Summary of Contents for F3QR80 Dry Horizontal Sidewall

Page 1: ...in this Bulletin for available temperature ratings Model F3QR80 Dry sprinklers are intended for installation on wet pipe dry pipe or preaction sprinkler systems in ac cordance with NFPA 13 Model F3QR80 Dry sprinklers are available with a vari ety of escutcheon options as illustrated in Figs 1 through 3 and Figs 5 through 7 In addition Model F3QR80 Dry Pen dent sprinklers are also available with th...

Page 2: ...Listing per Local Law 33 2007 NYC Technical Data Maximum Listed and Approved Working Pressure 175 psi 12 bar Nominal K Factor 8 0 gpm psi1 2 115 L min bar1 2 Temperature Classification Glass Bulb Color Sprinkler Temperature Rating Cover Plate Temperature Rating Maximum Ceiling Temperature Listings and Approvals 1 Ordinary Orange 135 F 57 C 135 F 57 C 100 F 38 C cULus NYC Red 155 F 68 C Intermediat...

Page 3: ...n is in nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 1 Model F3QR80 Dry Pendent Sprinkler with Standard Escutcheon SIN RA6112 A Dim 2 to 36 51mm to 914mm in 1 4 6mm increments Sprinkler Guard Model C2 ...

Page 4: ...el HB Extended Escutcheon SIN RA6112 A Dim 3 to 36 89mm to 914mm in 1 4 6mm increments Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment provides 12 7mm to 12 7mm A dimension adjustment range Fig 2 4 ...

Page 5: ...ndent sprinkler with the Model FP escutcheon in ceilings which have positive pressure in the space above Fig 3 5 Model F3QR80 Dry Pendent Sprinkler with Model FP Recessed Escutcheon SIN RA6112 A Dim 31 2 to 36 89mm to 914mm in 1 4 6mm increments ...

Page 6: ...odel CCP Cover Plate SIN RA6112 A Dim 31 2 to 36 89mm to 914mm in 1 4 6mm increments Note Do not install the Model F3QR80 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have positive pressure in the space above Fig 4 6 ...

Page 7: ...adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 5 Model F3QR80 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon SIN RA6132 A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments for 1 connections or 2 to 36 51mm to 914mm in 1 4 6mm increments for 3 4 connections ...

Page 8: ...m 31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment provides 12 7mm to 12 7mm A dimension adjustment range Fig 6 ...

Page 9: ...mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note Do not install the Model F3QR56 Dry Horizontal Sidewall sprinkler with the Model FP escutcheon in walls which are positively pressurized with respect to the protected space Fig 7 ...

Page 10: ...10 Fig 8 ...

Page 11: ...Fig 9 11 ...

Page 12: ...Fig 11 Model XLO2 Wrench Fig 10 Model F3 or Model F3R Wrench 12 ...

Page 13: ... C31400 6 GLASS BULB GLASS W GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 INLET BRASS ALLOY PER UNS C35330 12 CAP BRASS ALLOY PER UNS C54400 13 SPRING WASHER SEAL PTFE COATED BERYLLIUM NICKEL 14 FLIP DISK BRASS ALLOY PER UNS C54400 15 CAN ESCUTCHEON PAINTED OR PLATED MILD S...

Page 14: ...s cutcheon or cover plate option selected 2 Apply pipe joint compound or PTFE tape to the male threads of the sprinkler s inlet fitting 3 Install the sprinkler in the fitting using the installation wrench specified in the Installation Data table The Model F3 and F3R wrenches are designed to be in serted into the groves in the sprinkler s wrench boss as shown in Fig 10 The Model XLO2 wrench is de s...

Page 15: ...R80 Dry Standard Escutcheon 2 1 8 54 mm F3 or F3R HB Extended Escutcheon 2 1 2 64 mm XLO2 FP Recessed Escutcheon 2 1 2 64 mm CCP Cover Plate Pendent Only Maintenance The Model F3QR80 Dry Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25 Do not remove the factory applied thermally sen sitive wax fillet between the bulb supporting cup and the wrenching bos...

Page 16: ...ment connection Reliable offers a wide selection of sprinkler components Following are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Offices 800 848 6051 Sales Fax 914 829 2042 Corporate Offices www reliablesprinkler com Internet Address Manufactured b...