Technical Data

Sprinkler 

Model

Sprinkler Inlet

Total

Adjustment

Nominal 

Ori

fi

 ce

Nominal

K Factor

Thread

Approvals

Sprinkler

Identi

fi

 cation  (SIN)

US

Metric

G5-56

Non Adjustable

¾” (19mm)

½” (15mm)

5.6

80

½” NPT (R½)

1,2,3,4,5

RA3415

G5-42

Non Adjustable

¾” (19mm)

7

/

16

” (10mm)

4.2

60

½” NPT (R½)

1

RA3413

G5-28

Non Adjustable

¾” (19mm)

3

/

8

” (10mm)

2.8

40

½” NPT (R½)

1,2

RA3411

For VdS Approval, temperature rating sprinkler 165°F/74°c and cover plate 135°F/57°C only!

Notice

FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS

NOTE:

1.  Testing has shown that use of a “nipple extension” will not affect the listing of the sprinkler.
2.  For RETROFIT installations, per 

NFPA 13 (2010) section 8.15.19.4,

 “which allows the use of nipples as the same pipe 

thread size as the existing outlet when revamping existing systems”.

3.  Do not exceed 8-18 ft-lbs of torque during installation.

3.

Summary of Contents for G5-28

Page 1: ...ring an at tractive appearance and 3 4 19mm of cover adjustment for ease of installation The small diameter cover plate assem bly is easily attached and blends into the ceiling concealing the most dependable fire protection available an automatic sprinkler system The Model G5 56 G5 42 and G5 28 are designed for use where aesthetic appearance is important Offices hospitals motels and restaurants ar...

Page 2: ...uids Remove any sprinkler that has been painted other than factory applied or damaged in any way Concealed sprinklers cover plates can not be painted in the field after installation or have any other coating applied other than the factory finish A stock of spare sprinklers should be maintained to allow quick replacement of damaged or oper ated sprinklers Prior to installation sprinklers should be ...

Page 3: ...2 8 40 NPT R 1 2 RA3411 For VdS Approval temperature rating sprinkler 165 F 74 c and cover plate 135 F 57 C only Notice FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS NOTE 1 Testing has shown that use of a nipple extension will not affect the listing of the sprinkler 2 For RETROFIT installations per NFPA 13 2010 section 8 15 19 4 which allows the use of nipples as the same pipe thread size as th...

Page 4: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Reviews: