013FG02A
Model F1S5-56, F1S5 LO and F1S5-56,
F1S5 LO Recessed Sprinklers
Application
Model F1S5-56, F1S5
LO and F1S5-56, F1S5
LO
Recessed sprinklers are used in fixed fire protection systems:
Wet, Dry, Deluge or Preaction. Care must exercised that the
orifice size, temperature rating, deflector style and sprinkler
type are in accordance with the latest published standards
of the National Fire Protection Association or the approving
Authority Having Jurisdiction Installation.
Installation
Model F1S5 Series sprinklers are special response
sprinklers intended for installation as specified in NFPA 13.
They must also be installed with the Model D Sprinkler
Wrench specifically designed by Reliable for use with these
sprinklers.
The Model F1S5-56 and F1S5 LO Recessed Sprinklers
are to be installed with a maximum recess of
3
/
4
inch
(19 mm). The Model F1, F2 and FP Escutcheons illustrated
are the only recessed escutcheon to be used with the Model
F1S5-56 and F1S5 LO Pendent Sprinklers. The use of any
Fig. 1
Fig. 2
Model F1S5-56 F1/F2
Model F1S5-56 FP
Model F1S5-56 Recessed Pendent Sprinkler
Model F1S5 Large Orifice Recessed Pendent Sprinkler
Installation Wrench:
Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Orifice
Thread Size
K Factor
Sprinkler
Height
Sprinkler Identification
(1)
RTI
c
(fts
1
/
2
)
[ms
1
/
2
]
US
Metric
1
/
2
” (15 mm)
1
/
2
” NPT(R
1
/
2
)
5.6
80
2.25” (57 mm)
SP
(2)
(110-150)
[60-80]
Model F1S5 Large Orifice Recessed Pendent Sprinklers
(3)
(90-150)
[50-80]
20 mm
R
1
/
2
8.0
115
58 mm
SP
(1)
c= 1.09 (ft/s)
1
/
2
[0.60 (m/s)
1
/
2
]
(2)
VdS Approval for 155 °F (68 °C), 175 °F (79 °C) and 200 °F (93 °C) only.
(3)
Currently not VdS Approved.
other recessed escutcheon will void all approvals and negate
all warranties. When installing Model F1S5-56 and F1S5 LO
Recessed Pendent use the Model GFR2 Sprinkler Wrench.
Any other type of wrench may damage these sprinklers.
Note:
A leak tight sprinkler joint can be obtained with a torque
of 8-18 ft-lb (10.8 - 24.4 N-m). Do not tighten sprinklers over
maximum recommended torque. It may cause leakage or
impairment of the sprinklers.
Glass bulb sprinklers have orange covers to protect
the bulb during the installation process. REMOVE THIS
PROTECTION ONLY AFTER THE SYSTEM HAS BEEN
HYDROSTATICALLY TESTED AND, WHEN APPLICABLE,
THE ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers are
in place.
2
1
/
4
” HOLE DIA.
(57.2 mm)
1
15
/
16
” DIA. (49.2 mm)
1” x
1
/
2
” REDUCER
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER
WRENCH BOSS
ADJUSTMENT
(1)(2)
2
27
/
32
” DIA.
(72.2 mm)
FACE OF FITTING TO
CEILING DIMENSION
(1)
1
/
8
”
(3.2 mm)
“A”
(1)
1” x
1
/
2
” REDUCER
FACE OF FITTING TO
CEILING DIMENSION
(1)
“A”
(1)
ADJUSTMENT
(1)
CELING
(1) REFER TO FP ESCUTCHEON DATA TABLE FOR DIMENSIONS
2
5
/
8
” DIA. (66.7 mm)
HOLE IN CEILING
2
5
/
16
” DIA. (58.7 mm) CUP