14.

Installation Instructions

Model F3QR80 Dry sprinklers must only be installed in the 

following fittings:
1.  The side outlet of an ANSI B 16.3 class 150 (malleable 

or ductile) or ANSI B16.4 class 125 (cast) iron pipe 
tee

2.  The run outlet of an ANSI B 16.3 class 150 (malleable 

or ductile) or ANSI B16.4 class 125 (cast) iron pipe 
tee, with the side outlet plugged (wet-pipe systems 
only)

3.  Spears Manufacturing Company Brass Thread In-

sert Style or Special Reinforced Plastic Thread Style 
Listed adapter or tee (wet-pipe systems only) (gasket 
sealed outlets shall not be used)

4.  Any Listed CPVC sprinkler adapter or tee only in ac-

cordance with Fig. 9 and upon verification that the 
CPVC adapter or tee does not interfere with the sprin-
kler’s inlet (wet-pipe systems only) (gasket sealed 
outlets shall not be used)

Model F3QR80 Dry sprinklers must not be installed into 

couplings, elbows, welded outlets, or gasket sealed outlets. 
Installation of the Model F3QR80 Dry sprinkler is not recom-
mend in copper pipe systems, as this may reduce the life 
expectancy of the sprinkler.

In all dry-pipe system installations, the Model F3QR80 Dry 

sprinkler must be installed with protrusion into the fitting in 
accordance with Fig. 1 through Fig. 7 in this Bulletin.  Do not 
install Model F3QR80 Dry sprinklers with the standard (long) 
inlet fitting into CPVC fittings that have an internal obstruction 
(see Fig. 9); this will damage the sprinkler, the fitting, or both. 
Model F3QR80 Dry sprinklers are available with a short “PL” 
inlet fitting for installation on CPVC fittings of wet-pipe sprin-
kler systems only.

Model F3QR80 Dry sprinklers connected to wet-pipe sys-

tems must be installed with the Exposed Minimum Barrel 
Length required by Fig. 8 located in a Heated Area.

An orange protective clip is factory installed on the sprin-

kler to protect the glass bulb thermal element from dam-
age. The clip should remain in place during installation of 
the sprinkler and be removed when the sprinkler system is 
placed in service. 

Use the following steps for installation:

1.  Cut a hole in the wall or ceiling directly in-line with 

the outlet of the fitting. See the Installation Data table 
for the recommended hole diameter based on the es-
cutcheon or cover plate option selected.

2.  Apply pipe joint compound or PTFE tape to the male 

threads of the sprinkler’s inlet fitting.

3.  Install the sprinkler in the fitting using the installation 

wrench specified in the Installation Data table. The 
Model F3 and F3R wrenches are designed to be in-
serted into the groves in the sprinkler’s wrench boss 
as shown in Fig. 10. The Model XLO2 wrench is de-
signed to fit into the cup and engage the wrench boss 
as shown in Fig. 11. Do NOT wrench any part of the 
sprinkler assembly other than the wrench boss. When 
inserting or removing the wrench from the sprinkler, 

care should be taken to prevent damage to the sprin-
kler. The sprinkler is then tightened into the pipe fitting 
to achieve a leak free connection. The recommended 
minimum to maximum installation torque is 22 - 30 lb-
ft (30 – 40 N-m).
3a. Alternatively, where access to the outer tube of 

the sprinkler is available, the Model F3QR80 Dry 
sprinkler may be installed using a pipe wrench. 
The pipe wrench shall only be permitted to inter-
face with the galvanized steel outer tube portion of 
the sprinkler (Item #8 in Fig. 12). Do NOT wrench 
any other portion of the sprinkler assembly. A pipe 
wrench can install the sprinkler into the fitting with 
a large amount of torque; consideration should be 
given to the need for future removal of the sprin-
kler because the installation torque will have to be 
matched or exceeded to remove the sprinkler. The 
recommended minimum to maximum installation 
torque is 22 - 30 lb-ft (30 – 40 N-m).

4.  Standard and Model HB escutcheons can be in-

stalled by slipping the escutcheon over the can until 
the escutcheon is seated against the ceiling or wall.  
The Model FP escutcheon is installed by pressing 
or threading the escutcheon into the cup by hand; 
the escutcheon can be tightened against the ceiling 
or wall by turning the escutcheon in a clockwise di-
rection and removed by turning the escutcheon in a 
counter-clockwise direction. To install the Model CCP 
cover plate, first remove the protective clip. Install the 
Model CCP cover plate on the sprinkler by pressing 
or threading the cover plate into the cup by hand; the 
cover plate can be tightened against the ceiling by 
turning the cover plate in a clockwise direction and 
removed by turning the cover plate in a counter-
clockwise direction. 

5.  Remove the orange protective clip when placing the 

sprinkler system in service.

Summary of Contents for F3QR80 Dry Horizontal Sidewall

Page 1: ...in this Bulletin for available temperature ratings Model F3QR80 Dry sprinklers are intended for installation on wet pipe dry pipe or preaction sprinkler systems in ac cordance with NFPA 13 Model F3QR80 Dry sprinklers are available with a vari ety of escutcheon options as illustrated in Figs 1 through 3 and Figs 5 through 7 In addition Model F3QR80 Dry Pen dent sprinklers are also available with th...

Page 2: ...Listing per Local Law 33 2007 NYC Technical Data Maximum Listed and Approved Working Pressure 175 psi 12 bar Nominal K Factor 8 0 gpm psi1 2 115 L min bar1 2 Temperature Classification Glass Bulb Color Sprinkler Temperature Rating Cover Plate Temperature Rating Maximum Ceiling Temperature Listings and Approvals 1 Ordinary Orange 135 F 57 C 135 F 57 C 100 F 38 C cULus NYC Red 155 F 68 C Intermediat...

Page 3: ...n is in nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 1 Model F3QR80 Dry Pendent Sprinkler with Standard Escutcheon SIN RA6112 A Dim 2 to 36 51mm to 914mm in 1 4 6mm increments Sprinkler Guard Model C2 ...

Page 4: ...el HB Extended Escutcheon SIN RA6112 A Dim 3 to 36 89mm to 914mm in 1 4 6mm increments Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment provides 12 7mm to 12 7mm A dimension adjustment range Fig 2 4 ...

Page 5: ...ndent sprinkler with the Model FP escutcheon in ceilings which have positive pressure in the space above Fig 3 5 Model F3QR80 Dry Pendent Sprinkler with Model FP Recessed Escutcheon SIN RA6112 A Dim 31 2 to 36 89mm to 914mm in 1 4 6mm increments ...

Page 6: ...odel CCP Cover Plate SIN RA6112 A Dim 31 2 to 36 89mm to 914mm in 1 4 6mm increments Note Do not install the Model F3QR80 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have positive pressure in the space above Fig 4 6 ...

Page 7: ...adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 5 Model F3QR80 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon SIN RA6132 A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments for 1 connections or 2 to 36 51mm to 914mm in 1 4 6mm increments for 3 4 connections ...

Page 8: ...m 31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment provides 12 7mm to 12 7mm A dimension adjustment range Fig 6 ...

Page 9: ...mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note Do not install the Model F3QR56 Dry Horizontal Sidewall sprinkler with the Model FP escutcheon in walls which are positively pressurized with respect to the protected space Fig 7 ...

Page 10: ...10 Fig 8 ...

Page 11: ...Fig 9 11 ...

Page 12: ...Fig 11 Model XLO2 Wrench Fig 10 Model F3 or Model F3R Wrench 12 ...

Page 13: ... C31400 6 GLASS BULB GLASS W GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 INLET BRASS ALLOY PER UNS C35330 12 CAP BRASS ALLOY PER UNS C54400 13 SPRING WASHER SEAL PTFE COATED BERYLLIUM NICKEL 14 FLIP DISK BRASS ALLOY PER UNS C54400 15 CAN ESCUTCHEON PAINTED OR PLATED MILD S...

Page 14: ...s cutcheon or cover plate option selected 2 Apply pipe joint compound or PTFE tape to the male threads of the sprinkler s inlet fitting 3 Install the sprinkler in the fitting using the installation wrench specified in the Installation Data table The Model F3 and F3R wrenches are designed to be in serted into the groves in the sprinkler s wrench boss as shown in Fig 10 The Model XLO2 wrench is de s...

Page 15: ...R80 Dry Standard Escutcheon 2 1 8 54 mm F3 or F3R HB Extended Escutcheon 2 1 2 64 mm XLO2 FP Recessed Escutcheon 2 1 2 64 mm CCP Cover Plate Pendent Only Maintenance The Model F3QR80 Dry Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25 Do not remove the factory applied thermally sen sitive wax fillet between the bulb supporting cup and the wrenching bos...

Page 16: ...ment connection Reliable offers a wide selection of sprinkler components Following are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Offices 800 848 6051 Sales Fax 914 829 2042 Corporate Offices www reliablesprinkler com Internet Address Manufactured b...

Reviews: