background image

The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 132 

Rev

. B

Bulletin 132 

Rev

. B

Model GL 112
Quick Response
Upright and Pendent  
Sprinklers

Quick Response Sprinklers
(SIN R3226)Upright 
(SIN R3216) Pendent

Features

The Reliable Model GL 112 QR sprinkler offers 
the opportunity for:
1.  Compliance with FM requirements for QR 

Sprinklers to be used in Racks. The GL 112 
Upright uses the D-7 guard/shield. The GL 
112 Pendent can be used with the D-8 guard 
or the D-9 guard/shield. See Bulletin 208.

2.  Also for use as a ceiling sprinkler per FM 

Data Sheets 8-9.

3.  Pipe size reduction.
4.  Increasing densities with existing systems.
5.  Intended for use as a “Quick Response” 

storage sprinkler in hydraulic designed sys-
tems with a minimum pressure of 7 psi (0.5 
bar) in accordance with the area density 
curves of NFPA 13 applications.

6.  K- Factor = 11.2 (160)

Listings & Approvals:

Approved by Factory Mutual (FM) as a storage sprinkler.

Product Description

The Reliable Model GL 112 Quick Response sprinkler uti-

lizes a levered fusible alloy solder link in 165°F (74°C), 212°F 
(100°C).  The sprinkler has been designed to control high 
challenge fires in both palletized and rack storage occupan-
cies, utilizing relatively low water  pressures. This sprinkler 
is available with the standard ¾” NPT (R¾) thread  for new 
installation.

It has been proven in full scale fire testing, has complied 

with the applicable mechanical and hydraulic sections of the 
latest sprinklers standard, and has Factory Mutual Approval.

This product is intended for use as a “Quick Response” 

storage sprinkler in hydraulic designed systems with a mini-
mum pressure of 7 psi (0.5 bar) in accordance with the area 
density curves of NFPA 13* standards.

Design Criteria

The following criteria apply when designing an automat-

ic sprinkler system utilizing the Model GL 112 QR sprinkler 
for NFPA 13* applications.

•  Sprinkler spacing shall be a minimum of 6 ft. (1.8m)
•  Sprinkler discharge pressure for NFPA 13* standard 

and all Factory Mutual (FM) applications shall be a 
minimum of 7 psi (0,5 bar).

•  Factory Mutual (FM) Loss Prevention Data Sheets con-

tain requirements which differ from NFPA. The Model 
GL 112 is Approved by Factory Mutual for installations 
governed by  Data Sheets 8-9 and 2-0.

The Model GL 112 QR sprinkler is intended for standard 

flow. Pressure requirements and standard placement as 
specified for NFPA storage requirements. The Model GL 
112 QR sprinkler is not a “Large Drop” or “ESFR” sprinkler.

Temperature Ratings

Classi

fi

 cation

Sprinkler

Rating

Maximum Ambient 

Temperature

Frame 

Color

°F

°C

°F

°C

Ordinary

Intermediate

165
212

74

100

100
150

38
66

Uncolored

White

* For sprinkler standards prior to 1999 edition of NFPA 13,   use NFPA   
standards 231, 231C, 231D & 231F.

Model GL 112 QR Upright 3/4” NPT

Model GL 112 QR Pendent 3/4” NPT