the deluge system unless ...

Page 4: ...5306209 Clamping Ring OETIKER 515 2 23 95306210 Clamping Ring OETIKER 575 2 24 95106905 Plate Base 1 25 98543204 Nipple X 6 Lg Galv 1 26 94616910 Nameplate 1 Deluge System 1 27 94606910 Name Plate Manual Emergency Station 1 28 6999991339 Switch Pressure Eps10 1 1 6999992366 Switch Pressure Epsa10 2 30 98614403 Plug Galv 2 31 98614401 Plug Galv 1 32 98750025 Cross 2 X 1 Zinc Coated 1 33 98085680 Co...

Page 5: ...xperienced contact Reliable Technical Services before any field adjustment is made Should replacement parts be needed use only Reliable supplied parts When ordering specify part number name size model and serial number of the unit Figure 2 ...

Page 6: ...Maximum retightening torque on cover screws is 135 inch lbs 15 25 N m Replacement Parts When ordering replacement parts kit specify part number P N 6999991583 Parts includ ed in each kit are marked with an asterisk See ex ploded view Figure 3 Maintenance of Emergency Station Valve This valve Item 2 is not field serviceable In the event that leakage is occurring it must by replaced with a new manua...

Page 7: ...em description and applicable codes for minimum requirements The valve must be inspected at least monthly for cracks corrosion leakage etc and cleaned repaired or re placed or replaced as necessary If leakage is suspected through the solenoid valve the valve diaphragms and seats should be inspected and if necessary repaired or replaced WARNING CLOSE SYSTEM CONTROL VALVE TURN OFF POWER SUPPLY AND D...

Page 8: ... Remote Annunciator 3 Alarm Annunciator A Model SSM24 8 24 VDC Polarized Bell Model SSM24 10 24 VDC Polarized Bell Model MA24 D 24 VDC Polarized Sounder Model MASS24LO 24 VDC Polarized Sounder Strobe Reliable 700 4 Trouble Annunciator A Model SSM24 6 24 VDC Polarized Bell Model MA24 D 24 VDC Polarized Sounder Reliable 700 5 Manual Emergency Station Elec A Model BNG 1 SPDT 1 2 Area Detection Model ...

Page 9: ...9 Installation Measurements ...

Page 10: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Reviews: