Reliable H Deluge Riser Instructions For Installation, Operation Care And Maintenance Download Page 2

2.

General

Model H 1½” (40mm) Deluge Riser  incorporates a solenoid 

operated diaphragm type valve as the primary valve in deluge, 
preaction, or special types of fire protection systems.

The valve is easily reset by external means which eliminates 

the need for removing the cover.

The trim is factory assembled for every Model H Deluge Ris-

er.  This trim provides valve supervising and waterflow alarm 
electric connections, pressure gauges, and system draining 
provisions.

Actuation by solenoid enables a full range of electrical detec-

tors to be used for remote sensing.

Operation

Model H 1½” (40mm) Deluge Riser employs a quick opening 

hydraulically operated, diaphragm actuated solenoid valve.

De-energized: supply pressure is retained at the solenoid 

valve inlet. Flow through the valve is prevented by a plunger 
closing off the diaphragm pilot orifice and a diaphragm sealing 
against the main orifice.

Energized: the plunger is lifted off the pilot orifice and vents 

the pressure behind the diaphragm.  The venting creates a 
pressure imbalance across the diaphragm, which causes the 
diaphragm to open the main orifice allowing flow through the 
solenoid valve.

Once the solenoid valve has opened, water flows from the 

supply through the Deluge Riser into the piping system and to 
the alarm initiating water flow pressure switch.

After system shutdown and draining, the Deluge Riser is eas-

ily reset, without special tools, by first restoring detection devic-
es to the ready condition.  Once the detection system is ready, 
the releasing control panel can be reset which automatically 
resets the solenoid valve.  Next, the water supply pressure can 
be restored and  the Deluge Riser will be reset.  The external re-
set feature of the Model H 1½” (40mm) Deluge Riser provides 
a means for simple, economical system testing which is one 
essential facet of a good maintenance program.

Technical Data

Rated working pressure 175 psi (12,1 bar). Minimum 
Supply Pressure: 20 PSI (1,4 Bar)

 Note:

 1 bar=100 kPa

End connections - American Standard Taper Pipe 
Threads per ANSI B2.1. Inlet and outlet 1½”. Drain ¾”.
Color-galvanized pipe and fittings with bronze valves.
Shipping Weight - 52 lbs. (23.3 Kg)
Friction Loss - expressed in equivalent length of  Sch. 40 
pipe, based on Hazen & Williams formula with C=120  is 
29 ft. (8.84m) for the Model H  Riser Assembly.
Installation position:  Vertical 
Listed by Underwriters Laboratories, Inc. special system 
water control valves - deluge type (VLFT). Listed by Un-
derwriters’ Laboratory of Canada.  NYC MEA 258-93-E.

1.

2.

3.
4.
5.

6.
7.

Figure 1 -  Model H Deluge Riser Assembly

Summary of Contents for H Deluge Riser

Page 1: ...prinkler Co Inc 103 Fairview Park Drive Elmsford New York 10523 Model H Deluge Riser Assembly Bulletin 507 Rev D Bulletin 507 Rev D Instructions for Installation Operation Care and Maintenance 11 2 40mm Size Electric Actuation ...

Page 2: ...lve has opened water flows from the supply through the Deluge Riser into the piping system and to the alarm initiating water flow pressure switch After system shutdown and draining the Deluge Riser is eas ily reset without special tools by first restoring detection devic es to the ready condition Once the detection system is ready the releasing control panel can be reset which automatically resets...

Page 3: ...d and not leaking by performing Step 6 above The automatic drain valve Item 38 monitors internal leakage Push in on its plunger to be sure ball check is off its seat If no water appears the Deluge Riser Assembly is leak tight 1 2 3 4 5 6 7 1 2 3 Operation test Open the solenoid valve Item 4 us ing the procedure in Step 5 above Note Operation test will cause full flow into the deluge system unless ...

Page 4: ...5306209 Clamping Ring OETIKER 515 2 23 95306210 Clamping Ring OETIKER 575 2 24 95106905 Plate Base 1 25 98543204 Nipple X 6 Lg Galv 1 26 94616910 Nameplate 1 Deluge System 1 27 94606910 Name Plate Manual Emergency Station 1 28 6999991339 Switch Pressure Eps10 1 1 6999992366 Switch Pressure Epsa10 2 30 98614403 Plug Galv 2 31 98614401 Plug Galv 1 32 98750025 Cross 2 X 1 Zinc Coated 1 33 98085680 Co...

Page 5: ...xperienced contact Reliable Technical Services before any field adjustment is made Should replacement parts be needed use only Reliable supplied parts When ordering specify part number name size model and serial number of the unit Figure 2 ...

Page 6: ...Maximum retightening torque on cover screws is 135 inch lbs 15 25 N m Replacement Parts When ordering replacement parts kit specify part number P N 6999991583 Parts includ ed in each kit are marked with an asterisk See ex ploded view Figure 3 Maintenance of Emergency Station Valve This valve Item 2 is not field serviceable In the event that leakage is occurring it must by replaced with a new manua...

Page 7: ...em description and applicable codes for minimum requirements The valve must be inspected at least monthly for cracks corrosion leakage etc and cleaned repaired or re placed or replaced as necessary If leakage is suspected through the solenoid valve the valve diaphragms and seats should be inspected and if necessary repaired or replaced WARNING CLOSE SYSTEM CONTROL VALVE TURN OFF POWER SUPPLY AND D...

Page 8: ... Remote Annunciator 3 Alarm Annunciator A Model SSM24 8 24 VDC Polarized Bell Model SSM24 10 24 VDC Polarized Bell Model MA24 D 24 VDC Polarized Sounder Model MASS24LO 24 VDC Polarized Sounder Strobe Reliable 700 4 Trouble Annunciator A Model SSM24 6 24 VDC Polarized Bell Model MA24 D 24 VDC Polarized Sounder Reliable 700 5 Manual Emergency Station Elec A Model BNG 1 SPDT 1 2 Area Detection Model ...

Page 9: ...9 Installation Measurements ...

Page 10: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...